  • Designed for fixed installations, with wires laid in surface-mounted or attached insulating tubes or similar sealed systems. The wires are intended for the installation of electrical schemes for the control and management of various devices and equipment. The conductor is made of annealed copper wires, flexible and soft. The copper core is covered with PVC insulation.  

  • Electrical selection guide · heat-resistant flexible copper wires

    H05V2-K and H07V2-K: how to choose a wire for a distribution board, control circuit or fixed installation?

    From the class 5 copper conductor and 90 °C PVC insulation to voltage classes, cross-sections, permissible current, suitable terminals and installation conditions.

    300/500 V
    H05V2-K
    450/750 V
    H07V2-K
    +90 °C
    Maximum conductor temperature
    Class 5
    Flexible copper
    V2 PVC
    More heat-resistant insulation
    Kibirkštis Fazė Kibirkštis asks, Fazė answers – technology without unnecessary myths.
    Key point: H05V2-K and H07V2-K are flexible, single-core insulated wires intended for protected fixed electrical installation and internal wiring of electrical equipment. V2 denotes PVC insulation with increased heat resistance, K – a flexible stranded conductor. These are not multi-core cables with an additional outer sheath. Safe use requires a suitable trunking or enclosure, terminals and protective devices.

    Quick selection by electrical circuit

    Before choosing H05V2-K or H07V2-K, you must determine the circuit voltage, conductor cross-section, operating temperature, mechanical environment, required colour and connection type. A higher temperature class alone does not mean that the wire is suitable for every installation method.

    Need Selection direction Check
    Internal wiring of a control cabinet H05V2-K or H07V2-K according to voltage Terminals, control current, temperature, colours
    Power connections in a distribution board H07V2-K according to the design 450/750 V, permissible current, thermal conditions
    Machine control circuit V2-K for protected internal connections Vibration, movement, equipment standards
    Wires in an insulating conduit According to circuit voltage and installation Conduit fill, cooling, installation conditions
    Higher ambient temperature V2 insulation, if the limits are not exceeded Conductor and terminal temperature, temperature correction
    Open air, UV, soil or water A cable specifically designed for the environment The insulation of single-core V2-K is not sufficient

    H05V2-K and H07V2-K – the main differences

    These wires belong to a similar construction group, but they differ in rated voltage class, and depending on the specific cross-section the insulation thickness and outer dimensions may also differ. The higher voltage class of H07V2-K does not in itself mean a higher permissible current.

    Property H05V2-K H07V2-K
    U₀/U 300/500 V 450/750 V
    Conductor Cu, flexible, class 5 Cu, flexible, class 5
    Insulation V2 PVC, 90 °C V2 PVC, 90 °C
    Number of cores 1 1
    Additional sheath None None
    Purpose Protected internal connections and fixed circuits Protected panel, control and power connections
    Most common mistake The voltage class is not checked Higher voltage is confused with higher current

    Conductor construction and marking explained

    From the outside, H05V2-K and H07V2-K look like individual insulated wires. Inside are many thin annealed copper strands that form a single electrical conductor. It is therefore important to distinguish between the terms single-core wire and stranded conductor: one core can consist of many copper strands.

    H

    Harmonised designation of the wire type according to the relevant standards.

    05 or 07

    Indicates the voltage class: 300/500 V or 450/750 V respectively.

    V2

    Special PVC insulation designed for a higher operating temperature.

    K

    Flexible stranded copper conductor, usually class 5.

    How does the wire carry electricity? The annealed copper strands together form one cross-section, for example 1.5 mm² or 2.5 mm². Current flows through the conductor, and the surrounding PVC insulation electrically separates it from other wires and equipment. The flexibility of the conductor helps in forming connections, but its electrical suitability is determined by the cross-section, temperature, current-carrying capacity and protection.

    What does the +90 °C temperature class mean in practice?

