Energy meters
-
Electricity meters – how to choose the right one
The right meter depends on three things: the supply current, the network (1 or 3 phases) and where the data has to go. Below you will find a quick selection guide, an overview of the groups, a separate section on CT-connected meters and the most common mistakes.
Colour key:blue – informationgreen – benefit and suitabilityorange – ⚠ checkred – ⚡ dangerous voltagepurple – communicationQuick selection by situation
Situation What to choose Where to look Apartment, cottage or a separate single-phase line Single-phase direct-connected meter Single-phase meters House, workshop or line with a three-phase supply up to 100 A Three-phase direct-connected meter Three-phase meters Current above 100 A or CTs already installed in the panel ⚡ Meter connected via current transformers Three-phase via CT Single-phase line where current is measured via a CT ⚡ Single-phase meter via CT Single-phase via CT Data must reach SCADA, BMS or a PLC Meter with RS485 Modbus RTU Eastron SDM630 Modbus V2, Selec MFM384-R-C Tenants are invoiced from the readings MID-certified meter Eastron SDM72D-M-MID, Schneider iEM3150 Import and export must be measured ⇄ Bidirectional meter Eastron SDM630 Modbus V2, EL-TVPS3-80T Direct current: EV charging, batteries DC energy meter DC 1000 V / 100 A Groups in this category
Single-phase electricity meters →
For apartments, cottages and separate single-phase lines. Direct connection, models with MID, Modbus and Wi-Fi. E.g. Eastron SDM120D-MID, THORGEON 01001.Three-phase electricity meters →
For houses, workshops and company lines up to 100 A: from simple kWh meters to multifunction meters with RS485 Modbus, M-Bus and several tariffs. E.g. Eastron SDM630 Modbus V2, ELGAMA GAMA 300 G3E.144, Zamel LEM-30.⚡ Three-phase via current transformers (CT) →
For high-current supplies, power distribution boards and building energy monitoring. Modular, multi-channel and panel-mount devices.⚡ Single-phase via current transformers (CT) →
For single-phase lines where current is measured via a transformer.DC meters and AC/DC indicators →
For direct-current circuits (EV charging, battery systems) and panel voltage / current / power indicators. They are listed in this group.⚡ Meters with current transformers (CT)
When the line current exceeds 100 A or the meter has to be installed in an existing power board, it is connected via current transformers. The CT reduces the line current to a standard 5 A or 1 A secondary current, and the meter recalculates it using the ratio set in the menu (e.g. 400/5). This way a single meter can measure a line of hundreds or thousands of amperes.
When to choose
Supply or line current above 100 A; CTs already installed in the panel; metering in the main power board or monitoring of several lines.How to select a CT
Primary current – by the maximum line current with a margin; secondary (5 A or 1 A) – the same as the meter input; the CT window must fit the cable or busbar.How to connect
P1 – on the supply side, S1 → start of the meter current input, S2 → end. Each phase has its own CT, and the phase sequence must match the voltage inputs.ℹ A sample wiring diagram with terminal numbers and the most common mistakes – see the Selec MFM384-R-C description.
