Products catalog

Copper power supply cables BVV-P

  • Copper cables BVV-P (YDYP). These cables are designed for fixed electrical installations, with wires laid under plaster or in channels intended for electrical installations, suitable for installation in wet and dry areas. The conductor is made of annealed copper wire, flexible and convenient for connecting conductors to plug socket contacts. The cables are not suitable for laying underground or in water.  

  • Electrical installation guide · flat solid-core copper cables

    BVV-P (YDYP): how to choose the right cable for a safe fixed installation?

    The flat BVV-P cable with solid copper cores is used for fixed electrical installations in residential and commercial buildings. Learn how to choose it by number of cores, cross-section, load, run length and installation environment.

    300/500 V
    Rated voltage
    Cu
    Solid copper cores
    PVC/PVC
    Insulation and sheath
    +70 °C
    Max. conductor operating temperature
    Flat
    For fixed installation
    Kibirkštis Fazė Kibirkštis asks, Fazė explains – from cable selection to electrical safety.
    Key point: BVV-P (YDYP) is a flat PVC cable with solid copper cores, intended for fixed indoor installation. When choosing, not only the core cross-section matters, but also the presence of PE, current-carrying capacity, circuit breaker parameters, voltage drop, cable installation method and the project's CPR requirements.
    Selection Suitable ⚠ Check ⚡ Safety

    What do you need? Quick BVV-P selection

    Determine the cross-section and number of cores according to the circuit diagram, load and installation conditions. Selection guidelines are given below.

    Need Option to consider Note
    Lighting with L, N and PE 3×1.5 mm² grey Check core colours, current and protection.
    Socket-outlet circuit with PE 3×2.5 mm² white Check current-carrying capacity, PE and installation method.
    Two-conductor circuit 2×1.5 mm² white Only in circuits where a separate PE is not required or is provided by a legitimate design solution.
    Damp indoor room BVV-P according to the design Proper protection of connections, boxes and equipment is important.
    Direct burial in soil Another cable type BVV-P is not a cable for direct burial in the ground.

    BVV-P range matrix

    Below are direct links to specific elsprendimai.eu products. Other sizes and colours can be found in the BVV-P category.

    Cable Colour Construction Product
    BVV-P 2×1.5 mm² White 2 solid Cu cores Open →
    BVV-P 3×1.5 mm² Grey 3 solid Cu cores Open →
    BVV-P 3×2.5 mm² White 3 solid Cu cores Open →
    The outer sheath colour does not indicate the functions of the cable cores. Before ordering, check the internal colour coding, length, construction and product availability.

    Construction and operating principle

    1. Solid copper core
    A solid annealed copper conductor for transmitting electrical energy in a fixed circuit.
    2. PVC core insulation
    Separate core insulation reduces the risk of direct contact and electrical breakdown.
    3. Flat arrangement
    The cores are arranged in one plane, making it easy to form straight installation runs.
    4. PVC outer sheath
    Protects the insulated cores under the intended operating conditions.

    Operating principle: the copper conductor carries electric current from the supply to the load, the insulation electrically separates the conductors, and the outer sheath provides additional mechanical protection. Solid cores must not be continuously flexed during operation.

    Where is BVV-P suitable and where not?

    ✓ Residential buildings
    Lighting and other fixed circuits provided for in the design.
    ✓ Socket-outlet circuits
    When suitable PE, cross-section and protection are chosen.
    ✓ Under plaster
    In straight, properly designated electrical installation runs.
    ✓ Electrical trunking
    According to cable and trunking installation requirements.
    ⚠ Damp indoor rooms
    Assess room zones, protection and tightness of connections.
    ⚠ Cables in thermal insulation
    Assess reduced heat dissipation and current-carrying capacity.
    ✗ Soil and water
    Not intended for direct burial in the ground or immersion.
    ✗ Moving equipment
    Solid cores are not suitable for continuous dynamic flexing.

