  • HVAC automation: sensors, controllers and actuators for ventilation and heating

    A good ventilation system knows how much air is needed – and doesn't waste energy when it isn't.

    What do you need? Choose – we'll take you straight to the products:

    Ventilate according to occupancy

    CO₂ controller for the fan

    CO₂ controllers →

    Single-phase AC fan speed

    Transformer controller (not for EC!)

    Controllers →

    Three-phase motor, pump

    Frequency inverter

    Inverters →

    Open or close a damper

    Actuator 5–15 Nm, 230 / 24 V

    Actuators →

    Temperature, humidity, CO₂

    Room and duct sensors

    Sensors →

    Control remotely

    Modbus and internet modules

    Modbus modules →
    KibirkštisFazėNeed more information? Selection guide – AC or EC, signals, wiring diagram, mistakes and FAQ. Or ask us.
  • HVAC automation guide: from sensor to controlled fan

    Here you will find quick selection by situation, how the control chain works, a comparison of simple and smart solutions, fan and damper control, a wiring diagram with explanations, the most common mistakes and answers to key questions.

    Colour legend: ■ information · ■ benefit, solution · ■ ⚠ check · ■ ⚡ safety, mistakes

    What do you need? Quick selection

    Situation Solution Where to look
    Meeting room, classroom, office – ventilate according to occupancy CO₂ sensor + fan speed control based on CO₂ (demand-controlled ventilation) CO₂ sensors, smart controllers with CO₂
    Maintain temperature in a room, duct or water circuit Temperature sensor or thermostat + controller temperature sensors, thermostats
    Bathroom, swimming pool, warehouse – humidity control Humidity or temperature and humidity sensor controls the extract fan humidity sensors, T + RH sensors
    Filter clogging, fan operation, constant pressure Differential pressure switch, transmitter or PI controller pressure switches and transmitters
    Single-phase AC fan speed – simple and quiet Transformer (stepped) or electronic (stepless) speed controller transformer controllers, electronic controllers
    EC fan with 0–10 V input Controller or sensor with 0–10 V / PWM output, power supply – directly from the mains PI controllers, controllers with 0–10 V
    Three-phase motor: fan, pump, compressor Frequency inverter – soft start and speed control frequency inverters, electric motors
    Open, close or modulate an air damper 230 V or 24 V actuator, open / close or 0–10 V control damper actuators, motorised dampers
    Monitor and control remotely, log history Modbus RTU network + internet gateway Modbus modules
    Heating circuit: flow, temperature, level Flow and temperature meters, level sensors flow meters, level sensors

    Demand-controlled ventilation – less noise and lower bills

    A fan that runs at full speed all the time wastes electricity and heats or cools air that nobody needs. A sensor and controller match the speed to the actual demand – when the room is empty, the system runs slower. We supply the whole chain: sensors, controllers, speed controllers, frequency inverters, motors and actuators that are compatible with each other. Send us a description of your system – we will select a solution.

    How it works: measure → decide → act

    Every HVAC automation system consists of three parts: the sensor measures (CO₂, temperature, humidity, pressure), the controller compares the value with the setpoint and decides, and the actuator – a fan, damper actuator, valve or pump – carries out the action. All parts must "speak" the same signal language.

    Sensor
    CO₂, T, RH, Δp
    →
    Signal
    0–10 V, 4–20 mA, Modbus
    →
    Controller
    setpoint, PI, timer
    →
    Actuator
    fan, actuator, pump
    →
    Result
    air, comfort, energy
    Signal What it is What to watch out for
    0–10 V Analogue voltage signal – the most common in HVAC sensors, controllers, EC fans and actuators. Sensitive to interference on long runs – use shielded cable, routed separately from 230 V.
    4–20 mA (0–20 mA) Analogue current signal. More resistant to interference and suited to long runs; the 4 mA live zero allows a broken wire to be detected.
    PWM Pulse-width modulation – common for EC fans. Check which PWM frequency and level the fan accepts.
    Relay contact On / off: alarm, speed step switching, start. Do not switch a motor directly through the contact if the permitted contact current is lower than the motor current and its starting current – use a contactor.
    Modbus RTU Digital communication over an RS-485 line: values, settings, alarms. Daisy chain from device to device, terminating resistors (usually 120 Ω – per device instructions) at both ends, unique addresses.
    Passive sensor (PT1000, NTC) Resistance changes with temperature; the controller measures it directly. The sensor type must match the controller input.