Model Connection Communication Features Eastron SDM630MCT Modular, …/1 A or …/5 A RS485 Modbus RTU, 2 pulse outputs Multifunction, ⇄ import / export, THD Eastron SDM630MCT-2T Modular, …/1 A or …/5 A RS485 Modbus RTU 2 tariffs, MID Selec MFM384-R-C Modular, …/5 A (…/1 A), primary up to 10 kA RS485 Modbus RTU ⇄ Import / export, programmable PT ratio Carlo Gavazzi EM21 72D Modular, …/5 A, CT ratio up to 999 RS485 Modbus RTU, pulse Removable display, DIN or panel mounting ELGAMA GAMA 300 G3A.147 Transformer-operated, 5(10) A Depends on version 1 (C110) or 2 (F11) tariffs VEXEN ES3100DCT Modular, x/5 A, primary 1–9999 A Pulse output Simple kWh metering THORGEON 01004 Modular, 1.5(6) A via …/5 A CT Pulse, 400 imp/kWh Simple kWh metering, 1 tariff Schneider PM5110 / PM5330 Panel 96×96, via CT RS485 Modbus RTU Power analyser: power, energy, THD EARU EASEM-G-TY-W Modular, 3 CTs included (80–1000 A) Wi-Fi (Tuya), RS485 ⇄ Bidirectional, voltage and current protection TAC4371CT Modular, CT 100 / 150 / 200 A Ethernet / Modbus ⇄ Bidirectional, LCD display ME431Q4-2 Four-channel, DIN Modbus RTU / TCP, web server Several lines in one device MC60-GW30, 36-circuit meter Multi-channel, DIN, via CT RS485 Modbus Many lines – one device Panel 96×96 with Rogowski coil Panel, Rogowski coil RS485 Modbus Accuracy class 0.5S ⚡⚡ Dangerous voltage
An open CT secondary under load produces a dangerously high voltage and can damage the transformer. Always short-circuit the CT secondary terminals (S1–S2) before disconnecting the meter.Communication interfaces – how the data reaches your system
Interface Suitable for Examples Pulse output (S0) Simple energy counting to a PLC, controller or data logger THORGEON 01004, VEXEN ES3100DCT RS485 Modbus RTU SCADA, BMS, PLC, EV charger and other controller systems Eastron SDM630 Modbus V2, Selec MFM384-R-C, Eastron SDM72D-M-MID M-Bus Building metering systems with an M-Bus network VEXEN ESM3100DMB Ethernet / Modbus TCP Direct connection to the local network TAC4371CT, ME431Q4-2 Wi-Fi (Tuya / Smart Life) Monitoring in a mobile app, smart home EARU EASEM-G-TY-W, EL-TVPS3-80T 4G / LoRa Remote sites without a local network ESADW300, LoRa multi-channel meter ⚠ What to check before buying
Parameter What to check Why it matters Connection type Direct or via CT (…/5 A, …/1 A) Direct-connected meters usually handle up to 80–100 A; higher currents need CTs Current In / Imax E.g. 5(80) A, 10(100) A Imax must not be lower than the supply protection current Voltage and network type 230 V; 3×230/400 V; 3P4W or 3P3W Wrong type – wrong readings Accuracy class B (1), 0.5S Larger sites and analysis need a more accurate class MID Yes / no Required when billing is based on the readings Tariffs 1, 2, 4 or more When the price depends on the time of day Energy direction Single-direction or ⇄ bidirectional For import and export metering Communication S0, Modbus, M-Bus, Ethernet, Wi-Fi Must match your system Mounting DIN modules or panel 96×96 mm For planning space in the board ⇄Bidirectional metering
A bidirectional meter measures energy imported from and exported to the grid. Compatibility with inverter power / export control must be confirmed separately – bidirectional metering alone is not enough for that.⚠ Most common selection and wiring mistakes
Mistake Consequence ✗ Direct-connected meter chosen for a current above its Imax Terminals overheat, the meter fails ✗ CT installed backwards or S1/S2 swapped Negative power, energy counted as export ✗ CT and voltage input from different phases Wrong power and cos φ ✗ CT ratio not set in the menu Readings wrong by a fixed factor ✗ ⚡ CT secondary opened under load Dangerous voltage, CT damage ✗ Meter without MID used for billing tenants Readings are hard to justify on invoices ✗ RS485 A+/B− swapped or no 120 Ω at the end of the line No communication or intermittent data ⚡ Safe installation
- ⚡ Meters must be installed and connected only by a qualified electrician, with the power switched off and absence of voltage verified.
- ⚡ A CT secondary must never be opened under load – short-circuit the CT terminals before disconnecting the meter.
- Tighten the terminals of direct-connected meters to the torque specified by the manufacturer – a loose contact overheats.
- Protect the voltage measuring circuits according to the manufacturer's instructions.
- Follow the applicable electrical installation rules.
Frequently asked questions
What is the difference between a direct-connected and a CT-connected meter?
A direct-connected meter carries the full load current, so it is usually rated up to 80–100 A. A CT-connected meter measures only the 5 A or 1 A secondary current, so it suits lines of hundreds or thousands of amperes.Is MID certification required?
