Product Catalog
- Security and Surveillance Systems | accessories
- Lighting solutions for industrial | commercial | residential | outdoor environments | accessories
- Automation and Control Systems
- Smart Automated Products | Control | Transmission | Detection
-
Electrical distribution and installation
- Reactive Power Compensation Devices
-
Electrical power | power cables | wires with copper conductors
- Copper power cables CYKY-L (CYKY-J)
- Copper power supply cables KH05VV-U (NYM-J)
- Copper power supply cables BVV-LL
- Copper power supply cables H03VV-F, H05VV-F
- Copper power supply cables halogen-free NHXMH-J
- Copper power supply cables BVV-PLL
- Copper power supply cables BVV-P
- Copper power supply cables BVV-F, BVV-PL
- Copper power supply cables halogen-free BZ1Z1-P
- Copper power supply wires H05V2-K, H07V2-K
- Copper power supply wires H05V-K
- Copper power supply wires H07V-R, H07V2-R
- Copper power supply wires H07V-K
- Copper power supply wires H05V-U, H07V-U, H05V2-U, H07V2-U
- Halogen-free copper power supply cables H07Z1-K
- Aluminum power supply cables
- Computer power supply cables
- Special purpose power supply cables
- Copper | vintage | retro style braided cables
- Power transmission busbar
- Power supply cables / Leftovers
- Accessories for power supply cables
- Electrical Distribution Panels, Boxes & Accessories
- Modular equipment installed in electrical distribution boxes | panels
- Smart electrical network analyzers
- Reliable power management | stabilization | control | uninterrupted supply
- Fuse holder blocks
- Fuse disconnectors
- Fuses
- Electrical installation components
- Electric current transformers
- For domestic | professional use Extension cords | power supply extensions
- Industrial | domestic socket outlets | plugs | adapters for electricity supply
- High Voltage Equipment | Components 6kV | 10kV | 12kV | 20kV
- Underground Power Transmission | Overhead Power Lines
- Surge Protection and Lightning Protection
- Solar Energy Generation and Management Equipment
- HVAC control solutions for heating and ventilation
- Accessories for cars
- Workplace Safety | Electrical Safety Equipment | LOTO
- Technical maintenance | service equipment | fire protection solutions
- Emergency safety | hygiene | sanitary solutions
- Other products
- Quality used products
Copper power supply cables BVV-P
-
Copper cables BVV-P (YDYP). These cables are designed for fixed electrical installations, with wires laid under plaster or in channels intended for electrical installations, suitable for installation in wet and dry areas. The conductor is made of annealed copper wire, flexible and convenient for connecting conductors to plug socket contacts. The cables are not suitable for laying underground or in water.
-
Read moreElectrical installation guide · flat solid-core copper cables
BVV-P (YDYP): how to choose the right cable for a safe fixed installation?
The flat BVV-P cable with solid copper cores is used for fixed electrical installations in residential and commercial buildings. Learn how to choose it by number of cores, cross-section, load, run length and installation environment.
300/500 VRated voltageCuSolid copper coresPVC/PVCInsulation and sheath+70 °CMax. conductor operating temperatureFlatFor fixed installation
Kibirkštis asks, Fazė explains – from cable selection to electrical safety.Key point: BVV-P (YDYP) is a flat PVC cable with solid copper cores, intended for fixed indoor installation. When choosing, not only the core cross-section matters, but also the presence of PE, current-carrying capacity, circuit breaker parameters, voltage drop, cable installation method and the project's CPR requirements.Selection Suitable ⚠ Check ⚡ SafetyContents – go to the section you need- Quick selection
- Product matrix
- Construction and operating principle
- Where is it suitable and where not?
- Cores and PE
- Voltage class 300/500 V
- Load and cross-section
- Voltage drop
- Technical table
- Damp rooms and IP
- Cable comparison
- Installation
- Before buying
- Most common mistakes
- Fazė's recommendations
- Wrong / right diagram
- FAQ: Kibirkštis asks, Fazė answers
- Technical notes
What do you need? Quick BVV-P selection
Determine the cross-section and number of cores according to the circuit diagram, load and installation conditions. Selection guidelines are given below.