    Simple or smart? Four levels of automation

    Not every system needs a BMS. Choose the level based on how much you want to control yourself and how much the automation should do.

    1 · Manual

    Switch or stepped speed controller

    The user selects the speed. Simple, inexpensive, almost nothing to go wrong.

    Where to use: Workshops, warehouses, garages, constant-load ventilation.

    Products: transformer controllers, electronic controllers

    2 · Stand-alone

    Sensor + speed controller in one unit

    The speed adjusts automatically according to temperature, humidity or CO₂ – no separate controller or programming needed.

    Where to use: A single room or a single fan: meeting room, bathroom, greenhouse, basement.

    Products: controllers with CO₂, temperature-based speed controllers

    3 · 0–10 V controller

    Sensors, PI controllers, EC fans, actuators

    Continuous (stepless) control to a setpoint: constant pressure, CO₂ limit, temperature. Several sensors and actuators in one system.

    Where to use: Air handling units, VAV systems, offices, schools, production facilities.

    Products: pressure controllers, CO₂ sensors, actuators

    4 · Network and internet

    Modbus RTU + internet gateway or BMS

    All devices on one line: view values, change settings, receive alarms remotely and log history.

    Where to use: Multiple sites, remote maintenance, energy monitoring, service companies.

    Products: Modbus and internet modules, frequency inverters with communication

      Simple solution Smart solution
    Control Manual or based on a single sensor Based on multiple sensors, setpoints and time schedules
    Regulation Stepped or on / off Continuous, PI control
    Communication None or relay contact 0–10 V, 4–20 mA, Modbus RTU, internet
    Energy savings Limited Highest – ventilation only as much as needed
    When to choose Single fan, constant load, small budget Variable load, multiple units, remote maintenance
    Kibirkštis
    KibirkštisSo smart is always the better choice?
    Fazė
    FazėNo. A stepped speed controller is enough for garage extraction. But where occupancy varies – meeting room, classroom, sports hall – CO₂ control pays back fastest: the fan runs only when it is needed.

    Fan speed control: AC, EC or three-phase

    Motor type How to control What not to do Where to look
    Single-phase AC (voltage-controllable) Transformer speed controller – quiet, usually 5 steps; electronic – stepless, compact. Do not choose a controller rated for less current than the fan's maximum; check that the manufacturer allows voltage control. transformer controllers, electronic controllers
    EC (electronically commutated) Via 0–10 V or PWM signal, power supply – directly from the mains. Do not supply it through a transformer or TRIAC speed controller. PI controllers, controllers with CO₂
    Three-phase induction Frequency inverter; for simple applications – three-phase autotransformer, if the motor manufacturer allows voltage control. Do not choose an inverter with a lower current than the motor's rated current; do not switch a contactor or switch between the inverter and the motor while the inverter output is active. frequency inverters, three-phase autotransformers

    How to calculate: the fan rating plate states a maximum current of 2.3 A – choose a speed controller with a rated current of at least that, e.g. 3 A or more. Three-phase 1.5 kW motor, 400 V, rated current 3.4 A – the frequency inverter must be 400 V, rated at least 1.5 kW, with an output current of no less than 3.4 A. If you only have a single-phase 230 V supply, choose an inverter with a 1-phase input and a 230/400 V motor connected in delta (Δ 230 V) – the motor current is then higher, about 5.9 A for this motor, and the inverter output current must be no lower.

