Selection guide: how to choose a temperature and humidity sensor
A humidity sensor controls bathroom and pool ventilation, dehumidifiers, panel heaters, and the microclimate of greenhouses and warehouses. But relative humidity depends heavily on temperature, so the same air shows completely different percentages in different places. This guide helps you choose a sensor based on three questions: who makes the decision (the sensor itself, a controller, or a person on a phone), what signal is needed and where the sensor will be installed. General sensor selection (PT1000, NTC, CO₂, pressure) is covered in the sensors and probes guide.
Blue – information Green – benefit to you Orange – ⚠ check this Red – ⚡ safety and errors
What do you need? Quick selection
|
Situation |
Solution |
Where to find it |
|
Bathroom or shower room fan must speed up as humidity rises – no controller available |
Sensor-controller: you set humidity (and, if needed, temperature) limits, and it generates the 0–10 V / 0–20 mA / PWM signal for an EC fan or speed controller by itself. Room and flush-mounted (IP30) types – outside bathroom zones 0–2, where splashes do not reach; for wetter locations a duct IP54 sensor in the extract air duct is more reliable. Pool hall humidity is controlled by the air handling unit – a transmitter suits it |
Room RCTHG-2 · Flush-mounted FCTHG · Duct DCTHG-2 |
|
A controller, PLC or BMS is already in place – only measurement is needed |
Transmitter: temperature and humidity on separate analogue outputs (0–10 V / 0–20 mA / PWM) and Modbus RTU; the control logic stays in the controller |
Room RSTHG-3 · Duct DSTHG-3 · LFH10 4–20 mA / 0–10 V |
|
Office, school, hotel – temperature and humidity of every zone to the BMS or AHU controller |
Room Modbus sensors (PoM – power and data over one RJ45 cable) or transmitters with 0–10 V; in the extract air duct – a duct sensor. For comfort ~40–60 % RH is usually targeted, and together with CO₂ ventilation follows occupancy |
Room RSTHM-2 · Room RSTHG-3 · Duct DSTHM-2 · CO₂ sensors |
|
Production hall, industrial warehouse, dryer – long lines, PLC, dust and moisture |
Transmitter with a current output (LFH10 – 4–20 mA, Sentera – 0–20 mA), which is more immune to interference on long lines, or Modbus RTU to a PLC or SCADA; for ducts – duct type IP54, for outdoor and wet zones – IP65, −30…+70 °C |
LFH10 4–20 mA · Duct DSTHG-3 · Outdoor ODTHM |
|
Many measuring points, Sentera fans or controllers, BMS via Modbus |
Modbus RTU sensors powered over the same RJ45 cable (PoM 24 V DC): one cable for both power and data |
Room RSTHM-2 · Duct DSTHM-2 · Sensor-controller DCTHM-2 |
|
Outdoor temperature and humidity, unheated warehouse, damp room |
Outdoor sensor IP65, −30…+70 °C, 0–100 % RH; with an integrated control algorithm – outdoor sensor-controller |
Outdoor ODTHM · Outdoor OCTHM-R |
|
Walls get damp, mould in the corners – you need to see the condensation risk |
Room sensor that additionally measures wall surface temperature: together with air humidity it shows whether the surface is approaching the dew point |
RWTHM-2 with wall surface sensor |
|
Electrical panel, metering cabinet, outdoor enclosure – condensation on equipment |
DIN rail hygrostat: when the set humidity is exceeded, it switches on the panel heater or fan |
Hygrostat PHG02 · panel heaters |
|
Basement, garage, greenhouse, drying room, incubator – simple on/off switching |
Digital controller with sensor and relay output; maximum load: 230 V version – 1500 W, 24 V – 240 W, 12 V – 120 W |
Humidity, 230 V · 24 V · 12 V · Dual T + RH |
|
Home, office or greenhouse monitoring on your phone |
Zigbee sensor with display (Zigbee hub required) or LoRa sensor for remote sites (LoRa gateway required); Wi-Fi sensor if gas detection is also needed |