Need Option to consider Note Lighting with L, N and PE 3×1.5 mm² grey Check core colours, current and protection. Socket-outlet circuit with PE 3×2.5 mm² white Check current-carrying capacity, PE and installation method. Two-conductor circuit 2×1.5 mm² white Only in circuits where a separate PE is not required or is provided by a legitimate design solution. Damp indoor room BVV-P according to the design Proper protection of connections, boxes and equipment is important. Direct burial in soil Another cable type BVV-P is not a cable for direct burial in the ground. BVV-P range matrix
Below are direct links to specific elsprendimai.eu products. Other sizes and colours can be found in the BVV-P category.
Cable Colour Construction Product BVV-P 2×1.5 mm² White 2 solid Cu cores Open → BVV-P 3×1.5 mm² Grey 3 solid Cu cores Open → BVV-P 3×2.5 mm² White 3 solid Cu cores Open → The outer sheath colour does not indicate the functions of the cable cores. Before ordering, check the internal colour coding, length, construction and product availability.Construction and operating principle
1. Solid copper core
A solid annealed copper conductor for transmitting electrical energy in a fixed circuit.2. PVC core insulation
Separate core insulation reduces the risk of direct contact and electrical breakdown.3. Flat arrangement
The cores are arranged in one plane, making it easy to form straight installation runs.4. PVC outer sheath
Protects the insulated cores under the intended operating conditions.Operating principle: the copper conductor carries electric current from the supply to the load, the insulation electrically separates the conductors, and the outer sheath provides additional mechanical protection. Solid cores must not be continuously flexed during operation.
Where is BVV-P suitable and where not?
✓ Residential buildings
Lighting and other fixed circuits provided for in the design.✓ Socket-outlet circuits
When suitable PE, cross-section and protection are chosen.✓ Under plaster
In straight, properly designated electrical installation runs.✓ Electrical trunking
According to cable and trunking installation requirements.⚠ Damp indoor rooms
Assess room zones, protection and tightness of connections.⚠ Cables in thermal insulation
Assess reduced heat dissipation and current-carrying capacity.✗ Soil and water
Not intended for direct burial in the ground or immersion.✗ Moving equipment
Solid cores are not suitable for continuous dynamic flexing.2 or 3 cores? Phase, neutral and PE
2 coresTwo insulated copper conductors. There is no separate third core for protective PE, so this cable alone does not provide an L, N and PE circuit.
3 coresCan be used for an L, N and PE circuit if it has a proper green-yellow protective core and meets the cross-section and installation requirements.
⚡ Important: the green-yellow core is reserved for the protective conductor. A two-core cable cannot be considered a complete L, N and PE solution for an earthed socket. Check the core colour coding for the specific product.What does 300/500 V mean?
The cable voltage class U₀/U describes the rated voltage between conductor and earth and between conductors.
U₀ = 300 VRated voltage between conductor and earth.
U = 500 VRated voltage between conductors.
The 300/500 V voltage class may be suitable for a 230/400 V network, but this does not in itself mean that a two- or three-core cable is suitable for any three-phase circuit. The number of cores, purpose and load must match the design.
Cross-section, power and load current
The cross-section is selected taking into account the conductor current-carrying capacity, installation method, grouping, temperature, protective device and voltage drop.
Resistive load Current at 230 V Parameter to check 100 W 0.43 A Circuit purpose 500 W 2.17 A Cable cross-section 1000 W 4.35 A Protection characteristics 2000 W 8.70 A Continuous current-carrying capacity 3000 W 13.04 A Installation method and cooling 3680 W 16.00 A Entire circuit and circuit breaker Calculation: I = P / (U × cos φ)For a resistive load at cos φ = 1, 2300 W / 230 V = 10 A. This is not a formula for determining the current-carrying capacity of BVV-P cables.
Resistance of solid copper cores
Cross-section Maximum DC resistance at 20 °C 1.0 mm² 18.1 Ω/km 1.5 mm² 12.1 Ω/km 2.5 mm² 7.41 Ω/km 4.0 mm² 4.61 Ω/km Values apply to class 1 solid plain copper conductors. These are conductor electrical resistances, not a current-carrying capacity table. 4 mm² is included only for comparison of cross-sections; its availability in this group is not confirmed.
Cable length and voltage drop
Example of a single-phase 230 V circuit at 10 A current, resistive load, conductor temperature +20 °C. The combined length of phase and neutral is calculated.
