ELECTRICAL SAFETY · TRANSIENT OVERVOLTAGES · LIGHTNING PROTECTION · MODULAR SPD
Surge protective devices T1 / T2 / T3 | technical selection and installation guide
How to protect distribution boards and sensitive equipment against transient overvoltages: choosing the right SPD type, Uc, Up, Iimp, In, Imax, earthing system and protection stages.
T1 / T2 / T3
Surge protection types
10/350 µs
T1 lightning current impulse
8/20 µs
Discharge current impulse
DIN 35
Modular mounting in the board
Kibirkštis asks, Fazė answers – clear explanations of surge protection.
Key point
A surge protective device reduces the effect of a transient voltage impulse, but only a correctly selected and connected SPD can work as part of a coordinated protection system. The key parameters are T1 / T2 / T3 type, Uc, Up, Iimp, In, Imax, supply system configuration and disconnection and backup protection solutions. Short connecting conductors and effective equipotential bonding are just as important as the SPD itself.
1. What do you need? Quick SPD selection by building type
Selection starts with the building's lightning risk, the type of electrical service entrance, the external lightning protection system, the earthing configuration and the sensitivity of the equipment to be protected.
|
Situation |
Selection approach |
What to check? |
|
Main distribution board of the building |
T2 or T1+T2 according to lightning risk and design |
Service entrance, lightning protection, TN/TT system, Uc and Iimp |
|
Building with external lightning protection |
T1 or T1+T2 at the appropriate location |
Lightning current distribution and design conditions |
|
Additional sub-distribution board |
T2 where staged protection is required |
Distance and coordination with the incoming SPD |
|
Sensitive electronics |
Additional coordinated T3 |
Up, equipment impulse withstand, line protection |
|
Solar power plant |
Separate suitable SPDs for the AC side and the PV DC side |
PV Ucpv, DC system voltage and lightning protection |
|
Long-duration voltage deviations |
Voltage monitoring relay or another suitable disconnecting device |
An SPD is not a substitute for such protection |
Selection rule: T2 is not a universal substitute for T1. If the protection design requires a lightning current arrester, an SPD meeting the corresponding T1 test class is needed.
2. T1, T2, T3 and combined protection stages
|
Type |
Purpose |
Test parameters |
|
T1 |
Discharging lightning current impulses at the boundary of protection zones |
Iimp, 10/350 µs |
|
T2 |
Limiting induced and switching overvoltages |
In, Imax, 8/20 µs |
|
T3 |
Additional protection of terminal equipment |
Combination wave Uoc and others according to the test |
|
T1+T2 |
Limiting lightning current and residual overvoltages in a single device |
Iimp, In, Up and others |
|
T2+T3 |
Combined distribution and terminal equipment protection |
Test parameters of the corresponding types |
Older terminology may still use class B, C and D designations, but modern technical selection uses types T1, T2 and T3 according to the corresponding tests. They must not be confused with the B and C tripping characteristics of circuit breakers.
3. Uc, Up, Iimp, In, Imax – technical parameters explained
|
Parameter |
What does it mean? |
Relevance for selection |
|
Un |
Nominal system voltage |
E.g. 230/400 V AC system |
|
Uc |
Maximum continuous operating voltage |
Must suit the supply system and possible long-duration voltage conditions |
|
Up |
Voltage protection level under test conditions |
Coordinated with the equipment impulse withstand and installation effects |
|
Iimp |
Lightning impulse current, 10/350 µs |
Lightning current capability parameter of T1 SPDs |
|
In |
Nominal discharge current, 8/20 µs |
Assessment of SPD tests and impulse withstand capability |
|
Imax |
Maximum discharge current, 8/20 µs |
Must not be treated as the only indicator of protection quality |
|
Uoc |
Combination wave open-circuit voltage |
Relevant for the corresponding T3 tests |
|
Isccr |
SPD short-circuit current rating |
Important when coordinating with the prospective short-circuit current and protection |
|
TOV |
Temporary overvoltage of the network |
Verifies the SPD's ability to respond safely to longer-lasting overvoltages |
40 kA is not 40 kW. Discharge current is measured in kiloamperes, not watts. Moreover, 40 kA Imax and 40 kA Iimp are not equivalent quantities, because different impulse waveforms apply.
