Products catalog

Industrial circuit breakers

  • Industrial circuit breakers (MCCB) 16–800 A

    For an incomer, a distribution board or a high-power feeder – select by current and short-circuit current, not “by eye”.

    What do you need? Choose – we’ll take you straight to the product:

    Feeder up to 100 A
    Pump, fan, small board – FMC1 16 / 40 A, FMC2 80 / 100 A
    100 A FMC2 →
    100–250 A
    Workshop board, compressor, boiler room – FMC3, Icu 50 kA
    160 A FMC3 →
    250–400 A
    Building or farm incomer, main switchboard – FMC4, Icu 50 kA
    400 A FMC4 →
    400–800 A
    Transformer substation outgoing feeder, large incomer – FMC5 / FMC6
    630 A FMC5 →
    Precise protection required
    Adjustable electronic trip unit: 100–250 A or 160–400 A
    400 A electronic →
    Signalling, remote control
    Position contacts, releases, motor operator – selected by frame FMC1–FMC6
    FMC accessories →

    All types: up to 40 A (FMC1) · 250 A (FMC3) · 800 A (FMC6) · 250 A adjustable · with rotary handle · shunt trips · alarm contacts · motor operators · terminals

    Kibirkštis Fazė
    Not sure what Icu you need, or whether to choose FMC4 or FMC5 for 400 A? Turbo guide – below the product list. Or ask us – we’ll select it to suit your diagram.
    Read more
  • Turbo guide: how to select an industrial moulded-case circuit breaker (MCCB)

    An industrial moulded-case circuit breaker (MCCB, moulded case circuit breaker) protects cables and equipment against overload and short circuit. It is designed for higher currents than a miniature circuit breaker, and its ultimate breaking capacity Icu in this group ranges from 18 to 85 kA, depending on the model. A correctly selected breaker works for years. One chosen “by eye” either trips constantly or, worse still, fails to trip when it must.

    Blue – information Green – benefit to you Orange – ⚠ check Red – ⚡ safety and mistakes

    What do you need? Quick selection

    Situation Solution Where to look
    Separate feeder up to 100 A (pump, fan, small board) FMC1 (16 or 40 A, Icu 25 kA) or FMC2 (80 or 100 A, Icu 35–36 kA) 40 A · 100 A
    Board or high-power equipment feeder 100–250 A FMC3, Icu 50 kA (100, 125, 160, 200, 225, 250 A) 160 A · 250 A
    Building, farm or workshop incomer 250–400 A FMC4, Icu 50 kA (250, 315, 350, 400 A) 400 A FMC4
    Transformer substation outgoing feeder, large incomer 400–800 A FMC5 (400, 500, 630 A, Icu 50 kA) or FMC6 (800 A) 630 A · 800 A
    Precise coordination with the cable or generator, or selectivity, is required Electronic trip unit: 250 A (Ir1 100–250 A) or 400 A (160–400 A, in 1 A steps, Icu 85 kA) 250 A · 400 A
    The breaker is mounted inside the enclosure, but must be operated through the door Circuit breaker with rotary (door-mounted) handle 50 A, IP40
    Status must be visible in the control room, or the breaker must be tripped remotely or by a fire alarm signal Auxiliary / alarm contacts, shunt trip, motor operator – by frame Accessories table ↓
    What you gain by selecting correctly
    • The cable does not overheat, and the breaker does not trip for no reason under normal load.
    • During a short circuit the breaker safely interrupts the current and, if Ik does not exceed Ics, remains fit for further service.
    • With selectivity, only the faulty feeder trips – not the whole building.
    • Accessories (contacts, releases, motor operator) fit straight away, as they are selected for the same frame.

    Miniature circuit breaker or MCCB?

