  • BVV-F (OMY, OWY) copper cables are used in residential buildings to connect medium-power household appliances (e.g., washing machines, refrigerators). They are suitable for household use, including in damp rooms. The conductor is twisted from thin strands of annealed copper wire, making it very flexible. The insulated conductors are twisted together and covered with a PVC sheath, ensuring ease of use.

    BVV-PL cables are designed for fixed electrical installations, laying wires under plaster or in channels designated for electrical installations. They are suitable for installation in both damp and dry areas. The conductor is twisted from annealed copper wires, making it flexible and convenient for connecting conductors to socket contacts. These cables are not suitable for underground or underwater installation.  

    Read more
  • Professional cable selection guide · copper PVC cables

    BVV-F and BVV-PL: from connecting household appliances to fixed electrical installations

    Round flexible BVV-F (OMY, OWY) and flat BVV-PL cables are in one product group, but their purposes differ. Learn how to choose the right construction, number of cores, cross-section, connection method, operating environment and protective measures.

    300/500 V
    Rated voltage
    2 types
    BVV-F and BVV-PL
    PVC/PVC
    Insulation and sheath
    Cu
    Copper conductors
    +70 °C
    Max. conductor temperature of the specified BVV-F product
    Kibirkštis Fazė Asking: Kibirkštis – a young electrician. Answering: Fazė – an experienced electrical engineer.
    Key point:

    BVV-F and BVV-PL should not be chosen as identical cables that differ only in shape. BVV-F is intended for suitable connections of electrical appliances and equipment, while BVV-PL – for fixed indoor installation. The decision depends on cable construction, the permitted use of the specific product, number of cores, PE, load, environmental conditions and cable length.

    What do you need? Quick cable selection

    Before choosing the cable cross-section, first determine which electrical circuit it will be used for. A given cable may be suitable for connecting a washing machine but unsuitable for direct installation in a wall or for outdoor use.

    Situation Direction Key check
    Washing machine connection cord BVV-F, if suitable for the appliance Cross-section, three-core construction with PE, connection method and appliance instructions
    Refrigerator power cord BVV-F according to appliance requirements Voltage, mechanical strength, plug and protective conductor
    Fixed indoor installation under plaster BVV-PL Number of cores, PE, installation method and current-carrying capacity
    Flat run in a cable trunking BVV-PL Temperature, grouping and mechanical protection
    Larger cross-section round power cable BVV-F 3G6 or 5G6, if suitable for the purpose Current-carrying capacity, connections, flexibility, cable retention and protection
    Damp indoor room According to the conditions of use of the specific cable Equipment IP rating, cable entries, PE, protection and direct exposure to water
    Outdoor run with continuous UV exposure Cable specifically designed for outdoor use Declarations of UV, moisture, temperature and mechanical resistance
    Laying cable in ground or water Not BVV-PL A cable designed for such conditions and a suitable installation system

    BVV-F and BVV-PL range matrix

    The group includes cables with different numbers of cores and constructions. Specific catalogue variants are listed below. After choosing a variant, check its technical data sheet, the length to be ordered and availability.

    Model Cores Shape Main purpose Product
    BVV-PL 2×1.5 2×1.5 mm² Flat Fixed indoor installation without an integrated third PE core 0.64 € / m · Buy →
    BVV-PL 2×2.5 2×2.5 mm² Flat Fixed indoor installation; the need for PE must be assessed 0.98 € / m · Buy →
    BVV-F 2×6 2×6 mm² Round Larger cross-section flexible connection where no PE core in the cable is needed 2.29 € / m · Buy →
    BVV-F 3G6 3×6 mm² Round Power circuit with three cores, including PE 3.84 € / m · Buy →
    BVV-F 4G6 4×6 mm² Round Four-core circuit with PE according to the diagram 4.41 € / m · Buy →
    BVV-F 5G6 5×6 mm² Round Larger cross-section five-core power circuits 5.53 € / m · Buy →
    ℹ All links in the table lead directly to the product pages. Cables are sold by the metre, minimum order – 10 m. Prices include VAT.

    BVV-F or BVV-PL? Detailed comparison

    In this category the key selection question is whether a flexible appliance power cable or a flat cable for fixed building installation is required. The difference is not just aesthetic.