One-way distance 1.5 mm² 2.5 mm² 4.0 mm² 10 m 2.42 V 1.48 V 0.92 V 20 m 4.84 V 2.96 V 1.84 V 30 m 7.26 V 4.45 V 2.77 V 50 m 12.10 V 7.41 V 4.61 V Formula: ΔU ≈ 2 × L × I × R / 1000L – one-way length in metres, I – current in amperes, R – resistance of one core in Ω/km.
The actual voltage drop depends on conductor temperature, load power factor, connections and other circuit parts. The calculation does not replace verification of current-carrying capacity and protective device operation.Technical characteristics table
Parameter BVV-P / YDYP Cable construction Flat, with common sheath Conductor Solid annealed copper Rated voltage 300/500 V Insulation PVC Sheath PVC Maximum continuous conductor temperature +70 °C Installation temperature −5 °C to +40 °C for the specified variants Operating temperature −30 °C to +70 °C for the specified variants Test voltage 2 kV for the specified variants Short-circuit temperature Up to +160 °C for the specified variants, short-time Bending radius More than 5 cable thicknesses for the specified variants Reaction to fire Eca for the specified products; check the DoP Use Fixed indoor installation ⚠ Temperature difference: a negative operating temperature does not mean the cable may be bent or installed under such conditions. The +160 °C short-time short-circuit value is not a permitted continuous temperature.Damp rooms, IP and cable protection
PVC insulation allows the cable to be used under the intended indoor installation conditions, but the cable must not be treated as a stand-alone IP65 or IP67 device. The protection of an electrical installation depends on the entire system – boxes, connections, entries, sockets and installation zone.
Location Assessment Dry room or office Suitable according to design and installation method Kitchen, auxiliary indoor room Suitable if connections and equipment are protected Bathroom Only according to zone and protection requirements Constant sun and UV The standard BVV-P purpose does not confirm suitability Soil, immersion Not suitable BVV-P, BVV-PLL, NYM-J or NHXMH-J?
Type Key difference Go to group BVV-P (YDYP) Flat, solid-core, PVC, fixed installation BVV-P → BVV-PLL (OMYp) Flat, flexible stranded, PVC BVV-PLL → KH05VV-U / NYM-J Different indoor installation construction; assess cores and sheath Copper cable catalogue → NHXMH-J Halogen-free fixed installation, CPR class assessed separately NHXMH-J → H03VV-F / H05VV-F Flexible connection cables, depending on the class of use H03VV-F / H05VV-F → Cables of the same cross-section are not automatically interchangeable. Construction, conductor class, rated voltage, CPR, PE and installation environment must be checked.
Installation and proper connection
1. Route location
Lay the cable in designated installation zones, observing building structure requirements.2. Mechanical protection
Protect from screws, drilling, sharp edges and crushing.3. Bending radius
Avoid sharp kinks and observe the radius specified for the product.4. Contact terminals
Use terminals suitable for solid copper cores and the selected cross-section.5. Cable grouping
Assess the additional thermal effect in shared conduits and trunking.6. Final inspection
Check PE continuity, insulation resistance, condition of connections and operation of protection.Solid cores: they are intended for reliable fixed installation. When making a contact, it is important not to damage the copper, not to break the core and to use the conductor type permitted in the connection equipment instructions. Continuous flexing is not permitted.What to check before ordering?
1. Number of cores
Is an L, N and PE system required?2. Cross-section
Is the current-carrying capacity sufficient?3. Run length
Does the voltage drop stay within the permitted value?4. Installation conditions
Will the cable be in trunking, under plaster, in thermal insulation?5. Fire class
Does the CPR class of the specific product suit the project?6. Length
Has a reserve for connections and route bends been allowed for?Most common mistakes
✗ Wrong ✓ Right Only a 2-core cable is used for an earthed socket. Provide a PE conductor in accordance with the design. A 25 A load is automatically assigned to 2.5 mm². Determine the current-carrying capacity according to installation conditions. Solid-core cable is continuously flexed. Use only for fixed installation. BVV-P is considered halogen-free. If LSOH is required, choose a cable designed for it. Undeclared UV resistance is taken for granted. For outdoor use, use an appropriately approved cable. Voltage drop on long lines is not assessed. Calculate the entire supply circuit. Fazė's and Elsprendimai.eu recommendations
Fazė advisesFirst choose the circuit diagram and protective conductor, then calculate the cross-section. Do not start with the question “how many amps can 2.5 mm² carry” – without installation and cooling conditions there is no single universal answer.