SONOFF SNZB-02DR2 · IMOU ZTM1 · LoRa IP65 · Wi-Fi + gas |
|
Greenhouse, nursery, livestock or poultry building |
Control temperature and humidity together: too much humidity means disease and condensation, too little stresses the plants. To control a fan – an outdoor IP65 or duct sensor-controller with 0–10 V; for simple on/off – a controller with a relay; for monitoring – a Zigbee sensor with VPD (vapour pressure deficit) or LoRa for remote buildings. In livestock buildings, because of ammonia and dust, choose an IP65 housing and plan periodic checks |
Outdoor OCTHM-R · Duct DCTHG-2 · Controller 230 V · SONOFF with VPD · LoRa IP65 |
|
Irrigation based on actual soil moisture |
Soil moisture and temperature sensor: Modbus RTU or LoRa / LoRaWAN with additional parameters (EC, pH) |
Modbus SWCSM-075 · 8in1 LoRa |
What you gain by choosing correctly
-
Humidity-based ventilation: the fan runs harder only after a shower or bath, and at minimum speed the rest of the time. Less noise and lower heat losses.
-
No condensation or mould: walls, windows, panel equipment and stored goods stay dry.
-
The sensor fits the system straight away – no need to change the controller input or look for a different supply voltage on site.
-
Data you can trust: a correctly installed sensor shows the room air, not the air from a radiator or heater.
Transmitter, sensor-controller, hygrostat or wireless sensor?
All these devices measure temperature and humidity, but they differ in where the decision is made. First decide what will control the fan, dehumidifier or heater:
1. Transmitter
Only measures and transmits: separate 0–10 V / 0–20 mA signals or Modbus RTU. The decision is made by the controller, PLC or BMS.
2. Sensor-controller
Measures and calculates the control signal itself according to the set ranges. The fan or damper is connected directly to it – no separate controller needed.
3. Hygrostat / controller with relay
The relay contact switches on and off at a set threshold. The simplest on/off control, no programming.
4. Wireless sensor
Readings go to an app or the cloud (Zigbee, Wi-Fi, LoRa). For monitoring and smart home scenarios; for critical control a wired connection is better.
|
Type |
Output |
When to choose |
Examples |
|
Transmitter |
3 × 0–10 V / 0–20 mA / PWM + Modbus RTU; or 4–20 mA / 0–10 V |
The heat recovery unit or BMS controller has analogue inputs; you are replacing an old sensor |
RSTHG-3, RSTHF-3, DSTHG-3, DSTHF-3, LFH10, room RH 0–10 V + Modbus, room with LCD, duct with LCD |
|
Modbus sensor (PoM) |
Modbus RTU only, 24 V DC supply over the same RJ45 cable |
Many points, Sentera equipment, BMS; no analogue cabling wanted |
RSTHM-2, RWTHM-2, DSTHM-2, ODTHM |
|
Sensor-controller |
1 × 0–10 V / 0–20 mA / PWM control signal (in PoM versions – control value via Modbus) + Modbus RTU |
A single fan or zone: bathroom, pool, warehouse, production area |
RCTHG-2, RCTHF-2, RCTHH-2, FCTHF, FCTH8, DCTHF-2, OCTHM-R |
|
Hygrostat / controller with relay |
Relay contact (current and power – depending on model) |
Panel heater, dehumidifier, humidifier, fan without a controller |
PHG02, humidity controller 230 V, dual 24 V DC, dual 12 V DC |
|
Wireless |
Zigbee, Wi-Fi, LoRa – app or platform |
Monitoring, alerts, smart home scenarios, remote sites |
SONOFF SNZB-02DR2, IMOU ZTM1, LoRa IP65 |
Relative humidity, dew point and why sensor location is everything
Relative humidity (% RH) shows how much water vapour the air contains compared with the maximum amount the air can hold at the same temperature. Warm air holds more vapour, so when air is heated the amount of water stays the same while relative humidity drops. When cooled, it rises until it reaches 100 % and the vapour turns into condensate.