    Property BVV-F BVV-PL
    Shape Round Flat
    Cores Flexible, made of fine copper wires Class 2 (rigid stranded)
    Insulation PVC PVC
    Sheath PVC PVC
    Typical purpose Connection of appliances and equipment Fixed electrical installation
    Under plaster Only if permitted for the specific construction Intended use according to installation conditions
    Bending Convenient for connection; suitability for continuous dynamic cycles is a separate matter Intended to be installed and left in a fixed position
    Outdoors and UV Must not be considered UV-resistant without separate confirmation Must not be considered UV-resistant without separate confirmation
    Ground / water Direct laying not intended without special approval Not suitable for direct laying
    Key check Appliance requirements, flexibility class, PE and terminals Conductor class, cores, installation method and protection

    Cable construction and operating principle

    The main function of both types is to transmit electrical energy through copper conductors safely separated by insulation. However, how the conductors are formed and arranged in a common sheath directly affects ease of installation and intended use.

    BVV-F: round multi-core construction

    1. Flexible copper
    Each core consists of many fine annealed copper wires. In the 5G6 variant – conductor class 5.
    2. Core insulation
    Separate PVC insulation electrically separates the conductors.
    3. Stranded bundle
    The insulated cores are formed into a common round cable core.
    4. Outer PVC sheath
    Holds the inner elements together and provides additional protection under permitted conditions.

    BVV-PL: flat installation construction

    1. Copper conductors
    BVV-PL conductors are class 2 rigid stranded per EN 60228 (manufacturer AB Lietkabelis data).
    2. PVC insulation
    Separates the conductors from each other and reduces the risk of electrical contact.
    3. Flat shape
    Convenient for straight runs under plaster and in installation trunking.
    4. Common sheath
    Protects the insulated conductors and provides a uniform cable construction.
    Understanding the terms: “multi-core cable” means the cable contains several insulated cores, while “stranded core” means a single core consists of several or many wires. They are not the same. For example, a five-core cable may have five solid or five flexible stranded cores.

    BVV-F for connecting household and electrical equipment

    Round flexible BVV-F cables can be used for suitable power connections of electrical equipment. However, each appliance connection must match its rated power, protection class, terminals, type of movement and environmental conditions.

    Washing machines

    Important: power cord construction, proper PE, risk of water exposure and the cross-section specified in the appliance instructions.

    Refrigerators and refrigeration equipment

    Compressor start-up, number of cores, mechanical strength of the flexible cord and connection terminals are assessed.

    Auxiliary electrical equipment

    May be suitable for equipment connection circuits where the environmental and movement conditions match the cable construction.

    Industrial equipment

    Vibration, oils, mechanical loads, cable tension and equipment documentation must be assessed separately.

    ⚡ Wrong choice: do not choose BVV-F just because it is flexible. If the equipment cable constantly moves with a moving part, vibrates heavily, is pulled or rubs, a special cable designed for dynamic loads may be required.

    BVV-PL in fixed installations

    BVV-PL cables are intended for fixed indoor electrical installation runs. They can be installed under plaster or in dedicated trunking where the installation conditions, circuit parameters and building requirements allow such a construction.

    Installation location Suitability Practical note
    Under wall plaster Intended use Observe installation zones, do not damage the sheath.
    In electrical trunking Possible according to the design Check trunking fill and cable grouping.
    In a dry indoor room Suitable environment Ensure adequate mechanical protection.
    In a damp indoor room With conditions Check zones and protection of connections and equipment.
    Directly in the ground Not suitable Use a cable designed for underground runs.
    Immersion in water Not suitable A special-purpose cable is required.
    Continuous direct UV exposure Not proven for the type Resistance must be declared separately.

    What do 2×6, 3G6, 4G6 and 5G6 mean? Cores, neutral and PE

    In the cable designation, the first number indicates the number of cores, the second – the nominal cross-section of each core in mm². The letter G in common cable designation means the construction includes a green-yellow protective core. Nevertheless, the colour coding of the specific product must be checked.

    Designation What does it mean? Example circuit
    2×6 Two cores of 6 mm² Two-conductor circuit that does not require a separate PE core in the cable
    3G6 Three cores of 6 mm², with PE L, N and PE, if it matches the diagram
    4G6 Four cores of 6 mm², with PE L1, L2, L3 and PE, when N is not required
    5G6 Five cores of 6 mm², with PE L1, L2, L3, N and PE
    ⚡ Important PE rule: the green-yellow core is intended for the protective conductor, not for a phase, neutral or control signal. If the equipment requires PE, a two-core cable must not be arbitrarily used as a three-core power solution.