    2 or 3 cores? Phase, neutral and PE

    2 cores

    Two insulated copper conductors. There is no separate third core for protective PE, so this cable alone does not provide an L, N and PE circuit.

    3 cores

    Can be used for an L, N and PE circuit if it has a proper green-yellow protective core and meets the cross-section and installation requirements.

    ⚡ Important: the green-yellow core is reserved for the protective conductor. A two-core cable cannot be considered a complete L, N and PE solution for an earthed socket. Check the core colour coding for the specific product.

    What does 300/500 V mean?

    The cable voltage class U₀/U describes the rated voltage between conductor and earth and between conductors.

    U₀ = 300 V

    Rated voltage between conductor and earth.

    U = 500 V

    Rated voltage between conductors.

    The 300/500 V voltage class may be suitable for a 230/400 V network, but this does not in itself mean that a two- or three-core cable is suitable for any three-phase circuit. The number of cores, purpose and load must match the design.

    Cross-section, power and load current

    The cross-section is selected taking into account the conductor current-carrying capacity, installation method, grouping, temperature, protective device and voltage drop.

    Resistive load Current at 230 V Parameter to check
    100 W 0.43 A Circuit purpose
    500 W 2.17 A Cable cross-section
    1000 W 4.35 A Protection characteristics
    2000 W 8.70 A Continuous current-carrying capacity
    3000 W 13.04 A Installation method and cooling
    3680 W 16.00 A Entire circuit and circuit breaker
    Calculation: I = P / (U × cos φ)

    For a resistive load at cos φ = 1, 2300 W / 230 V = 10 A. This is not a formula for determining the current-carrying capacity of BVV-P cables.

    Resistance of solid copper cores

    Cross-section Maximum DC resistance at 20 °C
    1.0 mm² 18.1 Ω/km
    1.5 mm² 12.1 Ω/km
    2.5 mm² 7.41 Ω/km
    4.0 mm² 4.61 Ω/km

    Values apply to class 1 solid plain copper conductors. These are conductor electrical resistances, not a current-carrying capacity table. 4 mm² is included only for comparison of cross-sections; its availability in this group is not confirmed.

    Cable length and voltage drop

    Example of a single-phase 230 V circuit at 10 A current, resistive load, conductor temperature +20 °C. The combined length of phase and neutral is calculated.

    One-way distance 1.5 mm² 2.5 mm² 4.0 mm²
    10 m 2.42 V 1.48 V 0.92 V
    20 m 4.84 V 2.96 V 1.84 V
    30 m 7.26 V 4.45 V 2.77 V
    50 m 12.10 V 7.41 V 4.61 V
    Formula: ΔU ≈ 2 × L × I × R / 1000

    L – one-way length in metres, I – current in amperes, R – resistance of one core in Ω/km.

    The actual voltage drop depends on conductor temperature, load power factor, connections and other circuit parts. The calculation does not replace verification of current-carrying capacity and protective device operation.

    Technical characteristics table

    Parameter BVV-P / YDYP
    Cable construction Flat, with common sheath
    Conductor Solid annealed copper
    Rated voltage 300/500 V
    Insulation PVC
    Sheath PVC
    Maximum continuous conductor temperature +70 °C
    Installation temperature −5 °C to +40 °C for the specified variants
    Operating temperature −30 °C to +70 °C for the specified variants
    Test voltage 2 kV for the specified variants
    Short-circuit temperature Up to +160 °C for the specified variants, short-time
    Bending radius More than 5 cable thicknesses for the specified variants
    Reaction to fire Eca for the specified products; check the DoP
    Use Fixed indoor installation
    ⚠ Temperature difference: a negative operating temperature does not mean the cable may be bent or installed under such conditions. The +160 °C short-time short-circuit value is not a permitted continuous temperature.

    Damp rooms, IP and cable protection

    PVC insulation allows the cable to be used under the intended indoor installation conditions, but the cable must not be treated as a stand-alone IP65 or IP67 device. The protection of an electrical installation depends on the entire system – boxes, connections, entries, sockets and installation zone.