Outdoor air
0 °C, 80 % RH
→
Heat recovery unit and heater
heat it to +20 °C
→
Supply air
~21 % RH – same amount of water
→
Indoor air becomes humid
from people, showers, cooking
Dew point – the temperature to which air must cool for condensation to begin. If the surface of a wall, window or pipe is colder than the dew point, moisture condenses on it. Therefore:
|
Room |
What it usually controls |
Tip |
|
Residential, office |
Heat recovery unit intensity, humidification in winter |
For comfort, ~40–60 % RH is usually targeted; lower humidity in winter is normal |
|
Bathroom, shower room |
Extract fan speed |
Set the threshold above the normal level so the fan does not run around the clock – e.g. 65–70 % RH, and take the season into account |
|
Pool hall |
Air handling unit, dehumidification |
Humidity and air temperature are controlled together with water temperature according to the unit manufacturer's and design requirements |
|
Warehouse, basement, archive |
Dehumidifier, fan, heating |
Avoiding condensation is key: monitor both temperature and humidity |
|
Production hall, industrial site |
Ventilation, heating, dehumidification, process conditions (drying, painting, storage) |
Limits are set by the process or the product manufacturer; what matters is not only average humidity but also the risk of condensation on cold surfaces and structures |
|
Greenhouse, livestock building |
Ventilation, heating, fog humidification, window actuators |
For plants VPD matters – it combines temperature and humidity; in livestock buildings high humidity increases ammonia and disease risk. Limits are set by an agronomist or animal husbandry specialist |
|
Electrical panel |
Panel heater, fan |
The heater raises the temperature a few degrees above ambient – relative humidity in the panel drops and condensation does not form |
Power supply and signal: how not to pick the wrong version
Sensors of the same series often look identical but differ in power supply and outputs. In our range, the letter in the Sentera model name indicates the power supply variant:
|
Version |
Power supply |
Signal |
Examples |
|
…F |
18–34 V DC |
Analogue output(s) + Modbus RTU |
RSTHF-3, RCTHF-2, DSTHF-3 |
|
…G |
18–34 V DC or 15–24 V AC |
Analogue output(s) + Modbus RTU |
RSTHG-3, RCTHG-2, DCTHG-2 |
|
…H |
24 V DC via RJ45 (PoM) |
Analogue output + Modbus RTU |
RCTHH-2 |
|
…M |
24 V DC over the same RJ45 cable (Power over Modbus) |
Modbus RTU only – no analogue output; sensor-controllers (DCTHM-2, OCTHM-R) transmit the control value via Modbus |
RSTHM-2, DSTHM-2, DCTHM-2, ODTHM |
|
…8 |
85–264 V AC |
Analogue output + Modbus RTU |
FCTH8 |
The analogue output type (0–10 V, 0–20 mA or PWM) and range are usually selected in the settings (Modbus registers, jumpers or DIP switches – see the product description). PoM (Power over Modbus) uses an RJ45 connector, but it is not Ethernet and not PoE – do not connect it to a computer network switch. How signals travel to a fan or damper is described in the HVAC automation guide.
How to calculate: signal, dew point, relay load
1. Value from an analogue signal
Value = min + (signal − signal start) ÷ signal span × (max − min).
Example (4–20 mA, 0–100 % RH): the controller receives 13.6 mA → (13.6 − 4) ÷ 16 × 100 =
60 % RH.
Example (0–10 V, −30…+70 °C): signal 5 V → −30 + 5 ÷ 10 × 100 =
+20 °C.
2. Dew point (Magnus formula; its error is < 0.1 °C, real accuracy is determined by the sensor – ±2 % RH ≈ ±0.5 °C)
γ = ln(RH ÷ 100) + 17.62 × T ÷ (243.12 + T); dew point = 243.12 × γ ÷ (17.62 − γ).