    Load, power and cable cross-section selection

    An electrical cable is selected according to the load current, not by a single universal rule of how many amps 1 mm² of copper “can carry”. The current-carrying capacity depends on temperature, number of cores, cable construction, installation method and cooling.

    Single-phase 230 V load

    Appliance power Current at 230 V What else to check?
    500 W 2.17 A Appliance connection class
    1000 W 4.35 A Cores, plug and connections
    1500 W 6.52 A Continuous thermal conditions
    2000 W 8.70 A Current-carrying capacity and environment
    3000 W 13.04 A Suitability of terminals, cord and plug
    3680 W 16.00 A Parameters and protection of the whole circuit
    Single-phase circuit formula:
    I = P / (U × cos φ)
    Example: 2300 W / 230 V = 10 A at cos φ = 1. For motors, efficiency and starting current must also be considered.

    Three-phase 400 V load

    For a balanced three-phase system the formula is:

    I = P / (√3 × U × cos φ × η)
    P – useful mechanical power when the motor efficiency η is included in the formula; U – line voltage. If P is the electrical input power, η is not applied additionally.
    Three-phase electrical power Current, cos φ = 1 Current, cos φ = 0.8
    3 kW 4.33 A 5.41 A
    5 kW 7.22 A 9.02 A
    10 kW 14.43 A 18.04 A

    The table values are for calculating current but are not cable current-carrying capacity tables. A 6 mm² cable must not automatically be matched to a circuit breaker of a specific rating without assessing its installation and cooling conditions.

    Cable length and voltage drop: calculation examples

    Electrical energy is transmitted with losses in the conductor resistance. The longer the run, the higher the total circuit resistance. This is especially important when connecting equipment with longer power cords or designing distribution circuits.

    Below are the maximum DC resistances of class 5 flexible copper conductors at +20 °C, suitable for simplified calculation.

    Cross-section Class 5 resistance at +20 °C Note
    1.5 mm² 13.3 Ω/km Flexible conductor value
    2.5 mm² 7.98 Ω/km Lower resistance
    4 mm² 4.95 Ω/km For comparison
    6 mm² 3.30 Ω/km For calculations of BVV-F 6 mm² variants
    1.5 mm² 12.1 Ω/km Class 2 – BVV-PL
    2.5 mm² 7.41 Ω/km Class 2 – BVV-PL

    Single-phase line example at 10 A

    One-way length 1.5 mm² 2.5 mm² 6 mm²
    10 m 2.66 V 1.60 V 0.66 V
    20 m 5.32 V 3.19 V 1.32 V
    30 m 7.98 V 4.79 V 1.98 V
    50 m 13.30 V 7.98 V 3.30 V
    Simplified single-phase circuit formula:
    ΔU ≈ 2 × L × I × R / 1000
    L – one-way length in metres; I – current in amperes; R – resistance of one core in Ω/km.
    ⚠ Calculation limits: the table uses class 5 (BVV-F) resistance at +20 °C, ignoring conductor heating, the reactive component and contact resistances. BVV-PL has class 2 conductors: 1.5 mm² – 12.1 Ω/km, 2.5 mm² – 7.41 Ω/km, so their voltage drop is about 7–9 % lower than in the table. Current-carrying capacity and voltage drop are separate checks.

    Technical parameters table

    Parameter BVV-F BVV-PL
    Basic construction Round, flexible Flat, fixed
    Conductor material Annealed copper Annealed copper
    Conductor class Class 5 (flexible) Class 2 (rigid stranded)
    Rated voltage U₀/U 300/500 V 300/500 V
    Insulation PVC PVC
    Sheath PVC PVC
    Max. continuous conductor temperature +70 °C +70 °C
    Short-circuit temperature +160 °C +160 °C
    Test voltage 2 kV 2 kV
    Installation temperature −5…+40 °C −5…+40 °C
    Operating temperature −15…+70 °C −30…+70 °C
    Bending radius > 5 × cable thickness > 5 × cable thickness
    Application Connection of appliances and equipment Fixed indoor installation
    CPR class Eca · LK-DoP 07/006/LT Eca · LK-DoP 07/007/LT
    BVV-F 5G6 specific dimensions example: five 6 mm² cores, outer diameter 14.64 mm, insulation thickness 0.8 mm, sheath thickness 1.0 mm. Dimensions will differ for other cross-sections and numbers of cores. View the 5G6 product →

    Damp rooms, UV, outdoor conditions and IP protection

    The operating environment is one of the most important cable selection criteria. A PVC sheath provides protection under normal conditions, but the cable's moisture resistance is not the same as a sealed connection or resistance to continuous exposure to water and ultraviolet radiation.