    Location Assessment
    Dry room or office Suitable according to design and installation method
    Kitchen, auxiliary indoor room Suitable if connections and equipment are protected
    Bathroom Only according to zone and protection requirements
    Constant sun and UV The standard BVV-P purpose does not confirm suitability
    Soil, immersion Not suitable

    BVV-P, BVV-PLL, NYM-J or NHXMH-J?

    Type Key difference Go to group
    BVV-P (YDYP) Flat, solid-core, PVC, fixed installation BVV-P →
    BVV-PLL (OMYp) Flat, flexible stranded, PVC BVV-PLL →
    KH05VV-U / NYM-J Different indoor installation construction; assess cores and sheath Copper cable catalogue →
    NHXMH-J Halogen-free fixed installation, CPR class assessed separately NHXMH-J →
    H03VV-F / H05VV-F Flexible connection cables, depending on the class of use H03VV-F / H05VV-F →

    Cables of the same cross-section are not automatically interchangeable. Construction, conductor class, rated voltage, CPR, PE and installation environment must be checked.

    Installation and proper connection

    1. Route location
    Lay the cable in designated installation zones, observing building structure requirements.
    2. Mechanical protection
    Protect from screws, drilling, sharp edges and crushing.
    3. Bending radius
    Avoid sharp kinks and observe the radius specified for the product.
    4. Contact terminals
    Use terminals suitable for solid copper cores and the selected cross-section.
    5. Cable grouping
    Assess the additional thermal effect in shared conduits and trunking.
    6. Final inspection
    Check PE continuity, insulation resistance, condition of connections and operation of protection.
    Solid cores: they are intended for reliable fixed installation. When making a contact, it is important not to damage the copper, not to break the core and to use the conductor type permitted in the connection equipment instructions. Continuous flexing is not permitted.

    What to check before ordering?

    1. Number of cores
    Is an L, N and PE system required?
    2. Cross-section
    Is the current-carrying capacity sufficient?
    3. Run length
    Does the voltage drop stay within the permitted value?
    4. Installation conditions
    Will the cable be in trunking, under plaster, in thermal insulation?
    5. Fire class
    Does the CPR class of the specific product suit the project?
    6. Length
    Has a reserve for connections and route bends been allowed for?

    Most common mistakes

    ✗ Wrong ✓ Right
    Only a 2-core cable is used for an earthed socket. Provide a PE conductor in accordance with the design.
    A 25 A load is automatically assigned to 2.5 mm². Determine the current-carrying capacity according to installation conditions.
    Solid-core cable is continuously flexed. Use only for fixed installation.
    BVV-P is considered halogen-free. If LSOH is required, choose a cable designed for it.
    Undeclared UV resistance is taken for granted. For outdoor use, use an appropriately approved cable.
    Voltage drop on long lines is not assessed. Calculate the entire supply circuit.

    Fazė's and Elsprendimai.eu recommendations

    Fazė
    Fazė advises

    First choose the circuit diagram and protective conductor, then calculate the cross-section. Do not start with the question “how many amps can 2.5 mm² carry” – without installation and cooling conditions there is no single universal answer.

    For lighting circuits

    BVV-P 3×1.5 mm², if it matches the design.

    For socket circuits

    BVV-P 3×2.5 mm², after checking PE and load.

    When flexible cores are needed

    BVV-PLL (OMYp), if the conditions of use are suitable.

    When a halogen-free cable is needed

    NHXMH-J, checking CPR and DoP.

    Diagram: wrong / right – socket-outlet circuit

    ✗ WRONG
    230 V panel
    ↓
    BVV-P 2×1.5
    Only two cores, no PE
    ↓
    Earthed socket

    No separate protective conductor is provided.

    ✓ RIGHT
    230 V panel with PE
    ↓
    3-core cable according to the design
    L, N, PE and suitable cross-section
    ↓
    Earthed socket

    PE, current-carrying capacity and protection verified.

    FAQ – Kibirkštis asks, Fazė answers

    Practical questions on choosing BVV-P (YDYP) cables, solid cores, earthing, load, installation and alternatives.