4. How does a surge protective device work?
Under normal network conditions an SPD has a very small effect on the protected circuit. When a transient overvoltage impulse occurs, its protective components start conducting or otherwise divert the impulse current, limiting the voltage rise between the protected conductors.
1. Normal operation
The network voltage does not exceed the continuous operating conditions of the device.
2. An impulse occurs
A lightning discharge or a switching process causes a transient overvoltage.
3. The SPD responds
A varistor, spark gap or combined circuit limits the overvoltage.
4. The effect is limited
The impulse voltage passed on to the downstream installation is reduced.
Varistor and spark-gap SPDs
Metal oxide varistors (MOV) change their conductivity depending on voltage and are commonly used in T2 SPDs. Spark gaps are used in designs intended for high impulse currents, including T1 solutions. Some SPDs combine different technologies to meet specific protection requirements.
5. Single-phase and three-phase systems: 230/400 V, TN-S, TN-C-S and TT
The same network voltage does not mean that any SPD can be used. The type of earthing system determines the arrangement of protection paths between the phase, neutral and protective conductors.
|
System |
Common SPD configuration |
Important |
|
Single-phase 230 V |
1+1 or another connection scheme suitable for the specific system |
L, N, PE and the supply system |
|
Three-phase 230/400 V TN-S |
3+1 or 4+0 according to the product and design |
Connection of L1, L2, L3, N and PE |
|
TN-C |
Configuration according to phases and PEN |
PEN and the N/PE separation point |
|
TT |
Suitable 1+1 or 3+1 scheme |
N–PE protection element and protection coordination |
|
PV DC |
Dedicated PV DC SPD |
Ucpv, polarity, DC currents and PV installation requirements |
2P or 4P alone does not define the whole scheme. What matters is the configuration of the internal protection elements – for example 1+1, 3+1 or 4+0. Connection is made according to the diagram of the specific SPD and the supply system.
6. Coordination of protection stages and selectivity
Staged surge protection makes it possible to distribute the impulse stress at different points of the electrical system. T1 is used where lightning current protection is required; T2 helps to limit transient overvoltages in sub-distribution boards, and T3 can be used close to sensitive equipment.
Service entrance / lightning protection zone boundary
↓
T1 or T1+T2
Where the design requires lightning current protection
↓
T2
Sub-distribution board and limiting of residual impulses
↓
T3
Additional protection of sensitive terminal equipment
Coordination of SPD stages depends on the design, product compatibility, connecting conductors and installation distances. Any two SPDs must not be assumed to form an automatically coordinated system.
7. Applications of surge protective devices
Houses and apartments
Protection of supply circuits for household appliances, computers, TVs and smart systems.
Offices and retail premises
Computer workstations, security systems, controllers and distribution boards.
Industrial automation
PLCs, measuring equipment, control panels and auxiliary electrical circuits.
Solar power plants
AC and DC side protection according to inverter, module and installation requirements.
Server rooms and data centres
Coordinated protection of power supply, communication and data lines.
Heating and ventilation automation
Supply of heat pumps, heat recovery units, controllers and sensitive electronic assemblies.
8. SPD, voltage monitoring relay, circuit breaker and RCD – what is the difference?
|
Device |
Main protection function |
What does it not do? |
|
SPD |
Limiting transient impulse overvoltages |
Does not stabilise the long-term network voltage |
|
Voltage monitoring relay |
Disconnecting the supply in case of impermissible voltage deviations |
Does not replace an SPD for limiting impulses on a nanosecond or microsecond scale |
|
MCB circuit breaker |
Protection against overload and short circuit |
Is not a surge protective device |
|
RCD / RCCB |
Detection of residual (leakage) current |
Does not limit transient voltage impulses |
|
RCBO |
Residual current and overcurrent protection |
Does not perform the SPD function |
Risk of a broken neutral conductor: if the neutral conductor is interrupted in a three-phase system, some single-phase loads may be exposed to a long-lasting dangerous overvoltage. Protection against such a fault requires a suitable disconnection solution, not just an SPD.
9. Installation in the distribution board – connection, PE and backup protection
1. Determine the supply system
TN-C, TN-S, TN-C-S or TT.
2. Select the SPD type
T1, T2, T3 or a combination according to the risk.
3. Check Uc and Up
Coordinate them with the network and the equipment withstand.
4. Provide overcurrent protection
Use a fuse or circuit breaker matched to the device where required.