    Dry indoor environment
    Suitable for cables with the intended purposes, provided protection and installation requirements are met.
    Damp indoor environment
    Protection requirements for appliances, boxes, connections and cable entries are checked.
    Low temperature
    Operating temperature and permitted bending during installation are different parameters.
    Direct UV exposure
    A PVC sheath alone is no proof that the cable is suitable for long-term use in sunlight.
    Ground and water
    BVV-PL is not a cable for direct burial; BVV-F also cannot be considered as such without approval.
    Mechanical loads
    Vibration, tension, abrasion and continuous movement may require a special construction.
    ⚠ What about IP? A cable cannot automatically be assigned IP65 or IP67 just because of its PVC sheath. The IP rating is assessed for a specific enclosure, connection system or relevant device. In damp locations, suitable cable glands, seals, boxes and protective devices are important.

    How do BVV-F and BVV-PL differ from other cables?

    Different cables cannot be interchanged just because their cross-section is the same. For example, a flat solid-core cable and a round flexible cable may have the same rated voltage but a different permitted connection method.

    Cable type Purpose and construction Link
    BVV-F Round, flexible copper PVC cable for connecting appliances This group →
    BVV-PL Flat cable for fixed indoor installation This group →
    BVV-PLL Flat cable with flexible stranded cores BVV-PLL →
    BVV-P Flat, solid-core cable for fixed installation BVV-P →
    NHXMH-J Halogen-free cable for fixed installation NHXMH-J →
    H03VV-F / H05VV-F Standardised flexible PVC appliance connection cables for different load categories Copper cable catalogue →

    Installation recommendations and connection compatibility

    Cable service life is strongly affected by how the cores are prepared, how they are clamped in the terminals and whether excessive mechanical load is transferred to the cable.

    1. Suitable terminal
    Check whether the contact accepts solid or flexible stranded cores, depending on the specific cable.
    2. Crimp ferrules
    Where the terminal requires a ferrule, use a ferrule of the correct cross-section and type and a proper crimping tool.
    3. Strain relief
    The appliance power cord must be secured so that tension is not transferred directly to the contacts.
    4. Bending radius
    Do not kink the cable and do not exceed the permitted bending or temperature limits.
    5. Installation route
    Lay fixed BVV-PL according to installation zones and with adequate mechanical protection.
    6. Electrical testing
    Check insulation resistance, continuity of protective conductors, condition of connections and operation of protective devices.
    ⚡ Do not improvise with conductor connections. Do not leave unterminated stranded cores, do not use ferrules unsuitable for the terminals and do not change the purpose of protective conductors. Follow the instructions of the relevant connecting device before connecting.

    Most common selection and installation mistakes

    ✗ Wrong ✓ Right
    BVV-F is chosen for direct installation under plaster without checking its intended use. For fixed installation, choose a type permitted in the documentation, e.g. BVV-PL, when all conditions are met.
    BVV-PL is treated as a UV-resistant outdoor cable. For outdoor runs, check direct confirmation of UV and environmental resistance.
    A two-core cable is used for equipment that requires PE. Choose a suitable cable with a protective conductor.
    The circuit breaker for a 6 mm² cable is selected only by core cross-section. Assess current-carrying capacity, installation method, temperature and disconnection conditions.
    Flexible conductors are connected to unapproved terminals. Use compatible terminals and ferrules where required.
    Tension on the appliance power cord is taken by the contacts. Use a reliable cable strain relief device.
    PVC cable is considered halogen-free. Where required, choose a suitable LSOH construction and CPR class.
    An ordinary connection cable is constantly flexed. For continuous dynamic cycles, use a construction tested for this.