    Kibirkštis
    Kibirkštis · question 1What is BVV-P (YDYP) cable?
    Fazė
    FazėIt is a flat copper cable with PVC insulation and sheath, intended for fixed electrical installation. The solid copper cores are suitable for fixed circuit connections, and the flat shape is convenient for laying the cable under plaster or in suitable trunking.
    Kibirkštis
    Kibirkštis · question 2How does BVV-P differ from BVV-PLL?
    Fazė
    FazėThe BVV-P core is solid – a single copper conductor. The BVV-PLL core consists of many fine copper wires, so it is more flexible. Both types can be used in a properly designed fixed installation, but terminal selection and installation features differ. View BVV-PLL →
    Kibirkštis
    Kibirkštis · question 3Is BVV-P 3×1.5 mm² suitable for lighting?
    Fazė
    FazėYes, it is a common choice for lighting circuits if the number and colours of the cores match the diagram. Current-carrying capacity, circuit breaker parameters and voltage drop must also be checked. You can view BVV-P 3×1.5 mm² grey cable.
    Kibirkštis
    Kibirkštis · question 4Can 3×2.5 mm² be used for socket-outlet installation?
    Fazė
    FazėOften yes. However, you must make sure that one core is intended for PE, that the cable meets the installation conditions and that the protective device is correctly coordinated with the circuit. BVV-P 3×2.5 mm² white →
    Kibirkštis
    Kibirkštis · question 5Can an earthed socket be connected with a 2×1.5 mm² cable?
    Fazė
    FazėWith a two-core cable alone – no. An earthed socket requires a properly installed PE conductor. It is not permitted to replace PE with the neutral conductor or to connect it arbitrarily to a metal structure. Choose an L, N and PE solution that matches the design.
    Kibirkštis
    Kibirkštis · question 6Does a 2.5 mm² cable always carry 25 A?
    Fazė
    FazėNo. Current-carrying capacity depends on installation method, cooling, thermal insulation, cable grouping, ambient temperature and other factors. A protective device cannot be selected from the cross-section alone. See the load explanation →
    Kibirkštis
    Kibirkštis · question 7Can BVV-P be installed under plaster?
    Fazė
    FazėYes, this is one of its main uses. The cable must be properly installed in designated installation zones, protected from mechanical damage and not bent to a radius smaller than permitted.
    Kibirkštis
    Kibirkštis · question 8Can the cable be used in a damp room?
    Fazė
    FazėYes, under the intended conditions, but safety is not determined by the cable sheath alone. Connections, boxes, sockets and entries must be suitable for moisture, and in bathrooms the protection zones and additional electrical safety requirements are important. The cable must not be arbitrarily assumed to have IP65 or IP67 protection.
    Kibirkštis
    Kibirkštis · question 9Can BVV-P be laid directly in the ground?
    Fazė
    FazėNo, the BVV-P cables in this group are intended for fixed indoor installation, not for direct laying in soil or water. For such a route, a different cable with documented resistance to the specific environment is selected.
    Kibirkštis
    Kibirkštis · question 10Is this cable suitable for continuously moving equipment?
    Fazė
    FazėNo. A solid core is not suitable for continuous flexing. Moving equipment requires a flexible cable selected according to motion cycles, bending radius and environmental exposure. Depending on the application, you can start with the H03VV-F / H05VV-F group, but not all of these cables are suitable for continuous dynamic movement.
    Kibirkštis
    Kibirkštis · question 11Is Eca class BVV-P halogen-free?
    Fazė
    FazėNo. Eca is a reaction-to-fire class, which does not in itself confirm halogen-free properties. BVV-P is a PVC cable. If the project requires low smoke and a halogen-free construction, consider NHXMH-J and the CPR declaration of the specific product.
    Kibirkštis
    Kibirkštis · question 12How to choose the cable if the load is 50 metres away?
    Fazė
    FazėYou need to know not only the length, but also the load current, protective device and installation method. For example, on a 50 m single-phase line at 10 A, a simplified +20 °C calculation for a 1.5 mm² solid copper conductor gives a drop of about 12.1 V, and for 2.5 mm² – about 7.41 V. The actual operating temperature and protective device operation must also be checked. See the voltage drop table.
    Kibirkštis Fazė Have another question? Specify the cable length, number of cores, load and installation location. Contact Elsprendimai.eu.