    Feature Miniature circuit breaker (MCB) Industrial MCCB
    Standard EN 60898-1 (household and similar use) IEC/EN 60947-2 (industrial equipment)
    Current Usually up to 63–125 A In this group 16–800 A
    Breaking capacity Typically 4.5 / 6 / 10 kA In this group Icu 18–85 kA
    Mounting DIN rail Usually bolted to a mounting plate, connected with cables or busbars
    Accessories and adjustment Limited Contacts, releases, motor operator; adjustable settings on electronic models
    Simple rule: if the current exceeds 125 A, or the short-circuit current at the point of installation exceeds the MCB’s breaking capacity (e.g. close to a transformer) and cascade (back-up) protection per the manufacturer’s tables is not ensured – you need an MCCB.

    Selection in 4 steps

    1. Current In
    Ib ≤ In ≤ Iz: load current ≤ breaker rated current ≤ cable current-carrying capacity
    →
    2. Icu
    Icu ≥ maximum short-circuit current Ik at the point of installation
    →
    3. Trip unit
    Thermal-magnetic or adjustable electronic
    →
    4. Accessories and connection
    Contacts, releases, motor operator, terminals – for the same frame
    How to calculate the load current (3-phase, 400 V)
    Ib = P / (√3 × U × cos φ). Example (general load, not a motor): 110 kW, cos φ 0.9 → 110,000 / (1.732 × 400 × 0.9) ≈ 176 A. A 200 A breaker is suitable if the cable current-carrying capacity Iz is at least 200 A.
    For motors: Ib = P / (√3 × U × cos φ × η), or take the rated current from the motor nameplate. The starting current is 6–8 times the rated current, so the instantaneous protection threshold must be above the starting peak – otherwise the breaker will trip when the motor starts.

    FMC frames and currents

    The frame determines the dimensions, terminal size and which accessories fit. Always select accessories by the frame designation (FMC1–FMC6), not just by current.

    Frame Currents in the group Icu (400 V) Typical location
    FMC1 16, 40 A 25 kA Separate feeders, equipment
    FMC2 80, 100 A 35–36 kA Sub-distribution boards
    FMC3 100–250 A 50 kA Workshop boards, high-power equipment
    FMC4 250–400 A 50 kA Building incomers
    FMC5 400–630 A 50 kA Large incomers, substation outgoing feeders
    FMC6 800 A see product page Transformer substation outgoing feeder
    ⚠ 400 A is available in both the FMC4 and FMC5 frames. FMC5 is larger, its terminals are wider and its accessories are different. If you plan to increase capacity to 500–630 A in future or connect heavy cables, choose FMC5.

    Icu and Ics – what’s the difference

    Icu – ultimate breaking capacity
    The maximum short-circuit current the breaker can interrupt. After such an interruption the breaker may be damaged and unfit for further use – it must be inspected or replaced.
    Ics – service breaking capacity
    The current after interrupting which the breaker remains fit for further service. Stated in kA or as % of Icu (e.g. 50 %, 75 %, 100 %).

    Example from our product page: FMC3 160 A – Icu 50 kA, Ics 25 kA (400 V). If Ik = 20 kA at the point of installation, this breaker is suitable even on the basis of Ics. For critical incomers (hospitals, production lines), choose a breaker with Ics ≥ Ik.

    How to quickly estimate Ik at a transformer
    Ik ≈ In(transf.) × 100 / uk %, where In = S / (√3 × U). Example: 630 kVA, 400 V, uk 6 % → In = 630,000 / (1.732 × 400) ≈ 909 A → Ik ≈ 909 × 100 / 6 ≈ 15 kA directly at the transformer terminals. This is an upper limit – the calculation ignores the impedance of the high-voltage network. The further along the cable, the lower Ik. Oil-immersed 630 kVA transformers often have uk = 4 % – then Ik ≈ 23 kA. The Ik values of transformers operating in parallel add up. The exact value is provided by the designer or the network operator.