    Fazė's tips and Elsprendimai.eu recommendations

    Fazė
    Fazė recommends

    Start with the question of whether the cable will move with the appliance or be installed as a fixed part of the run. Then determine the number of cores, protective PE, rated voltage, cross-section and environmental conditions. Only after these checks compare cable prices and lengths.

    Need a flexible round cable?

    View BVV-F variants, including BVV-F 5G6, if you need five 6 mm² cores.

    Need flat installation cable?

    Choose according to permitted fixed installation; BVV-PL variants in the category.

    Need solid cores?

    Compare with BVV-P and check terminal compatibility.

    Need a halogen-free cable?

    View NHXMH-J according to the required CPR class.

    Diagram: wrong and correct cable selection

    ✗ WRONG
    Power supply needed
    ↓
    Any PVC cable is chosen
    Based only on cross-section and price
    ↓
    Installed without considering the intended use

    It is unclear whether the cable is suitable for fixed installation, movement, moisture and PE requirements.

    ✓ RIGHT
    Purpose and environmental conditions
    ↓
    BVV-F or BVV-PL according to purpose
    Cores, PE, load, connections, documents
    ↓
    Properly installed and tested circuit

    The right cable type, number of cores, protection and connection method are selected.

    FAQ – Kibirkštis asks, Fazė answers

    15 practical questions about BVV-F and BVV-PL cables – from their construction and use to proper conductor connection, short circuit, voltage drop, electrical safety and suitable alternatives.