If tenants or other consumers are billed from the readings, choose a MID model. MID is not required for internal energy monitoring.Which CT ratio should I choose?
Choose the primary current by the maximum line current with a margin, e.g. 250/5 or 300/5 for a 250 A supply. The ratio is set in the meter menu.Can the meter be connected to SCADA or BMS?
Yes, if it has an RS485 Modbus RTU, M-Bus or Ethernet (Modbus TCP) interface. Check the register map and communication settings.Is a bidirectional meter suitable for inverter export limitation?
It measures energy imported from and exported to the grid, but compatibility with a specific inverter's control must be confirmed separately.How much space does a meter take in the board?
Single-phase modular meters usually take 1–2 DIN modules, three-phase meters 4 or more. Panel devices are mounted in a 96×96 mm cut-out.Need help choosing?
Send us the supply current, network type and where the data needs to go – we will select the right meter and, if needed, the current transformers. All meters are delivered in Lithuania, Latvia and Estonia.
1 - 16 of 18Modular three-phase energy meter | CT-operated 5(6) A | 3×230/400 V | RS485 Modbus | detachable display | DIN / panel | Carlo Gavazzi EM21072DAV53XOSXCode: EM21072DAV53XOSXPrice 408.98 € VAT incl.( 338.00 € VAT excl. )Price 29.04 € VAT incl.( 24.00 € VAT excl. )Three-phase electricity meter | 5(10) A via current transformers | 3×230/400 V | CT connection | 2 tariffs | active energy | GAMA 300 | ELGAMA-ELEKTRONIKA G3A.147-230.F11Code: G3A.147-230.F11Price 224.88 € VAT incl.( 185.85 € VAT excl. )Three-phase electricity meter | 5(10) A via current transformers | 3×230/400 V | CT connection | 1 tariff | active energy | GAMA 300 | ELGAMA-ELEKTRONIKA G3A.147-230.C110Code: G3A.147-230.C110Price 152.15 € VAT incl.( 125.74 € VAT excl. )Price 63.53 € VAT incl.( 52.50 € VAT excl. )Modular three-phase energy meter | x/5 A via current transformers | 3×230/400 V | 1–9999 A primary | Pulse output | IP51 | DIN | VEXEN ES3100DCTCode: ES3100DCTPrice 102.90 € VAT incl.( 85.04 € VAT excl. )Price 150.00 € VAT incl.( 123.97 € VAT excl. )Modular three-phase multifunction energy meter | CT-operated …/5 A (…/1 A) | 3×230/400 V | RS485 Modbus | Import / export | DIN | Selec MFM384-R-C-CECode: MFM384-R-C-CEPrice 117.04 € VAT incl.( 96.73 € VAT excl. )Modular multifunction energy meter | 3-phase | 1/5 A CT operated | 2 tariffs | RS485 Modbus | MID | DIN | Eastron SDM630MCT-2TCode: SDM630MCT-2TPrice 144.72 € VAT incl.( 119.60 € VAT excl. )DC energy meter | dual circuit | up to 1000V DC | 100A (shunt) | RS485 Modbus | DIN rail | Class 0.5 | for EV charging stationsCode: ES-DCM3366D-J2-GPrice 299.40 € VAT incl.( 247.44 € VAT excl. )Panel digital multifunction DC energy meter | voltage | current indicator | with shunt | 50A | 6.5–100VDCCode: EL-TX-051DC5Price 27.23 € VAT incl.( 22.50 € VAT excl. )Panel digital multifunction DC energy meter | voltage | current indicator | with shunt | 20A | 6.5–100VDCCode: EL-TX-051DC2Price 25.41 € VAT incl.( 21.00 € VAT excl. )Digital AC electrical power | voltage | current meter | 20A | 85-250VACCode: EL-TXS-1002Price 23.60 € VAT incl.( 19.50 € VAT excl. )Price 25.41 € VAT incl.( 21.00 € VAT excl. )Price 26.50 € VAT incl.( 21.90 € VAT excl. )Price 25.41 € VAT incl.( 21.00 € VAT excl. )