-
Product Catalog
- Security and Surveillance Systems | accessories
- Lighting solutions for industrial | commercial | residential | outdoor environments | accessories
- Automation and Control Systems
- Smart Automated Products | Control | Transmission | Detection
- Electrical distribution and installation
- Solar Energy Generation and Management Equipment
-
HVAC control solutions for heating and ventilation
-
HVAC automation
- Sensors and detectors
- Electric motors
-
Frequency inverters for motor speed regulation
- Optidrive frequency inverters for motor speed control
- Siemens frequency inverters | efficient motor control | process automation
- Schneider Electric frequency inverters | efficient motor control | process automation
- EURA Drives frequency inverters | efficient motor control | process automation
- Frequency inverters
- Air damper drives
- Speed regulators for fans
- Motorized actuators for air dampers | ventilation (HVAC) systems | air ducts
- Modbus modules and power supplies
- Fans for ventilation systems
- Ducts and connections for ventilation | air conditioning systems
- Deflectors | ventilation | ventilation systems
- Dampers for ducts | ventilation | air conditioning systems
- Duct Silencers | Ventilation | Ventilation Systems
- Air Filters for Ducts | Ventilation | Ventilation Systems
- Supply Air Ventilation Dampers
- Diffusers for Ventilation Systems
- Electric heating
- Mobile Air Conditioners | for Indoor Climate Control
- Domestic | industrial air purification systems
- Aromatic diffusers | essential oil diffusers for homes | offices | industrial premises
- Domestic | industrial dehumidifiers | moisture collectors | humidity control solutions
- Domestic | industrial air humidifiers | ultrasonic | fog generators
-
HVAC automation
- Accessories for cars
- Workplace Safety | Electrical Safety Equipment | LOTO
- Technical maintenance | service equipment | fire protection solutions
- Emergency safety | hygiene | sanitary solutions
- Other products
- Quality used products
EURA Drives frequency inverters | efficient motor control | process automation
-
-
Read more
Eura Drives variable frequency drives – selection, operation, control and diagnostics
A practical motor control guide – from basic electrical engineering to professional drive selection and operation.
Buyers | Electricians | Students | Engineers | Automation specialists
Using the technical informationThis guide covers general operating and selection principles. Not every Eura Drives model supports all described functions. Check specific parameters, terminal functions, protections and installation conditions in the manufacturer's manual for the relevant product.
1. Quick drive selection
First identify the motor and its operating conditions. Select the drive by rated motor current, supply voltage, load characteristics and required functions, not only motor power in kW.
What do you know? What should be checked? Why does it matter? Motor power kW and rated current in A Drive output current must match the load Supply network 1×230 V, 3×230 V or 3×400 V Incorrect supply can damage equipment Mechanism Pump, fan, conveyor, mixer Torque and overload requirements differ Control requirements V/f, vector control, PID, 0–10 V, 4–20 mA Not all models support the same functions Operating environment IP rating, temperature, cooling, dust Environmental conditions may limit permissible load The key selection ruleRated drive output current must suit the motor and mechanism duty, including overload requirements and manufacturer-specified derating factors. Equal kW ratings do not guarantee compatibility.
2. Choose the information you need
For buyers – selection For electricians – commissioning For students – theory For engineers – design3. For buyers – which drive do you need?
Drives regulate motor speed, control starting and stopping, maintain pressure or flow automatically, and perform other functions.
Application Useful function What to consider? Water pump PID, pressure control Sensor, hydraulic system, protections Fan Speed regulation Motor type, EMC, load Conveyor Vector control Starting torque, inertia Mixer Torque control Duty cycle, low-speed cooling 4. For students – how a drive works
A drive is a power electronic device that changes the electrical supply parameters of a motor. A typical drive contains a rectifier, DC link and inverter.
Energy pathAC supply → Rectifier → DC link → PWM inverter → Motor
The rectifier produces DC voltage; semiconductor switches in the inverter generate a pulsed output voltage with controlled frequency and amplitude.
How does frequency affect motor speed?
Synchronous speed is calculated as:
ns = 120 × f / Pns – synchronous speed in rpm, f – frequency in Hz, P – number of poles.
Synchronous speed of a 4-pole motor:
- 20 Hz – 600 rpm
- 30 Hz – 900 rpm
- 40 Hz – 1200 rpm
- 50 Hz – 1500 rpm
Actual induction motor speed is lower because of slip.
