Products catalog

Speed regulators for fans

  • Fan speed controllers: how to choose the right type

    A speed controller reduces a fan's airflow and noise when full capacity is not needed, and lets you return to full power when required. In this group you will find three types of solutions: electronic (triac) controllers, transformer controllers and smart controllers with a CO₂ sensor. Which one suits you is determined not by the size of the fan but by its motor control method and current.

    Kibirkštis Kibirkštis: The fan in my bathroom is too loud. Can I just take any controller?
    Fazė Fazė: No. First we check whether the motor is voltage-controllable (AC), or whether it is an EC fan with a 0–10 V input. Then comes the current with a safety margin. Only then do we decide: electronic, transformer or automatic CO₂-based control.

    1. First step – what kind of fan motor?

    Motor How to recognise it What fits
    AC single-phase 230 V, voltage-controllable L, N, PE terminals; datasheet says “speed controllable” / “regelbar” Electronic or single-phase transformer controller
    AC three-phase 400 V, voltage-controllable 3 phases; manufacturer permits voltage control Three-phase transformer or three-phase electronic controller
    EC (electronically commutated) Separate 0–10 V / PWM control terminals 0–10 V potentiometer or CO₂ controller with 0–10 V output – not a power controller
    2–3 speed AC motor Several winding leads (1–2–3) Step switch or 3-speed CO₂ controller

    ⚠ Important: Never supply an EC fan through a triac or transformer controller – you will damage its electronics. Fans with a built-in timer, humidity or motion sensor may only be speed-controlled if the manufacturer allows it. Three-phase motors intended for frequency control use frequency inverters, not voltage controllers.

    2. Electronic, transformer or CO₂ controller? Comparison

    Feature Electronic (triac) Transformer Smart CO₂ controller
    Operating principle A triac cuts part of the sine wave (phase-angle control) – the effective motor voltage drops Autotransformer taps supply a lower but sinusoidal voltage Measures CO₂ (often also VOC, PM2.5, temperature, humidity) and adjusts the speed itself
    Speed adjustment Stepless In steps (usually 5) 3-speed outputs for AC fans or a 0–10 V signal for EC fans
    Noise at low speed Motor hum possible – reduced by setting the minimum speed trimmer correctly Quietest – no additional hum Depends on the controlled fan
    Motor heating Higher during long operation at low speed Lower, the motor runs more gently Depends on the control method
    Size and mounting Compact: flush-mounted, surface-mounted, on DIN rail Larger and heavier: on the wall, in a plant room or in a panel Wall-mounted controller with display, often Wi-Fi / RS485
    In our range 0.5–10 A single-phase, 3–6 A three-phase, with 0–10 V / Modbus / TK 1–20 A single-phase and three-phase 400 V, with TK protection AC 3-speed and EC 0–10 V models
    Price Lowest Higher Highest
    When to choose Bathrooms, kitchens, duct fans; when you need compact, stepless control or 0–10 V / Modbus automation When quiet operation matters (bedrooms, offices, classrooms), larger duct and industrial fans, three-phase motors When ventilation should run on demand: offices, classrooms, halls, flats and houses with heat recovery
    Subgroup Electronic controllers → Transformer controllers → CO₂ controllers →

    3. Current – how not to get it wrong

    • The controller's rated current must be no lower than the fan's rated current plus a 20–30 % margin – the motor's starting current is higher than its running current.
    • Take the current (A) from the fan's rating plate rather than calculating it from watts – small motors often have a cos φ of only 0.5–0.8.
    • Several fans on one controller – the currents add up, and all fans must be of the same type and voltage-controllable.
    • An oversized controller on a very small fan may run unstably – choose the nearest suitable current class.

    Detailed current table, mounting locations, IP ratings and the full model matrix – in the fan speed controller selection guide.

    Fazė Fazė: If the fan hums at low speed on a triac controller, this is not a fault but a feature of phase-angle control. Raise the minimum speed with the trimmer or choose a transformer controller.

    4. What else you may need

    This information is indicative and intended to make your choice easier. Base the final decision on the fan manufacturer's data; UAB „Elektrotechnikos sprendimai“ accepts no responsibility for product selection made solely on the basis of this description. Not sure? Write to info@elsprendimai.eu or call +370 658 01033 – we will help you choose.