Example: indoors +20 °C and 60 % RH → γ = −0.511 + 1.339 = 0.828 → dew point ≈
+12.0 °C. If an external wall corner or window frame is cooler than +12 °C – condensation will form there. For mould it is enough for relative humidity at the surface to stay around ~80 % for a long time (EN ISO 13788 criterion) – in this example that happens when the surface is cooler than approximately
+15 °C.
3. Will the hygrostat or controller relay handle the load?
Current = power ÷ voltage. Example: panel heater 100 W, 230 V → 100 ÷ 230 =
0.43 A –
PHG02 contact rated 10 (5) A – a large margin. Dehumidifier 2 kW, 230 V →
8.7 A. A compressor is an inductive load, for which PHG02 allows only 5 A; moreover, at start-up it briefly draws several times higher current. Direct connection is not allowed: connect via a
contactor or interposing relaywhose coil is controlled by the hygrostat (the coil voltage must match the circuit). Marking "10 (5) A": 10 A – for resistive load (heater), 5 A in brackets – for inductive load (motors, compressors).
Where to install: room, duct, outdoor, panel
|
Sensor |
Good location |
Where not to install |
|
Room, flush-mounted |
Interior wall, ~1.5 m high, free air circulation; in a bathroom – not directly above the shower where water splashes |
Near a radiator, supply air diffuser, door, on a cold external wall, in sunlight; in a zone where water reaches the sensor directly |
|
Duct |
For room humidity – in the extract air duct, in a straight section, probe in the middle of the duct |
In the supply duct downstream of the heater (shows too low humidity), immediately after a bend or humidifier, where the air is not mixed |
|
Outdoor |
North wall, no lower than ~2 m, protected from sun and rain, cable entry from below |
Above windows, ventilation openings, heat pump outdoor unit; in direct sunlight |
|
With wall surface sensor |
On the wall whose condensation risk you want to monitor (e.g. external wall, corner) |
On a heated or sun-warmed wall – the reading will not reflect the problem |
|
Hygrostat in a panel |
In the upper part of the panel, as far from the heater as possible and not directly above it; heater at the bottom, so warm air rises through the whole panel |
Directly above the heater or near ventilation grilles – it will switch off too early |
⚠ What to check before buying
Kibirkštis: "I ordered the same sensor as my colleague, but my controller doesn't see it – they say it's the wrong version…"
|
What to check |
Why |
|
Who will make the decision |
Controller available – you need a transmitter. None – a sensor-controller or hygrostat. Monitoring only – a wireless sensor |
|
Power supply |
24 V AC or DC only, PoM via RJ45, 85–264 V AC, 230 V, 12 / 24 V DC or battery. Versions of the same series differ – check the product name |
|
Controller input |
0–10 V, 0–20 / 4–20 mA or Modbus RTU; for Modbus – address, baud rate and parity must match |
|
Range and environment |
Room sensors usually 0…+50 °C and 0–95 % RH, duct and outdoor −30…+70 °C and 0–100 % RH. Is the environment condensing |
|
Mounting type and IP |
Room IP30, flush-mounted, duct IP54 (for probe IP see the product description), outdoor IP65, panel – DIN rail IP20 |
|
Relay contact |
Current for resistive and inductive load, NO / NC / changeover; does it switch on with rising humidity (dehumidification) or falling (humidification) |
|
Industrial environment |
Dust, oil mist, chemical vapours and solvents can damage the humidity element – choose a duct or outdoor housing with protection and plan periodic checks and calibration |
|
For wireless |
Do you have a Zigbee hub, Wi-Fi coverage or a LoRa network; which app, and do you need history and alerts |
✗ Most common mistakes
|
Mistake |
Consequence |
|
Humidity sensor in the supply duct downstream of the heater |
Shows 15–25 % RH even though the room is humid – the fan or dehumidifier never switches on |
|
Wrong power supply version bought (e.g. AC transformer, but the sensor is DC only) |