What are V/f and vector control?
V/f control – a scalar method maintaining a defined voltage-to-frequency ratio over a specified frequency range.
Vector control – a method for more precise magnetic flux and torque regulation, depending on the algorithm and motor model.
Vector control can benefit mechanisms requiring higher torque at low speed.
Why can pumps save energy?
Under certain conditions, affinity laws apply to typical centrifugal systems:
Q ∝ n | H ∝ n² | P ∝ n³At 80% speed, the cubic law predicts shaft power may fall to 51.2% of its original value.
Actual electrical savings depend on hydraulic characteristics, static head and equipment efficiency.
5. For engineers – load analysis and control solutions
Mechanism Load characteristics Design priority Centrifugal pump Often variable torque PID, pressure limits, dry-run protection Fan Often variable torque Speed range, resonance, EMC Conveyor Often constant torque Starting torque, overload capacity Mixer Depends on the medium Torque margin, cooling, duty cycle PID control – constant pressure
The PID controller compares set pressure with measured pressure and adjusts the motor speed reference according to the error.
Setpoint → PID → Drive → Pump → Pressure sensor → FeedbackConsider sensor range, signal scaling, PID gains, minimum and maximum speeds, process inertia and fault conditions.
Long motor cables and EMC
PWM pulses can cause high voltage rise rates and reflections in long cables.
Depending on drive, motor and cable characteristics, a dV/dt or sine-wave filter, proper shielding and additional EMC measures may be required.
Permissible cable length is specified in the model documentation.
Braking energy and braking resistor
When braking a high-inertia mechanism, the motor may generate energy that returns to the drive DC link.
If energy cannot be safely dissipated or returned to the supply, a braking unit and resistor or another manufacturer-approved solution may be needed.
Resistor resistance, power and duty cycle must meet drive requirements.
6. For electricians – installation and commissioning
DANGEROUS VOLTAGEDangerous voltage may remain in the drive DC link after disconnection. Before work, isolate safely, prevent reconnection, wait the manufacturer-specified time and verify absence of voltage with a suitable instrument. Work must be performed by qualified specialists.
Commissioning checklist
- Check drive model and supply network.
- Check motor nameplate and connection compatibility.
- Check supply, motor and PE connections against the manufacturer diagram.
- Check protections, cables, EMC measures and cooling.
- Enter rated motor parameters.
- Select control mode and command source.
- Set frequency limits and acceleration/deceleration times.
- Check safety functions against the system design.
- Perform a controlled test start.
- Record settings and measurements.
Correct and incorrect practice
Correct Incorrect Use the specific model wiring diagram Use another drive's terminal layout Check motor current and load Select only by kW Provide suitable cooling Ignore heat dissipation inside the cabinet Follow output switching requirements Switch the motor circuit arbitrarily while the drive is running 7. Fault diagnostics
Before checking, record the fault code, operating state and circumstances. Fault codes differ between drive series.
Symptom Possible cause What to check Overcurrent Load, short ramp, mechanical jam Check load and parameters DC overvoltage Regenerative energy, excessively fast braking Analyse braking operation Overheating Cooling, ambient temperature, load Check ventilation and duty Motor does not rotate Control signal, interlock, settings Check states and command source EMC interference Shielding, filters, cable routing Review EMC measures 8. Practical selection examples
2.2 kW water pump
Constant water pressure is required.
Solution approach: A drive with suitable output current and PID, a compatible pressure sensor, and hydraulic and electrical protections specified by the design.
Check: Rated motor current, pump curve, minimum speed limit and sensor signal.
7.5 kW fan
Airflow must follow process demand.
Solution approach: A drive with suitable output current supporting speed control from an automation signal.
Check: Motor compatibility, fan mechanical limits, resonance, EMC and cooling.
4 kW conveyor
Smooth starting and controlled transport speed are required.
Solution approach: A drive whose overload capacity and control method meet the mechanism's starting torque requirement.
Check: Conveyor inertia, load variations, braking and motor thermal duty.
9. Frequently asked questions
Does a drive always save energy?
No. Savings depend on load, control method and duty. Centrifugal pump and fan systems often offer high potential.
Can a 230 V drive control a three-phase motor?