5. Keep connections short
Route the conductors to the SPD and the PE busbar as short as possible, without unnecessary loops.
6. Coordinate the earthing
Ensure the required equipotential bonding.
7. Check the indication
Check the SPD operating status and the replaceable module indicators, if provided.
8. Document
Record the type, connection, protection and periodic inspection requirements.
Why does the length of connecting conductors matter?
When impulse current flows through the connecting conductors, their inductance creates an additional voltage. As a result, the overvoltage seen by the equipment may be higher than the rated Up of the SPD. Long wire loops should be avoided, and the connection topology and total conductor length should be chosen according to the installation standard and the product instructions.
Installation principle: The entire connection path matters for SPD effectiveness – from the phase conductors to the protective and equipotential bonding connections. A low Up value alone does not guarantee a low impulse voltage reaching the equipment.
Electrical safety: the surge protective device must be connected by a qualified electrician. The supply must be disconnected, the absence of voltage verified, and the board safety rules and the product wiring diagram followed.
10. Diagram: wrong / right – SPD installation and protection stages
✗ WRONG
Service entrance
↓
SPD of the wrong type
Long wires, unsuitable PE and protection coordination
↓
Higher residual overvoltage
Even an SPD with good electrical parameters may perform poorly if it is installed incorrectly.
✓ RIGHT
Service entrance and supply system
↓
Correctly selected T1 / T2 / T3 SPD
Short conductors, suitable backup protection and PE
↓
Coordinated transient overvoltage protection
All protection elements are assessed together with the supply network and installation conditions.
11. Practical examples of surge protection selection
|
Building |
Solution principle |
Additional conditions |
|
House without external lightning protection |
T2 or another stage determined by the service entrance and risk assessment |
Overhead line, service entrance conditions, supply system |
|
House with lightning protection |
T1 or T1+T2 at the service entrance |
LPS, equipotential bonding, coordination |
|
Industrial PLC panel |
Coordinated protection of AC supply and signal lines |
PLC inputs, cable routes, shields |
|
Solar power plant |
AC SPD and a separate suitable PV DC SPD |
PV maximum voltage, inverter, LPS |
|
Server room |
Staged SPD protection and data line protection |
Coordination of power supply, communication and equipotential bonding |
12. Most common SPD selection and installation mistakes
|
✗ Wrong |
✓ Correct |
|
Selecting only by the 40 kA or 20 kA marking. |
The type, Iimp / In / Imax, Uc, Up and the supply system are assessed. |
|
T2 is treated as a substitute for any T1 protection. |
Where required, a T1 lightning current SPD is used. |
|
An unsuitable Uc is chosen. |
Uc is matched to the actual network voltage and system. |
|
Long connection loops are left. |
A short, properly routed connection path is used. |
|
Unsuitable SPD backup overcurrent protection. |
The fuse or circuit breaker is matched to the SPD and system parameters. |
|
An AC SPD is used on the PV DC side. |
An SPD designed specifically for PV DC systems is used. |
|
The SPD status indication is not checked. |
Periodic inspection of the indication and connections is planned. |
13. Status indication, replaceable modules and maintenance
Some modular SPDs have a mechanical or optical status indicator that helps to determine whether the protective circuit is still fit for service. Some SPDs have replaceable protection modules and remote signalling contacts.
Status window
Colour or other indication helps to assess the module condition according to the marking of the specific device.
Replaceable module
Where the design allows, a failed protective cartridge is replaced with a compatible new one.
Remote signalling
Some models allow the SPD status to be transmitted to building automation or a monitoring system.
Periodic inspection
Performed according to the operating conditions, the facility maintenance programme and the SPD documentation.
Service life: There is no universal fixed 3–5 year replacement date for an SPD. Its condition depends on the technology, impulse intensity, operating conditions and the device status indication. The module is replaced when its condition or the product's technical requirements call for it.
14. FAQ – Kibirkštis asks, Fazė answers
10 practical questions about T1, T2 and T3 protection, voltage limitation, lightning impulses, single-phase and three-phase systems, installation and SPD maintenance.
Kibirkštis asks · 01 What is the difference between T1 and T2 surge protective devices?
Fazė answers T1 is designed to discharge part of the lightning current and is tested with a 10/350 µs impulse waveform. T2 is designed to limit transient induced and switching overvoltages; its 8/20 µs discharge current parameters are important. If a facility requires T1 protection, T2 alone is not an equivalent substitute.