    Standards and important technical notes

    When assessing cable suitability, the EN 60228 conductor parameters, LST HD 60364 principles of design and erection of electrical installations, and EN 50575 / EN 13501-6 reaction-to-fire requirements, where applicable to the specific product, are important.

    Technical characteristics of related products at elsprendimai.eu:

    Technical data consistency

    BVV-P cable data may vary depending on cross-section, colour, production batch and specific product. Before use, check rated voltage, core colours, conductor construction, temperature limits, CPR class and installation conditions. Current-carrying capacity is not determined by nominal cross-section alone.

    Disclaimer: technical tables and calculation examples are for information only. The final cable, protection and installation solution must be determined by qualified specialists according to the design and applicable requirements. UAB „Elektrotechnikos sprendimai“ is not liable for the consequences of improper selection or installation to the extent permitted by applicable law.

    Need BVV-P cables for a project?

    Specify the required cross-section, number of cores, colour, length and installation conditions. We will help compare BVV-P with other copper cables and choose the right option.

    Contact Elsprendimai.eu

    Copper cables BVV-P are high-quality electrical cables made of copper, designed for use in indoor electrical installations. These cables feature excellent electrical conductivity properties, durability, and reliability, making them widely used in both industry and household applications.

    Construction:

    Conductor:

    BVV-P cables are made from pure copper, ensuring efficient electrical power transmission.
    The conductors are often multi-core, allowing for easier installation in confined spaces and various configurations.
    Insulation:

    The cables have PVC (polyvinyl chloride) insulation, which protects against moisture, chemical exposure, and mechanical damage.
    The insulation is fire-resistant, providing additional protection to ensure safety during use.
    Specifications:

    Voltage Range:

    BVV-P cables are designed for use at voltages up to 300/500 V, making them suitable for many residential and industrial applications.
    Temperature Range:

    The cables typically operate in a temperature range from -15 °C to +70 °C, allowing for use in various environments.
    Color Code:

    BVV-P cables use a standard color code: brown (phase), blue (neutral), green-yellow (earthing), ensuring proper connections.
    Applications:

    Industry:

    BVV-P cables are ideal for various industrial solutions, including automation systems, lighting systems, and other electrical devices requiring reliable conductivity.
    Household Use:

    These cables are widely used in home lighting systems, electrical appliances, and energy transmission and distribution systems.
    Construction Sector:

    The cables are used in the electrical installations of new and renovated buildings, both indoors and outdoors, ensuring safety and efficiency.
    Advantages:

    High Electrical Conductivity: Due to the pure copper conductor, BVV-P cables ensure efficient energy transfer, reducing losses.
    Durability: PVC insulation helps ensure the long-term service life of the cables and protects against external factors.
    Easy Installation: Due to flexibility and various constructions, the cables are easy to install and adapt to different situations.
    Safety: Resistance to moisture and chemicals ensures safe use in challenging conditions.
    Copper cables BVV-P are an excellent choice for both industrial and household electrical solutions. Their reliability, durability, and excellent electrical conductivity properties ensure they meet the highest standards required for reliable energy transmission and distribution. 

    Read more
    Copper cable 2x6mm² | flexible | flat | VVG 2x6 | (1m) | black
    Code: VVG2X6J

    VVG 2x6 mm² flat electrical cable with two single-core flexible conductors made of annealed copper, designed for fixed electrical installations in residential, commercial, or industrial buildings. The PVC sheath and insulation provide excellent protection against mechanical impact and comply with strict safety standards. The cable offers great flexibility and easy installation both in electrical conduits and open installations.