Yes, if the drive output is three-phase and the motor nameplate and connection allow that voltage.
Can one drive supply several motors?
Sometimes, but total current, individual motor protection, control method and manufacturer requirements must be assessed.
Can frequency exceed 50 Hz?
Only if the motor, mechanism and drive allow it. Assess mechanical speed, cooling and torque changes.
Does the drive replace all external protections?
No. System protections follow the drive documentation, design and applicable standards.
A drive – more than a speed controller
A correctly selected drive controls motor operation, automates processes, regulates speed, reduces mechanical stress and can save energy in suitable systems.
Elektrotechnikos sprendimai – a catalogue of electrical equipment, automation and technical solutions.
Practical guide continued: Inputs and functions | Six control scenarios | Connection principles | Project ideas | Overload limitsDrive inputs, control functions, reversing and speed safety
The drive can be controlled by its keypad, external buttons, switches, potentiometer, analogue sensors, PLC or communications. Available functions depend on the model and parameters.
1. Main input and output types
Interface Application Example DI – digital input Receiving commands and states Start, Stop, Reverse, Reset, speed selection AI – analogue input Continuous reference or sensor signal input 0–10 V, 4–20 mA DO – digital output State output Running, frequency reached, fault RO – relay output Signalling or control contact Fault signal to PLC AO – analogue output Output of operating quantity Frequency or current indication RS485 / Modbus RTU Data and command exchange PLC, BMS, SCADA ImportantDI, AI, DO, AO and RO describe functions, not universal Eura Drives terminal names. Terminal numbers, logic levels, input types and allowable voltages must be taken from the model manual.
2. Speed control with a 0–10 V signal
A 0–10 V analogue signal commonly provides the speed reference. If supported, parameters define the frequencies corresponding to minimum and maximum input voltages.
Potentiometer / PLC → 0–10 V → Analogue input → Frequency reference → MotorEducational example: The analogue input is configured for a linear 0–50 Hz range.
Input voltage Frequency reference Relative reference 0 V 0 Hz 0 % 2 V 10 Hz 20 % 5 V 25 Hz 50 % 8 V 40 Hz 80 % 10 V 50 Hz 100 % Linear scaling formula: f = fmin + (U / 10) × (fmax − fmin). Valid only for this input configuration. The calculated frequency is a reference, not guaranteed actual motor speed.
0 V does not necessarily mean a safe stop. This depends on minimum frequency, command source and signal-loss logic.
3. The 4–20 mA signal and its applications
4–20 mA is common for industrial pressure, temperature and other process measurements. With proper configuration, it distinguishes the normal lower measurement limit from certain signal-break conditions.
Example: 0–10 bar pressure sensor4 mA = 0 bar; 12 mA = 5 bar; 20 mA = 10 bar. This is sensor scaling, not an automatic drive frequency relationship.
Check current-input support, sensor power supply and the response to signal loss.
4. Programming buttons and digital inputs
Many drives allow different functions to be assigned to digital inputs. Available functions, priorities and control logic depend on the model.
Function What does it do? Where is it used? Run Forward Forward rotation command Conveyors, pumps Run Reverse Reverse rotation command Transport mechanisms Stop Normal stop Operator control Fault Reset Fault reset After eliminating the cause Jog Movement at a preset speed Adjustment, positioning Preset Speed Preset speed selection Several operating modes External Fault External fault signal Process interlock Local / Remote Control source selection Local / PLC control Two-wire and three-wire control
Two-wire control: A maintained switch signal. The input state may represent a continuous run command.
Three-wire control: Usually momentary Start and Stop buttons with internal command latching logic.
In both cases, define behaviour after power restoration, control signal loss and fault reset. Unexpected automatic starting can be hazardous.
5. Reversing – changing motor direction
Reversing changes motor rotation direction. A drive can do this electronically if supported and if the mechanism permits both directions.
Forward command → Deceleration → Stop or controlled transition → Reverse rotationThe transition depends on settings, load inertia and control method. Assess braking energy, mechanical shocks and safety.
Reversing hazardNot every mechanism permits reverse operation. Pumps, fans and gearboxes may restrict direction changes. Block reversing where incompatible with the process.
6. Selecting several speeds with buttons
Some drives allow several preset frequencies selected through digital inputs.