    Kibirkštis
    Kibirkštis · Question 1Why are BVV-F and BVV-PL cables grouped together if their purposes differ?
    Fazė
    FazėBoth are copper power cables of PVC construction, so they can be grouped together in a retail catalogue. However, BVV-F is primarily intended for connecting equipment, and BVV-PL for fixed electrical installation. The same rated voltage or copper core cross-section does not mean they are interchangeable. Before choosing, always assess whether the cable will be moved or installed on a fixed route. More in the BVV-F and BVV-PL comparison.
    Kibirkštis
    Kibirkštis · Question 2Can a BVV-F cable be used to connect a washing machine?
    Fazė
    FazėYes, a BVV-F of suitable construction can be used for such a connection, but not any cross-section or number of cores. A washing machine usually requires protective earthing, so a PE conductoris important. Also consider the appliance instructions, rated power, plug, terminal type, mechanical protection of the cord and exposure to moisture. The original appliance cord must not be arbitrarily replaced with another cable without checking its suitability.
    Kibirkštis
    Kibirkštis · Question 3Does BVV-F 5G6 mean I can connect any 400 V three-phase device?
    Fazė
    FazėNot any. 5G6 means five 6 mm² cores, including PE, but connecting a specific device depends on the load current, starting modes, protective devices, connections and the cable environment. A 300/500 V rating can be suitable for a 230/400 V system, but 6 mm² cannot automatically be linked to a specific permissible number of amperes. View BVV-F 5G6 →
    Kibirkštis
    Kibirkštis · Question 4If BVV-F is flexible, can I use it in a constantly moving machine?
    Fazė
    FazėA flexible class 5 copper core makes shaping and connecting the cable easier, but it does not guarantee resistance to continuous bending cycles. If a machine part moves in every work cycle, or the cable is pulled or exposed to strong vibration, a product specifically designed for this is required. Otherwise, the strands, insulation or cable sheath may eventually be damaged.
    Kibirkštis
    Kibirkštis · Question 5Can BVV-PL cable be laid under plaster without an additional conduit?
    Fazė
    FazėBVV-PL is intended for fixed indoor installation, including laying under plaster. However, the specific installation solution must comply with local electrical installation rules, the building construction and the design requirements. Where additional mechanical protection or replaceability is needed, or the design requires it, a suitable conduit or trunking is provided. The sheath must not be damaged, the bending radius must not be arbitrarily reduced, and the cable must not be laid outside the permitted installation zones.
    Kibirkštis
    Kibirkštis · Question 6Is BVV-PL 2×2.5 suitable for an earthed socket installation?
    Fazė
    FazėA two-core cable alone cannot form a normal L, N and PE circuit, as there is no third protective core. 2.5 mm² is a cross-section, not confirmation of earthing. An earthed socket requires a properly installed PE conductor and an installation matching the design. Most often a suitable three-core cable with L, N and PE is chosen for such a circuit, after checking the cross-section and protection.
    Kibirkštis
    Kibirkštis · Question 7What is the difference between 4G6 and 5G6? Are five cores always needed?
    Fazė
    FazėNot always. 4G6 can be suitable for a three-phase device that needs L1, L2, L3 and PE but no N. 5G6 can be used for a circuit with L1, L2, L3, N and PE. Nevertheless, the core colours and functions must match the device diagram. If you choose a four-core cable for a device that requires a neutral and a protective PE, one conductor may be missing. Therefore, we do not select a cable solely by the number of phases of the device.
    Kibirkštis
    Kibirkštis · Question 8Can a 6 mm² copper cable always work with a 32 A MCB?
    Fazė
    FazėNo. The cable’s continuous current-carrying capacity depends on the installation method, temperature, number of loaded cores, cable grouping, cooling and other parameters. If a 6 mm² cable is installed in thermal insulation, its permissible load may differ from that of an openly installed cable. The MCB is selected to protect the whole circuit, not just according to the nominal copper cross-section. See the load calculation section.
    Kibirkštis
    Kibirkštis · Question 9Can I install BVV-PL in a yard if the cable runs in black trunking?
    Fazė
    FazėThe colour of the trunking alone does not guarantee the cable is suitable outdoors. Check whether outdoor use is permitted for the cable itself, whether the trunking protects against UV, water and mechanical loads, and whether condensation will accumulate. BVV-PL is intended for fixed indoor installation, so for an outdoor route it is safer to choose a product with clearly stated suitability for the specific environment. Cable resistance cannot be judged solely from the fact that it has a PVC sheath.
    Kibirkštis
    Kibirkštis · Question 10Are these cables suitable for a bathroom or another damp room?
    Fazė
    FazėUnder suitable conditions – yes, but a damp room does not mean the effects of water can be ignored. In bathrooms, electrical safety zones, IP protection of equipment, additional protection against electric shock, PE and proper sealing of connections must be considered. The PVC material of the cable sheath does not by itself give the whole installation IP65 or IP67 protection. All connection parts must suit the operating environment.
    Kibirkštis
    Kibirkštis · Question 11Why do soft copper cores sometimes require crimp ferrules?
    Fazė
    FazėA flexible core consists of many fine copper strands. In some terminals, without proper preparation the strands may spread unevenly or be damaged. A crimp ferrule can help form a neat contact, but it is used only when such a connection method is specified in the terminal documentation. Some spring terminals allow direct connection of a stranded core. The need for a ferrule cannot be determined from the cable type alone.
    Kibirkštis
    Kibirkštis · Question 12If I connect an appliance with a 30-metre cable, will 1.5 mm² be enough?
    Fazė
    FazėLength and cross-section alone are not enough. You need to know the appliance current, power factor, cable laying conditions and permissible voltage drop. For example, on a 30 m single-phase line at 10 A, a simplified calculation at +20 °C for a 1.5 mm² class 5 copper core gives a voltage drop of about 7.98 V . For 2.5 mm² it would be about 4.79 V. The cable’s continuous current-carrying capacity must still be checked. More in the voltage drop table.
    Kibirkštis
    Kibirkštis · Question 13Is a PVC cable automatically fire-resistant and halogen-free?
    Fazė
    FazėNo. A PVC construction is not halogen-free, and a cable’s reaction to fire and its ability to maintain circuit operation during a fire are different properties. If the design requires low smoke or a specific CPR class, an appropriate cable must be chosen. You can compare the NHXMH-J halogen-free cable group. Always check the reaction-to-fire declaration of the specific product.
    Kibirkštis
    Kibirkštis · Question 14How does BVV-F differ from H05VV-F, and are they interchangeable?
    Fazė
    FazėBoth names can be associated with flexible PVC power cables, but their equivalence must be confirmed by the specific product’s standard designation, data sheet and conditions of use. The “BVV-F” label alone is not enough to claim that every variant exactly matches a specific H05VV-F construction. Compare the conductor class, voltage, temperature, mechanical resistance and core marking.
    Kibirkštis
    Kibirkštis · Question 15How do I order the right cable length and avoid mistakes?
    Fazė
    FazėFirst determine the actual length of the route or the appliance connection. Allow for bends, vertical runs, connection reserve and technological losses. If you are ordering a cable for an appliance, check the permissible cord length and mechanical fixing conditions. If you are ordering for a fixed installation, don’t forget the voltage drop and the design. On each product page, also check the minimum order quantity – for some variants in this group a 10 m minimum. Open the cable category →
    Kibirkštis Fazė Kibirkštis and Fazė remind you: if you are not sure about the cable’s purpose, PE core, terminals or cross-section, it is better to clarify your choice before installation. Contact Elsprendimai.eu specialists.