    Air damper actuators: how to select

    What to look at What it means
    Torque, Nm Must match the damper area and design – check the Nm/m² value specified by the damper manufacturer and add a safety margin.
    Power supply 230 V AC or 24 V AC/DC – must match the control circuit.
    Control type Open / closed (2-point), 3-point or modulating 0–10 V.
    Spring return On power loss, a spring-return actuator moves to a safe position (e.g. closes the outdoor air for frost protection). Our range includes actuators without spring return, 5–15 Nm; spring-return actuators available on request.
    Fire dampers ⚡ Only actuators approved by the damper manufacturer and tested together with the damper are suitable (EN 15650) – standard HVAC actuators are not suitable.

    A ready-made solution for small ducts – motorised dampers with a 24 V actuator, Ø100–315 mm.

    Diagram: sensor, controller, fan, damper and Modbus – wrong and right

    On the left – typical mistakes we see on site; on the right – how it should be done. The numbers in the diagram correspond to the explanations below it.

    Kibirkštis
    KibirkštisI've wired the system, but the fan sometimes surges and Modbus keeps losing devices. Where should I look?
    Fazė
    FazėAlmost always – in the wiring. A 0–10 V signal next to 230 V cables, an EC fan through a transformer speed controller, Modbus wired as a "star" without terminating resistors. Look at the diagram from 1 to 4.
    HVAC automation wiring: sensor, controller, fan, damper, Modbus – diagram | elsprendimai.eu
    ☝ Click the diagram to open an enlarged version.
    ⚠ The diagram is for guidance only and may contain inaccuracies.
    Before connecting, check against the manufacturer's instructions and the markings on the device. Installation is the responsibility of the qualified electrician carrying it out. UAB „Elektrotechnikos sprendimai“ accepts no liability for the connection or any errors.

    Why – explanation by diagram number

    1Signal cable

    ✗ 0–10 V wire in the same trunking as 230 V cables.

    ✓ Shielded cable on a separate route; shield earthed at one end, as specified by the manufacturer.

    Why: Next to power cables, interference is induced into the signal line – a few hundred millivolts of noise on a 0–10 V scale turns into erratic speed or false temperature readings.

    Products: sensors · CO₂ sensors

    2EC fan control

    ✗ EC fan supplied through a transformer or electronic speed controller.

    ✓ Power supply – directly from the mains, speed – via 0–10 V or PWM signal.

    Why: The EC motor electronics need a constant supply voltage. Reduced voltage overloads them or the fan simply shuts down – speed is controlled by the signal only.

    Products: PI controllers · controllers with CO₂

    3Actuator torque

    ✗ Actuator chosen "by eye" – the damper does not close fully.

    ✓ Torque based on the damper area and the manufacturer's Nm/m², with a safety margin.

    Why: An undersized actuator does not seal the damper – in winter the heating coil freezes, in summer energy is lost. An overloaded actuator fails sooner.

    Products: damper actuators · motorised dampers

    4Modbus line

    ✗ Devices wired in a "star", no terminating resistors.

    ✓ One daisy chain from device to device, 120 Ω only at both ends.

    Why: RS-485 is a bus: stubs and unterminated ends cause signal reflections – devices "disappear" and communication errors occur.

    Products: Modbus modules

    ⚠ What to check before buying

    Kibirkštis
    KibirkštisBefore ordering, I write these things down – then the components fit together the first time.
    What to check Why it matters
    Fan motor type AC, EC or three-phase – this determines the speed controller or frequency inverter.
    Current and power The rated current of the speed controller or inverter must be no lower than the motor's.
    Signal compatibility Sensor output, controller input and actuator control – the same language (0–10 V, 4–20 mA, Modbus).
    Supply voltage 230 V or 24 V AC/DC – for sensors, controllers and actuators.
    Mounting location and IP Room, duct or outdoor – housing, degree of protection, temperature limits.
    Measuring range CO₂ ppm, °C, %RH, Pa – the operating value should be in the middle of the range.
    Communication and integration Whether Modbus addresses, BMS or remote access will be needed.