Educational example:
DI1 DI2 Selected reference 0 0 10 Hz 1 0 20 Hz 0 1 35 Hz 1 1 50 Hz This is a logic example, not an approved Eura Drives parameter table. DI combinations and permissible speeds depend on the model.
7. Modbus RTU over RS485 – remote control
Modbus RTU exchanges data between the drive and PLC, BMS or SCADA if the interface and protocol are supported.
PLC / BMS / SCADA ↔ RS485 / Modbus RTU ↔ DrivePossible Modbus functions
- Send Start / Stop commands.
- Change speed or frequency reference.
- Control direction, where permitted.
- Read operating frequency and current.
- Read drive status and faults.
- Read or change certain parameters, where permitted.
Configure address, baud rate, parity and other protocol settings. The model-specific Modbus register map is also required.
Response to communication lossDefine whether communication loss causes stopping, another mode or a design-specified action. This logic must match the mechanism risk assessment.
8. Minimum, maximum and safe speed
These are different concepts. Distinguish ordinary parameter-based limits from certified functional safety functions.
Term Meaning Use Minimum frequency Lower permissible reference limit Limiting pump or fan operation Maximum frequency Upper frequency reference limit Mechanism speed limitation Jog speed Separate movement reference Adjustment and process movement SLS Safely Limited Speed – SLS Certified functional safety, if supported STO Safe Torque Off – STO Safety circuit, if supported CRITICAL SAFETY DISTINCTIONA simple 10 Hz speed limit or Jog mode is not an SLS safety function. SLS requires a suitable certified safety solution matching the machine risk assessment. STO neither guarantees instantaneous stopping nor removes dangerous voltage.
9. Practical use of functions
Equipment Control method Key function Fan 0–10 V from BMS Speed limits, communication and signal loss Water pump 4–20 mA + PID Pressure control and process protections Conveyor Buttons / PLC Forward, reverse, braking ramps Mixer Multiple speeds Mode selection, torque margin Automated line PLC / Modbus States, faults, response to communication loss 10. What to check before programming inputs?
- Does this drive support the required function?
- Is the input intended for voltage, current or a digital command?
- Is local or remote control selected correctly?
- Are Start/Stop and reversing priorities defined?
- Is a safe response to signal and communication loss defined?
- Do speed limits suit the motor and mechanism?
- Are process control and functional safety circuits separated?
- Is unexpected starting prevented after fault reset?
- Have all settings been tested under controlled conditions?
Practical drive control diagrams
Six common industrial control scenarios are shown here. These diagrams illustrate functional principles, not product-specific electrical wiring.
SAFETY NOTEDI, AI, COM and other labels are indicative. Before wiring, verify terminal functions, internal supply limits, PNP/NPN logic, contact type and manual. These diagrams are not a functional safety design.
1. Potentiometer – manual speed control
Potentiometer → 0–10 V → AI → VFD → MotorIn practice: Speed control of a fan, small conveyor or process mechanism.
- One potentiometer end connects to a compatible reference voltage.
- The other end connects to analogue signal common.
- Wiper connects to the analogue input.
- Select the analogue speed reference source in the parameters.
- Configure input scaling and speed limits.
Note: Potentiometer resistance, supply and wiring must follow the manufacturer manual. A 0 V signal is not an emergency stop function.
2. Start / Stop – momentary pushbuttons
START (NO) / STOP (NC) → DI inputs → VFDIn practice: Operator-controlled equipment requiring separate start and stop buttons.
- START is usually normally open (NO).
- STOP is often normally closed (NC).
- Select a compatible three-wire control mode.
- Set control source and start/stop logic.
- Check that power restoration does not cause unexpected starting.
Important: A normal STOP button is not an emergency stop device. Emergency stopping is designed separately according to machine risk assessment.
3. Reversing – conveyor forward and reverse
FORWARD / REVERSE → DI → VFD → MotorIn practice: Conveyor belts, feeders and other equipment designed to allow changes of direction.
- Assign forward and reverse command functions.
- Provide mutual command interlocking.
- Set acceleration and braking ramps.
- Check permissible mechanism direction.
- Assess regenerative braking energy.
Danger: A reverse command may cause unexpected movement. Conflicting direction commands must not be enabled simultaneously.4. Four speeds – two digital inputs
DI1 + DI2 → speed selection → VFDIn practice: Production lines, mixers and conveyors with several operating modes.