    PVC insulation with increased heat resistance allows the conductor to reach a higher specified operating temperature than standard +70 °C class PVC wires. However, this is not permission to use the wire in any hot environment.

    Parameter Value What does it mean?
    +90 °C Maximum continuous conductor temperature Must not be exceeded in normal operation.
    +160 °C Short-term short-circuit limit for the H07V2-K technical version Not an indicator of continuous operating temperature.
    −5…+40 °C Installation temperature of the H07V2-K version Install and bend only under permissible conditions.
    −30…+90 °C Operating range of the H07V2-K version At low temperature this does not mean the wire may be actively bent.
    The limiting element may be the terminal. If the wire insulation allows +90 °C but the temperature class of the terminal or equipment connection used is lower, the entire circuit cannot be designed as if all components allowed +90 °C. The terminal requirements must be checked and the permissible current determined accordingly.

    Where are these wires suitable and where must they not be used?

    ✓ Distribution boards
    For internal power and control connections according to the design.
    ✓ Automation cabinets
    For relays, controllers, terminal blocks and other suitable circuits.
    ✓ Insulating conduits
    For protected fixed installation.
    ✓ Closed trunking
    Provided that appropriate insulation and mechanical protection are ensured.
    ⚠ Warmer working environment
    The temperature limits of the conductor, environment and connection must be assessed.
    ⚠ Production equipment
    Check the conditions of oil, vibration, movement and mechanical stress.
    ✗ Directly in the ground
    A single-core insulated wire without an additional sheath is not designed for this.
    ✗ Continuous dynamic flexing
    A class 5 conductor is not in itself a wire designed for cable chains.

    Application in distribution boards and automation systems

    Control cabinets require clear separation of circuits, reliable connections and neat wire routing. Flexible H05V2-K and H07V2-K conductors allow wiring from terminal blocks to relays, contactors, circuit breakers and other suitable components.

    Circuit Key parameters Typical mistake
    Control signals Operating voltage, cross-section, identification The wire is chosen by colour alone.
    Contactor coil Coil voltage, protection, connection type The terminal cross-section limit is not checked.
    Power connections Permissible current, heat, protection 90 °C insulation is taken as permission to increase the load.
    PE connections Green-yellow colour, continuity, cross-section An unsuitable colour is used for the PE function.
    Long control wires Voltage drop, signal interference Signal sensitivity to interference is not assessed.

    Wire colours: identification of L, N, PE and control circuits

    Different insulation colours make safe wire identification easier, but colour does not replace measurement, the circuit diagram or core marking. In standard AC networks, the following marking principles are important.

    Colour Most common function Note
    Brown Line conductor L According to the diagram and marking
    Black Line conductor or control conductor specified in the diagram Not for PE
    Grey Line conductor According to purpose
    Blue Neutral conductor N Apply the relevant identification rules
    Green-yellow Protective conductor PE Reserved for the protective function
    ⚡ PE must not be used for a phase or a control signal. The colours and numbering of wires inside panels must comply with the requirements of the design and the applicable equipment standards. Circuit identification is carried out not only visually but also by checking the marking and by measurement.

    How to correctly connect a class 5 flexible copper conductor?

    One of the most important advantages of these wires is the flexible stranded construction. However, when connecting, the terminal mechanism and its documented compatibility must be taken into account.

    Screw terminals

    Check whether the terminal accepts a flexible conductor without a ferrule or requires a correctly crimped ferrule. Observe the tightening torque.

    Spring terminals

    In some terminals a flexible conductor can be connected directly. Check the permitted conductor classes and the use of ferrules.

    Crimp ferrules

    Use only a ferrule of the correct size and design and a certified crimping tool. Improper crimping can cause the contact to overheat.

    Common mistake

    Loose strands, insulation stripped too short or too long, an unsuitable ferrule and a poorly tightened contact.

    Practical rule: a ferrule is not mandatory for every flexible conductor. What is essential is a correct connection method permitted for the terminal. Do not tin or solder conductor ends unless the connection device instructions permit it.