    Technical standards, documents and important notes

    When choosing a cable and installing an electrical circuit, it is important to assess the conductor construction, electrical resistance, rated voltage, fire characteristics and conditions of use.

    Important technical information

    BVV-F conductors are class 5 (flexible), BVV-PL conductors are class 2 (rigid stranded). Dimensions, weight, bending radius and operating temperature differ by type and cross-section – the exact data for each variant is on its product page (verified against AB Lietkabelis datasheets).

    A PVC cable cannot automatically be considered halogen-free, UV-resistant, suitable for direct burial in soil or capable of maintaining power supply during a fire. Such properties must be confirmed in the specific product’s documentation.

    Liability and usage note: the technical tables, formulas, comparisons and selection examples in this guide are for information only. They do not replace the specific product’s technical document, declaration of performance or electrical design. The final cable type, cross-section, protective devices, connection method and laying conditions must be determined by a qualified specialist. UAB “Elektrotechnikos sprendimai” is not liable for the consequences of incorrect selection, incorrect connection or non-compliant installation to the extent permitted by applicable law.

    Need BVV-F or BVV-PL cables for a project or equipment?

    State the cable’s purpose, required number of cores, cross-section, length, installation location and the parameters of the appliance or circuit. We will help compare suitable cable variants, check availability and provide a quote for the required quantity.

    Contact Elsprendimai.eu
    Read more
    Cable 2x1.5 | copper | stranded, class 2 | flat | BVV-PL 2x1.5 | 1 m | white
    Code: BVV-PL 2x1,5
    Flat cable for fixed indoor installation under plaster or in installation trunking. Manufacturer AB Lietkabelis, DoP LK-DoP 07/007/LT, Eca. Minimum order quantity – 10 m.
    Price 0.64 € VAT incl.
    ( 0.53 € VAT excl. )
    Cable 2x2.5 | copper | stranded, class 2 | flat | BVV-PL 2x2.5 | 1 m | white
    Code: BVV-PL 2x2,5
    Flat cable for fixed indoor installation under plaster or in installation trunking. Manufacturer AB Lietkabelis, DoP LK-DoP 07/007/LT, Eca. Minimum order quantity – 10 m.
    Price 0.98 € VAT incl.
    ( 0.81 € VAT excl. )
    Cable 5x6 | copper | flexible | round | BVV-F 5G6 | 1 m | white
    Code: BVV-F 5G6
    Round flexible cable for connecting electrical appliances and equipment. Manufacturer AB Lietkabelis, DoP LK-DoP 07/006/LT, Eca. Minimum order quantity – 10 m.
    Price 5.53 € VAT incl.
    ( 4.57 € VAT excl. )
    Cable 2x6 | copper | flexible | round | BVV-F 2x6 | 1 m | white
    Code: BVV-F 2x6
    Round flexible cable for connecting electrical appliances and equipment. Manufacturer AB Lietkabelis, DoP LK-DoP 07/006/LT, Eca. Minimum order quantity – 10 m.
    Price 2.29 € VAT incl.
    ( 1.89 € VAT excl. )
    Cable 3x6 | copper | flexible | round | BVV-F 3G6 | 1 m | white
    Code: BVV-F 3G6
    Round flexible cable for connecting electrical appliances and equipment. Manufacturer AB Lietkabelis, DoP LK-DoP 07/006/LT, Eca. Minimum order quantity – 10 m.
    Price 3.84 € VAT incl.
    ( 3.17 € VAT excl. )
    Cable 4x6 | copper | flexible | round | BVV-F 4G6 | 1 m | white
    Code: BVV-F 4G6
    Round flexible cable for connecting electrical appliances and equipment. Manufacturer AB Lietkabelis, DoP LK-DoP 07/006/LT, Eca. Minimum order quantity – 10 m.
    Price 4.41 € VAT incl.
    ( 3.65 € VAT excl. )
  • Subscribtion to new arrivals

    privacy policy

    Information