Kibirkštis asks · 02 Is a 40 kA SPD always better than a 20 kA one?
Fazė answers Not necessarily. First you need to know whether 20 kA and 40 kA refer to Iimp, In or Imax. Identical kiloampere values obtained with different test impulse waveforms are not directly comparable. Protection quality is also determined by the SPD type, voltage protection level Up, continuous operating voltage Uc and installation conditions.
Kibirkštis asks · 03 What does Up = 1.5 kV on a surge protective device mean?
Fazė answers Up is the voltage protection level under specified test conditions. It is not the continuous mains voltage and does not guarantee that exactly 1.5 kV will appear at every device for any impulse. The actual voltage also depends on the connecting leads, the impulse current and the whole protection system.
Kibirkštis asks · 04 Will a surge protective device protect against a broken neutral conductor?
Fazė answers An SPD is not a substitute for such protection. A broken N conductor can cause a longer-lasting dangerous mains overvoltage. Appropriate mains voltage monitoring and disconnection devices are used for this. An SPD is designed to limit transient impulse overvoltages.
Kibirkštis asks · 05 Is T1 protection mandatory in a house with a lightning rod?
Fazė answers In a building with an external lightning protection system, it is often necessary to provide appropriate T1 or T1+T2 protection at the service entrance. The exact solution depends on the lightning protection design, conductor layout, service entrance and equipotential bonding. T2 alone, which is not intended for lightning current impulses, must not be regarded as a universal substitute for T1.
Kibirkštis asks · 06 Will one SPD at the service entrance protect all appliances?
Fazė answers An incoming SPD reduces the effect of impulse overvoltages, but long electrical circuits, sensitive appliances and separate signal lines may require additional protection stages. Some systems use T2, T3 and special SPDs for communication lines. The final solution is determined by the immunity of the protected equipment and the installation design.
Kibirkštis asks · 07 Must an SPD be connected to earth?
Fazė answers Connecting a power system SPD to PE or the appropriate equipotential bonding system is an essential part of the protection, but the exact connection depends on the TN or TT network and the SPD design. Inadequate equipotential bonding or long connecting conductors can significantly reduce protection effectiveness.
Kibirkštis asks · 08 Is an AC surge protective device suitable for the DC side of a solar power plant?
Fazė answers No. On the PV DC side, an SPD specifically designed for photovoltaic direct current networks is used. It must match the maximum possible DC voltage of the system and the PV circuit connection requirements. AC and DC devices are not freely interchangeable.
Kibirkštis asks · 09 How often should a surge protective device be replaced?
Fazė answers There is no uniform 3- or 5-year replacement period for all SPDs. Service life depends on the design, the overvoltage impulses experienced and the operating environment. If the device has a status indicator, its readings are assessed according to the instructions of the specific model. A damaged module or one in unsuitable condition must be replaced.
Kibirkštis asks · 10 What data should be provided to select the right SPD?
Fazė answers You need to know whether the network is single-phase or three-phase, its voltage, the TN or TT earthing system, whether the building has external lightning protection, what the service entrance is and what equipment is to be protected. It is also important whether an AC or PV DC device is needed, which protective devices are planned and whether several SPD stages will be used.
Kibirkštis and Fazė remind you
The right SPD is not simply the model with the highest kA figure. Effective protection consists of the correct T1 / T2 / T3 type, coordinated Uc and Up parameters, appropriate overcurrent protection, short connecting conductors and correct earthing and equipotential bonding.
15. Standards and electrical safety requirements
Surge protection systems are designed taking into account the technical purpose of the installation, the lightning risk, the building electrical system and the applicable electrical engineering rules.
-
IEC / EN 61643-11 – requirements and tests for surge protective devices connected to low-voltage power systems.
-
IEC / EN 61643-31 – requirements and tests for SPDs on the DC side of photovoltaic systems.
-
IEC / EN 61643-21 – test requirements for surge protective devices for telecommunication and signalling lines.
-
IEC 60364-4-44 – protection of low-voltage installations against voltage disturbances and electromagnetic influences, including impulse overvoltage issues.
-
IEC 60364-5-53 – selection and erection of devices for protection, isolation, switching and control, including SPDs.
-
IEC / EN 62305 series – protection against lightning, risk assessment and lightning effect mitigation measures.