    Thermal-magnetic or electronic trip unit

    Level What it is Suitable for
    Thermal-magnetic (FMC1–FMC6 series) The thermal element protects against overload, the electromagnetic element against short circuit. Settings are usually fixed (on some models the thermal element is adjustable – see product page). Most feeders and incomers where there are no special selectivity requirements
    Electronic (250 A and 400 A with LCD) A microprocessor measures the current; settings are adjustable. The 250 A model has long-time (L), short-time delay (S) and instantaneous (I) protection; for the 400 A model functions, see the product page. Incomers, generators, where coordination with the cable or selectivity is required

    Settings of the adjustable 250 A breaker per product page: Ir1 100–250 A, t1 12–150 s, short-time protection Ir2 2–12 × Ir1 with delay t2 0.06–0.3 s, instantaneous Ir3 4–14 × Ir1. The long-time protection of the 400 A breaker is adjustable 160–400 A, in 1 A steps. For other settings, see the product page.

    Tripping characteristics: how to read the time–current curve

    The curve shows how long the breaker takes to trip at a given current. Both axes are logarithmic. On the left – small overloads that the breaker tolerates for minutes or hours; on the right – a short circuit, which it interrupts within hundredths of a second.

    10,000 s1000 s100 s10 s1 s0.1 s0.01 s 1 × In10 × In100 × In Current (multiple of In) 1 – thermal (overload) 2 – instantaneous (typically 8–12 × In) S – with delay → I Thermal-magnetic Electronic (L-S-I)

    Illustration to explain the principle – not the curve of a specific model. The exact curve can be found in the manufacturer’s datasheet.

    Zone What happens What it means in practice
    1 – Thermal (overload) Per IEC/EN 60947-2: at 1.05 × In the breaker does not trip; at 1.30 × In it trips within 1 h (In ≤ 63 A) or 2 h (In > 63 A). The greater the overload, the faster it trips. Short overloads (starting, peaks) do not cause trouble; a sustained overload is cleared before the cable overheats
    2 – Instantaneous (short circuit) Once the Im (Ii) threshold is exceeded, the breaker trips without intentional delay – within ~10–20 ms. For thermal-magnetic distribution MCCBs the threshold is typically about 10 × In, with a tolerance usually of ±20 %. The short-circuit current at the end of the feeder must exceed Im with a margin
    L-S-I (electronic) L – long-time (Ir, t1), S – short-time delay (Isd, t2), I – instantaneous (Ii). Each threshold and time can be set. The curve can be “shifted” to suit the cable, generator or downstream breakers

    Comparison with miniature circuit breakers (EN 60898-1)

    Characteristic Instantaneous tripping Typical load
    B 3–5 × In Long feeders, lighting, sockets, low starting currents
    C 5–10 × In General purpose, small motors, LED with drivers
    D 10–20 × In Transformers, compressors, high starting currents
    Thermal-magnetic MCCB Typically ~10 × In (fixed or adjustable – see manufacturer’s data) Distribution boards, incomers, high-power equipment

    MCCBs are not designated by the letters B/C/D: their instantaneous protection threshold is stated as a multiple of In (e.g. 10 × In) or, on electronic models, is set by the user.

    ⚠ Long feeder – check the minimum short-circuit current
    A fault at the end of the feeder must be cleared by the instantaneous protection. Therefore the minimum short-circuit current at the end of the feeder (Ik min, phase–PE) must exceed Im with a tolerance margin (≈ 1.2 × Im). Example: 160 A breaker with Im ≈ 10 × In = 1600 A → Ik min ≥ ~1920 A is required. If the cable is long and Ik min is lower, the breaker will clear the fault by the thermal element only – within seconds or longer. In that case: a larger cable, an electronic breaker with a lower Isd / Ii, or a designer’s solution.
    We do not currently state the exact Im multiple and curve for FMC thermal-magnetic breakers on the product pages. If your project requires them – ask us and we’ll send the manufacturer’s data.