DI1 DI2 Reference 0 0 10 Hz 1 0 20 Hz 0 1 35 Hz 1 1 50 Hz Frequencies are illustrative. A separate run-enable command is usually needed; input combinations follow drive documentation.
5. Pump – automatic pressure control
4–20 mA pressure sensor → PID → VFD → PumpIn practice: Water supply, pressure boosting stations and process systems.
Educational example: 0–10 bar sensor, desired pressure 3.0 bar.
- Select a compatible analogue input.
- Scale the 4–20 mA signal to 0–10 bar.
- Set PID reference to 3.0 bar.
- Limit permissible pump speed.
- Provide pressure, dry-run and sensor-failure protections.
Operation: As demand rises, pressure may fall and PID increases the speed reference. As demand falls, it reduces the reference.
6. Modbus RTU – PLC control
PLC ↔ RS485 / Modbus RTU ↔ VFD ↔ MotorIn practice: Automated lines, ventilation systems and remote status monitoring.
- Match the Modbus device address.
- Match baud rate and parity.
- Select remote control mode.
- Send frequency reference using the manufacturer register map.
- Read status, current and faults, if supported.
- Define response to communication failure.
Note: RS485 A/B labels may differ between devices. Topology, shielding, termination and register addresses must follow equipment manuals.
When is additional functional safety required?
Process speed limitation is not certified safety.
A 10 Hz Jog mode may help conveyor adjustment but does not itself provide SLS. Working in a hazardous area while moving requires safety functions and equipment selected through risk assessment.
STO, if supported, may form part of the safety system but does not disconnect power or guarantee an immediate stop.
Connection principles – from power to control
Educational connection diagrams. Labels describe functions, not terminal numbers of a specific EURA model. Verify connection variant, PNP/NPN, supply limits and input parameters in its manual. Emergency stopping is designed separately. Installation is performed by a qualified specialist.A. Power circuit – three-phase supply and motor
Three-phase supply at the correct voltage → isolation and manufacturer-specified protections → VFD supply input VFD motor outputs U / V / W → motor cable → Three-phase motor: terminals according to nameplate PE busbar → protective conductors → Drive PE and motor frame Do not confuse: Connect the supply to the drive input, not U/V/W. Select star/delta motor wiring from its nameplate and drive output voltage. PE is not analogue COM. Do not switch the motor circuit while running unless the manufacturer permits a specific sequence. Single-phase drives use only their manual's supply diagram.
B. Potentiometer – three connection paths
Compatible reference voltage output → First potentiometer end Potentiometer wiper → 0–10 V reference → VFD analogue input, voltage mode Second potentiometer end → VFD analogue signal common Check reference output capacity and potentiometer resistance in the manual. Start is commanded separately. 0 V does not replace a safety circuit.
C. START / STOP – momentary buttons, three-wire logic
Manufacturer-specified DI activation potential → START, NO contact → DI: momentary start command The same compatible activation potential → STOP, NC contact → DI: stop / run-enable function DI common terminal ↔ according to PNP / NPN diagram ↔ Control supply reference potential This is a functional diagram: STOP active state and command latching are defined by the specific three-wire mode. Do not use it as a universal terminal wiring drawing. Check STOP priority, broken-wire response and starting after power restoration.
D. Forward / reverse and four speeds
Compatible DI activation potential → forward contact → DI assigned to RUN FORWARD Compatible DI activation potential → reverse contact → DI assigned to RUN REVERSE Speed selector contact 1 → DI, speed selection bit 1 Speed selector contact 2 → DI, speed selection bit 2 Interlock forward and reverse commands. When both features are used, speed-selection inputs must be separate from direction inputs. See the four-speed table in the practical diagrams section. The meaning of 00 depends on settings and does not always select the first preset frequency.
E. Two-wire 4–20 mA pressure transmitter – external supply
Compatible DC supply, + → Two-wire transmitter + Two-wire transmitter − → 4–20 mA → VFD AI, current mode VFD analogue input common → current return path → DC supply − This applies only to a compatible passive current input and two-wire transmitter. Active inputs, three-wire sensors or isolation modules need another diagram. Check loop voltage margin, polarity and common-potential compatibility. PID feedback and the 3.0 bar reference are configured separately.