For lighting circuitsBVV-P 3×1.5 mm², if it matches the design.
For socket circuitsBVV-P 3×2.5 mm², after checking PE and load.
When flexible cores are neededBVV-PLL (OMYp), if the conditions of use are suitable.
When a halogen-free cable is neededNHXMH-J, checking CPR and DoP.
Diagram: wrong / right – socket-outlet circuit
✗ WRONG230 V panel↓BVV-P 2×1.5Only two cores, no PE↓Earthed socketNo separate protective conductor is provided.
✓ RIGHT230 V panel with PE↓3-core cable according to the designL, N, PE and suitable cross-section↓Earthed socketPE, current-carrying capacity and protection verified.
FAQ – Kibirkštis asks, Fazė answers
Practical questions on choosing BVV-P (YDYP) cables, solid cores, earthing, load, installation and alternatives.
Kibirkštis · question 1What is BVV-P (YDYP) cable?
FazėIt is a flat copper cable with PVC insulation and sheath, intended for fixed electrical installation. The solid copper cores are suitable for fixed circuit connections, and the flat shape is convenient for laying the cable under plaster or in suitable trunking.
Kibirkštis · question 2How does BVV-P differ from BVV-PLL?
FazėThe BVV-P core is solid – a single copper conductor. The BVV-PLL core consists of many fine copper wires, so it is more flexible. Both types can be used in a properly designed fixed installation, but terminal selection and installation features differ. View BVV-PLL →
Kibirkštis · question 3Is BVV-P 3×1.5 mm² suitable for lighting?
FazėYes, it is a common choice for lighting circuits if the number and colours of the cores match the diagram. Current-carrying capacity, circuit breaker parameters and voltage drop must also be checked. You can view BVV-P 3×1.5 mm² grey cable.
Kibirkštis · question 4Can 3×2.5 mm² be used for socket-outlet installation?
FazėOften yes. However, you must make sure that one core is intended for PE, that the cable meets the installation conditions and that the protective device is correctly coordinated with the circuit. BVV-P 3×2.5 mm² white →
Kibirkštis · question 5Can an earthed socket be connected with a 2×1.5 mm² cable?
FazėWith a two-core cable alone – no. An earthed socket requires a properly installed PE conductor. It is not permitted to replace PE with the neutral conductor or to connect it arbitrarily to a metal structure. Choose an L, N and PE solution that matches the design.
Kibirkštis · question 6Does a 2.5 mm² cable always carry 25 A?
FazėNo. Current-carrying capacity depends on installation method, cooling, thermal insulation, cable grouping, ambient temperature and other factors. A protective device cannot be selected from the cross-section alone. See the load explanation →
Kibirkštis · question 7Can BVV-P be installed under plaster?
FazėYes, this is one of its main uses. The cable must be properly installed in designated installation zones, protected from mechanical damage and not bent to a radius smaller than permitted.
Kibirkštis · question 8Can the cable be used in a damp room?
FazėYes, under the intended conditions, but safety is not determined by the cable sheath alone. Connections, boxes, sockets and entries must be suitable for moisture, and in bathrooms the protection zones and additional electrical safety requirements are important. The cable must not be arbitrarily assumed to have IP65 or IP67 protection.
Kibirkštis · question 9Can BVV-P be laid directly in the ground?
FazėNo, the BVV-P cables in this group are intended for fixed indoor installation, not for direct laying in soil or water. For such a route, a different cable with documented resistance to the specific environment is selected.
Kibirkštis · question 10Is this cable suitable for continuously moving equipment?
FazėNo. A solid core is not suitable for continuous flexing. Moving equipment requires a flexible cable selected according to motion cycles, bending radius and environmental exposure. Depending on the application, you can start with the H03VV-F / H05VV-F group, but not all of these cables are suitable for continuous dynamic movement.
Kibirkštis · question 11Is Eca class BVV-P halogen-free?
FazėNo. Eca is a reaction-to-fire class, which does not in itself confirm halogen-free properties. BVV-P is a PVC cable. If the project requires low smoke and a halogen-free construction, consider NHXMH-J and the CPR declaration of the specific product.