    Accessories: contacts, releases, motor operator, terminals

    Accessory What it does Frames in the group
    Auxiliary contact Indicates the breaker position (on / off) – for an indicator lamp, PLC, control room FMC1–FMC5 (1NO+1NC, left- and right-hand), FMC6 (2NO+2NC, left-hand)
    Alarm contact Signals that the breaker has gone to the “tripped” position – due to overload, short circuit or a shunt trip command. It does not signal manual switching off FMC1, FMC3, FMC4 (left-hand), FMC2 (right-hand)
    Shunt trip (230 V) Trips the breaker on a remote command (fire alarm system, dispatcher). Requires a reliable control supply; for emergency stopping, where the breaker must trip on loss of voltage, choose a solution per the design (e.g. an undervoltage release) FMC2–FMC6
    Motor operator (230 V) Motor drive – switches the breaker on and off remotely (ATS, control-room operation) FMC1–FMC4
    Spreader / extension terminals Spreader – for connecting larger cables or busbars; extension (straight) – extend the terminals FMC2–FMC6, set of 3 pcs
    ⚠ Left-hand and right-hand accessories are mounted on different sides of the breaker. Before ordering, check which side is free and how many accessories fit in the same frame. If the accessory you need for your frame is not listed – ask us and we’ll order it.

    ⚠ What to check before buying

    Kibirkštis
    Kibirkštis: “They said 250 A was needed, so I took 250 A. Nobody told me the cable was too thin for that current…”
    What to check Why
    Cable current-carrying capacity Iz The breaker protects the cable: In must not exceed Iz
    Short-circuit current Ik at the point of installation Icu must not be lower – otherwise the breaker may fail to clear the fault
    Voltage and number of poles FMC breakers are 3P – the neutral (N) is not switched by the breaker. Icu depends on voltage: at 690 V it is lower than at 400 V
    Cable cross-section and terminal size A heavy cable may not fit – spreader terminals are available for this
    Frame (FMC1–FMC6) for accessories An accessory for another frame will not fit – accessories are not universal
    Ambient temperature in the switchboard The operating range is usually −25…+55 °C. Thermal protection is calibrated at the temperature stated by the manufacturer (often +30 or +40 °C) – in a hotter board it will trip earlier, so a current derating factor applies

    ✗ Most common mistakes

    Mistake Consequence
    Breaker selected by load without checking the cable The cable overheats, but the breaker does not trip
    Icu too low close to a transformer The breaker may disintegrate during a short circuit
    Incoming and outgoing breakers with the same current rating Both may trip during a fault – the entire site loses power
    Accessories ordered by current rather than by frame They do not fit and have to be returned and reordered
    Shunt trip supply taken downstream of the same breaker On loss of supply the shunt trip cannot operate, and after tripping the alarm and automation systems no longer work. Supply it from a reliable source (upstream of the breaker, UPS, 24 V DC)
    Long feeder: Ik at the end of the feeder lower than the instantaneous protection threshold Im The fault is cleared by the thermal element only – within seconds or longer; danger to people and the cable
    ⚡ Terminals not tightened or under-tightened The contact heats up, insulation burns, and a fire may start
    Fazė
    ⚡ Safe installation – Fazė’s tip
    Install the breaker only after isolating it and verifying that there is no voltage. Lock off the incomer (LOTO). Tighten the terminals to the torque specified by the manufacturer using a torque wrench. Cable lugs must match the cross-section and terminal width. After commissioning, under load, it is worth checking the connections with a thermal imaging camera – you will spot an overheating contact before it burns out. Work must be carried out by a qualified electrician.
    ☝ Elsprendimai.eu recommends