The sensor does not work or is damaged; the product or power supply has to be replaced |
|
The controller expects 0–10 V, but the sensor output is set to 0–20 mA (or vice versa) |
A current output on a high-impedance voltage input drives the voltage to its limit – the controller almost always sees the maximum; the other way round – it reads too low. Check the output setting before commissioning |
|
PoM sensor with RJ45 plugged into a computer network switch |
Devices do not work, possible damage to the switch or sensor |
|
Hygrostat switches a dehumidifier or fan directly, exceeding the contact current |
Contacts overheat and weld, the device fails or does not switch off |
|
Sensor cleaned with solvents, painted, covered with film during renovation |
The humidity element is damaged or "drifts" – readings no longer match reality |
|
Outdoor sensor in the sun or above a ventilation opening |
Temperature distorted by several degrees, humidity by tens of percent |
|
⚡ 230 V hygrostat or controller in a damp room without a suitable enclosure and residual current protection |
Risk of electric shock and short circuit |
⚡ Safe installation – Fazė's tip
Before connecting sensors, hygrostats or controllers, disconnect the power and verify the absence of voltage – in panels 24 V and 230 V are often on adjacent terminals. Supply 24 V sensors only from a safety isolating transformer or power supply, and route signal cables separately from 230/400 V. In bathrooms, shower rooms and pool areas, install equipment according to HD 60364-7-701 zones and IP rating (in zones 1 and 2 – at least IPX4; in zones 0 and 1 – SELV only, with the power source outside the zones), and protect all circuits of the room with a residual current device with IΔn ≤ 30 mA. 230 V devices must be connected by a qualified electrician.
☝ Elsprendimai.eu recommends
-
For a panel hygrostat – panel heater: together they prevent condensation on automation equipment and terminals.
-
For active sensors – 24 V DC DIN rail power supply: suitable for F, G and H versions; M (PoM) versions are powered via a Sentera PoM device or power module, version 8 – directly from 230 V.
-
Already have a sensor-controller – all that's left is a fan with 0–10 V control or a speed controller.
-
Humidity does not drop even with ventilation? Choose an air dehumidifier and control it with a hygrostat.
-
Controller accepts a different signal than the sensor? Choose a signal converter, not a different sensor.
-
Need air quality as well as humidity? See CO₂ sensors – many of them also measure temperature and humidity.
Diagram: humidity-controlled bathroom or pool ventilation – wrong and right
Kibirkštis: "I installed a humidity sensor and a fan, but after a shower the mirror is fogged up and the fan barely turns. The sensor shows 22 %."
Fazė: "The sensor is fine – it is measuring the wrong air. Let's look at the whole circuit."
✗ WRONG
① Duct sensor in the supply duct downstream of the heater
↓
② Sensor output range does not match the controller settings
↓
③ Humidity threshold set to 40 % RH
↓
④ 230 V fan switched via a controller relay contact with too low a current rating; no residual current protection in the circuit
✓ RIGHT
① Sensor in the extract air duct or in the room on an interior wall, not above the shower
↓
② Output type and range match the controller input and settings (0–10 V = 0–100 % RH on both sides)
↓
③ Threshold above the normal level (e.g. 65–70 % RH), minimum speed – for continuous ventilation
↓
④ EC fan controlled by a 0–10 V signal; high load – via a contactor; RCD IΔn ≤ 30 mA in the circuit
Why – explanation by diagram numbers
-
①: downstream of the heater the air is warmed, so its relative humidity is low (outdoor air at 0 °C and 80 % RH, heated to +20 °C, has about 21 % RH), even though humidity in the bathroom may reach 90 %. The sensor must measure the air leaving the room – in the extract duct or in the room itself. Above the shower, water splashes and the vapour stream distort readings and shorten the sensor's service life.