    ✗ Most common mistakes

    Mistake Consequence
    0–10 V signal next to 230 V cables Interference, unstable speed, false readings.
    EC fan through a voltage speed controller Fan electronics failure, loss of warranty.
    Speed controller rated for less current than the fan Overheating, fuse tripping, shorter service life.
    Sensor in the wrong location (near a door, radiator, supply air stream) Control reacts to local conditions rather than to the room.
    Modbus without terminating resistors, duplicate addresses Communication errors, "disappearing" devices.
    Contactor or switch between inverter and motor switched while the inverter output is active ⚡ Damage to the inverter output.
    24 V actuator connected to 230 V ⚡ Actuator failure and danger to people.
    Fazė

    ⚡ Safe installation – Fazė's advice

    • Before working, isolate the supply and make sure the fan cannot start automatically.
    • Frequency inverter capacitors remain charged after the supply is disconnected – wait for the time specified by the manufacturer.
    • Supply 24 V control from a safety isolating transformer – safety extra-low voltage (SELV), separate from 230 V.
    • Route signal and power cables separately.
    • After installation, check every link in the chain: sensor value, controller output, actuator response.
    ☝ Elsprendimai.eu recommends: for meeting rooms and classrooms – a controller with a CO₂ sensor; for AC fans – a transformer speed controller; for air handling units – pressure switches and PI controllers; for three-phase motors – a frequency inverter; for dampers – actuators selected by torque. For a multi-unit system – a Modbus and internet module.

    Frequently asked questions

    Questions from Kibirkštis – a young, curious electrician who dares to ask what others don't. Answers from Fazė – an experienced engineer.

    Kibirkštis
    KibirkštisHow do I tell an AC fan from an EC fan?
    Fazė
    FazėLook at the fan rating plate and terminals. An EC fan has signal terminals (0–10 V or PWM, sometimes Modbus) and is often marked "EC". An AC fan has only L, N, PE and sometimes multi-speed leads.
    Kibirkštis
    KibirkštisTransformer or electronic speed controller?
    Fazė
    FazėTransformer – quieter, stepped, reliable, but larger. Electronic – compact and stepless, but some motors may hum with it. Most importantly – check whether the fan manufacturer allows voltage control.
    Kibirkštis
    KibirkštisWhere should a CO₂ sensor be mounted?
    Fazė
    FazėIn the room, in the breathing zone, at a height of about 1–1.5 m, away from doors, windows and the supply air stream. A duct sensor goes in the extract air duct.
    Kibirkštis
    KibirkštisCan I control several motors with one frequency inverter?
    Fazė
    FazėYes, if the inverter current is no lower than the sum of the motor currents and each motor has its own thermal overload protection. In that case the inverter runs in U/f (not vector) mode. In most cases, however, a separate inverter for each motor is more practical.
    Kibirkštis
    KibirkštisHow many devices can be connected to one Modbus line?
    Fazė
    FazėOn a standard RS-485 line – up to 32 unit loads; the actual number depends on the devices. Each one must have a unique address, terminating resistors (usually 120 Ω) go only at the line ends, and line biasing at one point, usually in the controller.
    Kibirkštis
    KibirkštisDo you help with selection?
    Fazė
    FazėYes. Send us the fan data, room use or project – we will select sensors, controllers, speed controllers, frequency inverters and actuators. Contact us.

    Sources

    • Sentera Controls – technical data for sensors, controllers, speed controllers and Modbus modules.
    • Technical data from manufacturers of frequency inverters, electric motors and damper actuators (product pages).
    • Modbus over Serial Line Specification and Implementation Guide (Modbus Organization) – RS-485 bus, terminating resistors, line biasing.
    • EN 16798-3 – Energy performance of buildings. Ventilation for non-residential buildings.
    • EN 61800 series – Adjustable speed electrical power drive systems.

    Calculation examples are indicative – final parameters are specified by the equipment manufacturer or the project design. Checked on 2026-10-14.

    The complete HVAC automation chain – from sensor to motor

    Sensors, controllers, speed controllers, frequency inverters, electric motors, damper actuators and Modbus modules – all in one place. Send us a system description or project: we will select compatible components and prepare a quotation.