    Diagram: selectivity – wrong and right

    Kibirkštis
    Kibirkštis: “One compressor failed, and the whole workshop went dark. Why?”
    Fazė
    Fazė: “Because the incoming breaker tripped together with the feeder breaker. Look at the diagram.”
    ✗ WRONG
    ① Incomer 250 A, thermal-magnetic
    ↓
    ② Feeder 250 A
    Feeder 100 A
    Feeder 100 A
    ↓ ⚡ short circuit
    ③ Both ② and ① trip
    ✓ RIGHT
    ① Incomer 250 A, electronic: S with delay, I – maximum setting
    ↓
    ② Feeder 100 A
    Feeder 100 A
    Feeder 40 A
    ↓ ⚡ short circuit
    ③ Only ② trips, the other feeders keep running
    Why – explanation by diagram numbers
    1. Wrong ①–②: both breakers have the same current rating and both have instantaneous protection only. The short-circuit current exceeds the instantaneous threshold of both, so both trip almost simultaneously.
    2. Wrong ③: when the incomer trips, the healthy feeders also lose power.
    3. Right ①: the ratio of incomer to feeder current ratings is at least ~2 (250 A / 100 A = 2.5). The incomer’s short-time protection (S) operates with a delay (e.g. t2 0.1–0.2 s), and the instantaneous protection (I) is set to maximum. Within the delay time the feeder breaker has time to clear the fault.
    4. Right ②–③: only the faulty feeder trips – but only as long as the fault current does not exceed the incomer’s instantaneous protection threshold. For this 250 A breaker that is at most 14 × Ir1 ≈ 3.5 kA. When Ik is higher (close to a transformer often 10–25 kA), the incomer will trip too: in that case selectivity is ensured only by the manufacturer’s selectivity tables or by design.
    ⚠ The diagram is for guidance only. Check settings and wiring against the manufacturer’s instructions and the design. Installation is carried out by, and is the responsibility of, a qualified electrician. UAB „Elektrotechnikos sprendimai“ accepts no liability for connection or possible errors.

    FAQ

    Kibirkštis: The feeder needs 250 A – will a miniature circuit breaker do?

    Fazė: No. Miniature circuit breakers are usually rated up to 125 A, so a 250 A current requires an MCCB. Most importantly, In must not exceed the cable current-carrying capacity, and Icu must not be lower than the short-circuit current at that point.

    Kibirkštis: What is the difference between Icu and Ics?

    Fazė: Icu is the maximum current the breaker can interrupt, but it may be damaged afterwards. Ics is the current after interrupting which it remains fit for service. Icu is stated on the product page; if Ics is not stated – ask us and we’ll confirm it.

    Kibirkštis: 400 A is available in both FMC4 and FMC5. Which one should I choose?

    Fazė: If 400 A will be enough in future too and the cables are standard – FMC4. If you plan to expand to 500–630 A or connect larger cables and busbars – FMC5. The accessories for the two frames are different.

    Kibirkštis: Can I also switch the neutral with the same breaker?

    Fazė: No, FMC breakers are 3-pole. If the design requires the neutral to be switched, you need a 4P breaker – ask us and we’ll make an offer.

    Kibirkštis: When is it worth paying more for an electronic trip unit?

    Fazė: When the breaker protects an incomer, generator or transformer, when precise coordination with the cable is required, or when selectivity is important. For a separate feeder, thermal-magnetic is usually sufficient.

    Kibirkštis: Which characteristic – B, C or D – do these breakers have?

    Fazė: The letters B/C/D designate miniature circuit breakers. The MCCB instantaneous protection threshold is stated as a multiple of In – for thermal-magnetic distribution breakers typically about 10 × In, i.e. roughly between C and D. On electronic breakers you set it yourself.

    Kibirkštis: What is the difference between an auxiliary contact and an alarm contact?

    Fazė: An auxiliary contact shows whether the breaker is on or off. An alarm contact signals that the protection or the shunt trip has operated – it does not signal manual switching off. This lets the dispatcher immediately distinguish a fault from a planned shutdown.

    Sources: IEC/EN 60947-2 (low-voltage circuit breakers); IEC 60364-4-43 (protection against overcurrent, Ib ≤ In ≤ Iz); EN 60898-1 (miniature circuit breakers); technical data from elsprendimai.eu product pages (FMC3 160 A, FMC3E 250 A, FMC4Ei 400 A). Checked 2026-10-15.

    Send us your diagram – we’ll select the breaker and accessories

    State the load, cable and transformer rating or Ik. We’ll reply with the frame, Icu and accessories you need, and give you a price.

    Get a quote →
    Price 169.82 € VAT incl.
    ( 140.35 € VAT excl. )
    Price 104.04 € VAT incl.
    ( 85.98 € VAT excl. )
  • Subscribtion to new arrivals

    privacy policy

    Information