-
②: the controller converts the signal into percent according to its own settings. If 0–10 V on the sensor corresponds to 0–100 % RH but a different range (or a different signal type) is entered in the controller, the same humidity looks different to the controller and the fan speeds up at the wrong time. In addition, a 0–20 mA current output connected to a high-impedance 0–10 V input drives the voltage to its limit – the controller would almost always see the maximum. Match the output type and range before commissioning.
-
③: if the threshold is below the normal room humidity, the fan runs at maximum all the time – noise and heat losses, and after a shower there is no "reserve" left to speed up. Set the threshold above the normal level and fine-tune it to the season; keep the minimum speed for continuous ventilation.
-
④: the EC fan is smoothly controlled by a 0–10 V signal directly from the sensor-controller. If you do switch a 230 V load with a relay contact, its permissible inductive current must be higher than the fan's, and larger loads should be switched via a contactor. The damp room circuit must have residual current protection with IΔn ≤ 30 mA.
⚠ The diagram is for guidance only. Check the wiring of the sensor, controller, fan and power supply against the manufacturer's instructions and the design. Installation is carried out by, and is the responsibility of, a qualified electrician. UAB "Elektrotechnikos sprendimai" is not responsible for the connection or possible errors.
FAQ
Kibirkštis: What is the difference between a transmitter and a sensor-controller if both have a 0–10 V output?
Fazė: A transmitter's 0–10 V simply reflects the measured temperature or humidity – the decision is made by the controller. A sensor-controller's 0–10 V is an already calculated control signal based on the limits you set, so it can be connected directly to an EC fan or damper actuator.
Kibirkštis: Why does a humidity sensor in the duct downstream of the heater show barely 20 %?
Fazė: When air is heated, the amount of water vapour stays the same, but warm air can hold more of it – so relative humidity drops. To control room humidity, install the sensor in the room or in the extract air duct.
Kibirkštis: What humidity threshold should I set for a bathroom fan?
Fazė: Slightly above the normal humidity of that room, often 65–70 % RH. Too low a threshold – the fan runs around the clock; too high – the mirror stays fogged for a long time. In summer and autumn normal room humidity is higher than in winter, so it is worth adjusting the threshold to the season.
Kibirkštis: Can I connect a PoM sensor with RJ45 to a computer network?
Fazė: No. RJ45 is used here only as a connector – the cable carries Modbus RTU (RS485) and 24 V DC power. It is connected to Sentera PoM devices or a Modbus network according to the manufacturer's diagram.
Kibirkštis: When does a panel need a hygrostat, and when is a thermostat enough?
Fazė: A thermostat switches on the heater only in cold conditions, but condensation also forms in autumn or spring, when humid air cools below the dew point at night. A hygrostat responds specifically to humidity. Outdoor cabinets often use both: a thermostat against frost, a hygrostat against condensation.
Kibirkštis: Can a wireless Zigbee sensor control a fan?
Fazė: Yes, via a smart home hub and a smart switch or relay – by creating a scenario "humidity above threshold → switch on". However, such control depends on the connection and batteries, so for continuous or critical ventilation a wired sensor-controller is more reliable.
Sources: technical data from elsprendimai.eu product pages (Sentera Controls, SONOFF, IMOU, Plastim, Taxnele, etc.); Sentera Controls documentation (Power over Modbus, T+RH sensor series); Magnus formula for dew point (coefficients 17.62 / 243.12 °C – WMO CIMO guide, Sonntag 1990); EN ISO 13788 (surface humidity and condensation assessment); EN 16798-1 (indoor environment); HD 60364-7-701 (electrical installations in bathrooms and shower rooms). Checked 2026-10-18.
Tell us what you want to control – we will select the sensor and accessories
Specify the room (bathroom, pool, warehouse, panel), the controller or fan and the supply voltage. We will offer a compatible sensor, power supply and control equipment – with prices.
Get a quote →