F. PLC and RS485 / Modbus RTU
PLC RS485 data terminal, by polarity ↔ twisted-pair conductor ↔ Corresponding VFD RS485 data terminal Second PLC RS485 data terminal ↔ other pair conductor ↔ Second VFD RS485 data terminal Both physical ends of the line → termination according to manuals → Daisy-chain bus, short branches A/B labels may be reversed between manufacturers: check polarity, not only letters. Signal common, shield, earth and isolation follow both manuals. A bus, rather than a star, is normally used. Set address, baud rate, parity, registers and communication-loss response.
Six more ambitious automation projects
These are design concepts, not ready-made parameter sets. Functions must follow drive, motor and mechanism documentation.
1. Workshop dust extraction following active machines
Machine states → PLC → Dampers and VFD → Fan
Set airflow demand for each active workstation; a pressure sensor may adjust fan speed.
Consider: The aim is sufficient extraction rather than continuous maximum speed. Minimum flow depends on dust transport. Combustible dust or explosive atmospheres require a separate appropriate equipment design.
2. Water station with two alternating pumps
Pressure sensor → PLC / PID → Separate drives → Pumps
The controller balances operating hours, adds the second pump when needed and manages standby.
Consider: Each pump needs protections, check valves and operating limits. Multiple pumps on one drive require a separate manufacturer-approved design.
3. Smart greenhouse ventilation
Temperature / humidity → PLC / BMS → Speed reference → Fans
Ventilation follows the microclimate; local and automatic modes facilitate servicing.
Consider: Consider sensor-failure mode, minimum ventilation, condensation and humidity, and motor suitability for VFD.
4. Conveyor feed based on product presence
Product sensor → PLC → Speed and direction → Conveyor
Select recipes, gentle ramps and controlled feed for different products.
Consider: Current can indicate jamming but is not universal force or personnel protection. Jog and reverse require a suitable mechanism design and separate safety system.
5. Mixer with a multi-stage recipe
Operator recipe → PLC → Frequency and stage times → Mixer
One cycle combines slow loading, working stage and controlled stopping.
Consider: Calculate starting torque, viscosity changes, gearbox limits and low-speed cooling. Lid interlocking must match risk assessment.
6. Remote wastewater pumping station diagnostics
Level sensor → PLC → VFD → Pump; states → SCADA
Monitor hours, current, faults and level; transmit status information.
Consider: Provide high-level alarms, dry-run and blockage protections, and communication-loss operation. External communications must not be the sole critical process control path.
Overloads – how much and for how long?
Overload capacity is specified as a percentage of rated drive output current and a duration. It is a short-term starting or load-surge margin, not permission to use a larger motor continuously.
Series / source Specified current Duration / condition E800 120% of rated current 60 s; European series data specify a 60 s / 15 min cycle E2000 150% of rated current 60 s according to the cited manufacturer manual These values apply to the series in the cited documents. Check the exact model, version, temperature, altitude, switching frequency and duty conditions in its manual. Do not automatically apply these limits to other EURA series.
Example: rated drive output current 10 A120% = 12 A, meaning +20% above rated current.
150% = 15 A, meaning +50% above rated current.
It is not an extra 120% or 150% added to 10 A. Current percentage cannot simply be equated to mechanical power or torque percentage.What limits actual permissible overload?
- Drive current and thermal capacity, temperature and previous load.
- Motor rated current, permissible duty and cooling, especially at low speed.
- Permissible mechanism, gearbox and transmission torque.
- Repeated start frequency and the manufacturer recovery cycle.
- Parameter and protection settings; raising a trip threshold does not increase physical equipment capability.
Practical selection
If the mechanism needs 14 A for 40 seconds, a 10 A E800's specified 12 A margin is insufficient. A 10 A E2000's specified 15 A / 60 s margin may meet this requirement alone; repetition cycle, derating, motor and mechanics still need checking. Continuous 14 A requires a drive with suitable continuous output current.
Overload, overcurrent and braking overvoltage are different conditions.Sustained increased current can cause thermal overload. A brief surge may trip overcurrent protection before 60 s has elapsed. Braking high-inertia loads can regenerate energy and raise DC-link voltage; a larger current margin alone does not solve this.
Manufacturer sources: E800 manual, technical specifications; E800 European series data; E2000 manual, section 2.5.