Kibirkštis · question 12How to choose the cable if the load is 50 metres away?
FazėYou need to know not only the length, but also the load current, protective device and installation method. For example, on a 50 m single-phase line at 10 A, a simplified +20 °C calculation for a 1.5 mm² solid copper conductor gives a drop of about 12.1 V, and for 2.5 mm² – about 7.41 V. The actual operating temperature and protective device operation must also be checked. See the voltage drop table.
Have another question? Specify the cable length, number of cores, load and installation location. Contact Elsprendimai.eu.Standards and important technical notes
When assessing cable suitability, the EN 60228 conductor parameters, LST HD 60364 principles of design and erection of electrical installations, and EN 50575 / EN 13501-6 reaction-to-fire requirements, where applicable to the specific product, are important.
Technical characteristics of related products at elsprendimai.eu:
- BVV-P 2×1.5 mm², white
- BVV-P 3×1.5 mm², grey
- BVV-P 3×2.5 mm², white
- Full range of the BVV-P category
Technical data consistencyBVV-P cable data may vary depending on cross-section, colour, production batch and specific product. Before use, check rated voltage, core colours, conductor construction, temperature limits, CPR class and installation conditions. Current-carrying capacity is not determined by nominal cross-section alone.
Disclaimer: technical tables and calculation examples are for information only. The final cable, protection and installation solution must be determined by qualified specialists according to the design and applicable requirements. UAB „Elektrotechnikos sprendimai“ is not liable for the consequences of improper selection or installation to the extent permitted by applicable law.Need BVV-P cables for a project?
Specify the required cross-section, number of cores, colour, length and installation conditions. We will help compare BVV-P with other copper cables and choose the right option.
Contact Elsprendimai.euCopper cables BVV-P are high-quality electrical cables made of copper, designed for use in indoor electrical installations. These cables feature excellent electrical conductivity properties, durability, and reliability, making them widely used in both industry and household applications.
Construction:
Conductor:
BVV-P cables are made from pure copper, ensuring efficient electrical power transmission.
The conductors are often multi-core, allowing for easier installation in confined spaces and various configurations.
Insulation:The cables have PVC (polyvinyl chloride) insulation, which protects against moisture, chemical exposure, and mechanical damage.
The insulation is fire-resistant, providing additional protection to ensure safety during use.
Specifications:Voltage Range:
BVV-P cables are designed for use at voltages up to 300/500 V, making them suitable for many residential and industrial applications.
Temperature Range:The cables typically operate in a temperature range from -15 °C to +70 °C, allowing for use in various environments.
Color Code:BVV-P cables use a standard color code: brown (phase), blue (neutral), green-yellow (earthing), ensuring proper connections.
Applications:Industry:
BVV-P cables are ideal for various industrial solutions, including automation systems, lighting systems, and other electrical devices requiring reliable conductivity.
Household Use:These cables are widely used in home lighting systems, electrical appliances, and energy transmission and distribution systems.
Construction Sector:The cables are used in the electrical installations of new and renovated buildings, both indoors and outdoors, ensuring safety and efficiency.
Advantages:High Electrical Conductivity: Due to the pure copper conductor, BVV-P cables ensure efficient energy transfer, reducing losses.
Durability: PVC insulation helps ensure the long-term service life of the cables and protects against external factors.
Easy Installation: Due to flexibility and various constructions, the cables are easy to install and adapt to different situations.
Safety: Resistance to moisture and chemicals ensures safe use in challenging conditions.
Copper cables BVV-P are an excellent choice for both industrial and household electrical solutions. Their reliability, durability, and excellent electrical conductivity properties ensure they meet the highest standards required for reliable energy transmission and distribution.1 - 1 of 1Copper cable 2x6mm² | flexible | flat | VVG 2x6 | (1m) | blackCode: VVG2X6JVVG 2x6 mm² flat electrical cable with two single-core flexible conductors made of annealed copper, designed for fixed electrical installations in residential, commercial, or industrial buildings. The PVC sheath and insulation provide excellent protection against mechanical impact and comply with strict safety standards. The cable offers great flexibility and easy installation both in electrical conduits and open installations.
Price 2.70 € VAT incl.( 2.23 € VAT excl. )
Subscribtion to new arrivals
Information