Technical note: SPD type classification, lightning current tests, short-circuit withstand, protection level and permissible network configuration are characteristics of the specific product. Devices of different designs must not be considered identical merely because of matching rated voltage or discharge current markings.
Safety: surge protective devices reduce the effect of impulse overvoltages, but they do not ensure absolute protection against a direct lightning strike, impermissible long-term voltage deviations or all possible electrical system faults. Installation and testing are carried out in accordance with the electrical safety requirements applicable to the specific system.
Surge protective devices – for protecting distribution boards and sensitive equipment
Choose surge protective devices according to the mains voltage, T1 / T2 / T3 protection type, discharge current parameters, installation conditions and the needs of the protected equipment. If you need help, provide the single-phase or three-phase system parameters, earthing scheme and lightning protection information.
View surge protective devices Lightning current arresters Contact us
The final selection and installation of protective devices must comply with the network diagram, the facility's lightning protection design and the technical requirements of the specific devices.
Technical Data
Operating Voltage: Surge protectors are designed to operate with various voltages, typically from 230V to 400V (in three-phase systems).
Surge Protection Level (Protection Class): SPD (Surge Protection Device) classification, typically marked according to the IEC 61643 standard. These devices can have Class A, B, C, or D protection levels, depending on their operating range and power.
Direct Lightning Protection: Protects equipment from direct lightning strikes and sudden voltage fluctuations.
Indirect Surge Protection: Protects against voltage fluctuations that occur due to network changes, such as after equipment shutdown or network failure.
DIN Rail Mounting: Commonly used for mounting in distribution boards, ensuring easy and quick device installation.
Wired and Modular Mounting: Some models can be mounted on different connections, depending on the type of installation.
Service Life: Surge protectors often have a specific lifespan (usually 3-5 years), after which they need to be replaced or inspected.
Protection Degree (IP Class): IP20, IP44, IP65 – the protection degree depends on the device type and its intended location, e.g., indoor or outdoor conditions.
Response Time: The surge protector has a specific response time within which it cuts off high voltage, typically less than 1 ms.
Power Capacity: Devices can have various power capacities (e.g., 10kA, 20kA, or more), depending on the protection level and needs.
Usage:
Industrial Equipment: Surge protectors safeguard heavy industrial systems, equipment, and machines from lightning strikes and electrical network failures, which can damage equipment, cause downtime, and lead to expensive repairs.
Residential and Commercial Buildings: These devices are used in residential and commercial buildings to protect televisions, computers, air conditioners, heaters, household appliances, and other sensitive electronic devices from surges.
Data Centers and Servers: Surge protectors are essential in server rooms and data centers, where stability and equipment protection are critical, as servers are particularly sensitive to voltage fluctuations.
Electrical Networks and Power Plants: Used in electrical transmission and distribution networks to protect power generation and distribution equipment from lightning and other surge impacts.
Advantages:
Equipment Protection: The primary benefit is the protection of equipment from harmful surges that can damage electronic components, helping to avoid costly repairs and reducing downtime.
Quick Surge Response: Surge protectors ensure fast response to voltage fluctuations with a very short response time, often less than 1 ms, helping to effectively protect equipment.
Durability and Reliability: These accessories are durable and reliable, designed to withstand numerous surge impacts during their lifespan.
Easy Installation: The DIN rail mounting or free mounting options allow for easy integration of surge protectors into the existing electrical system without major modifications.
Wide Application Range: Suitable for both indoor and outdoor conditions, depending on the device's protection degree (IP class).
Disadvantages:
Limited Service Life: After prolonged use and frequent surge impacts, surge protectors lose their effectiveness and will need to be replaced.
Cost: They can be expensive, especially for devices designed for high-power systems, but the cost is justified in the long term by ensuring equipment protection.
Additional Costs and Installation Time: Although easy to install, some protection systems may require additional components and increase the overall system installation cost.
Protection Limitations: Some surge protectors may not be sufficient for extreme conditions, such as very strong lightning strikes, in which case a higher-class device may be needed.
Surge protectors are essential components for equipment protection, ensuring that equipment is shielded from potential lightning strikes, network disturbances, or other surge impacts. They are used in both industrial and residential buildings, as well as in electrical networks and data centers. While they may be more expensive and have a limited service life, their benefits—protecting equipment and ensuring stable system operation—are invaluable.