    How do cross-section, power and temperature determine the load?

    The rated voltage of a conductor is not an indicator of its permissible current. The choice of cross-section is determined by current-carrying capacity, ambient temperature, installation method, wire grouping, the temperature class of the connection and the protective device. The load currents below are for guidance only and do not confirm the selection of a specific cable.

    Single-phase load Current at 230 V Practical note
    100 W 0.43 A Control or auxiliary load
    500 W 2.17 A Check circuit protection
    1000 W 4.35 A Assess the thermal regime
    2000 W 8.70 A Select the cross-section according to the current
    3000 W 13.04 A Assess grouping and terminals
    3680 W 16.00 A The entire circuit and protection are checked
    Single-phase load formula:
    I = P / (U × cos φ)
    Example: 2300 W / 230 V = 10 A at cos φ = 1. For motors, efficiency and starting mode are also taken into account.

    Resistance of flexible copper conductors according to EN 60228

    Below are the maximum DC resistance values of class 5 plain copper conductors at +20 °C. They help to compare cross-sections and calculate voltage drop.

    Cross-section Resistance at 20 °C
    0.5 mm² 39.0 Ω/km
    0.75 mm² 26.0 Ω/km
    1.0 mm² 19.5 Ω/km
    1.5 mm² 13.3 Ω/km
    2.5 mm² 7.98 Ω/km
    4 mm² 4.95 Ω/km
    6 mm² 3.30 Ω/km
    10 mm² 1.91 Ω/km

    The table is intended for technical comparison. It does not confirm that all listed cross-sections are available in this shop category or in stock.

    Voltage drop: how to calculate a longer wire run?

    As a wire gets longer, its electrical resistance increases. In a single-phase circuit, the combined path of the line and neutral conductors is calculated. This is relevant for long control circuits, panel connections and loads located far from the distribution board.

    Simplified example: 10 A current, resistive load, +20 °C conductor temperature.

    Length one way 1.5 mm² 2.5 mm² 4 mm² 6 mm²
    10 m 2.66 V 1.60 V 0.99 V 0.66 V
    20 m 5.32 V 3.19 V 1.98 V 1.32 V
    30 m 7.98 V 4.79 V 2.97 V 1.98 V
    50 m 13.30 V 7.98 V 4.95 V 3.30 V
    Formula:
    ΔU ≈ 2 × L × I × R / 1000
    L – distance one way in metres, I – current in amperes, R – resistance of one conductor in Ω/km.
    Under real conditions: as the conductor temperature rises, its electrical resistance increases. When calculating the 90 °C mode, the 20 °C resistance cannot be used directly as the final value. The resistance of connections, the nature of the load and other circuit elements must also be taken into account.

    Detailed table of technical parameters

    Parameter H05V2-K H07V2-K
    Conductor Flexible annealed copper Flexible annealed copper
    Conductor class Class 5 Class 5
    Number of cores 1 1
    Rated voltage U₀/U 300/500 V 450/750 V
    Insulation material Type V2 PVC Type V2 PVC / TI3
    Maximum conductor temperature +90 °C +90 °C
    Outer sheath None None
    Temperature during short circuit Check the specific version Up to +160 °C in the corresponding version
    Test voltage According to the specific product 2.5 kV in the corresponding version
    Installation temperature According to the specific product −5…+40 °C in the corresponding version
    Operating temperature According to the specific product −30…+90 °C in the corresponding version
    CPR class According to the specific DoP Eca in the corresponding version
    Halogen-free construction No – PVC insulation No – PVC insulation
    Purpose Protected internal and fixed connections Protected internal and fixed connections

    Moisture, UV, outdoors and IP protection

    Single-core PVC-insulated wires must be installed so that their protection matches the environmental hazards. The presence of insulation does not mean that the wire has a separately declared IP65 or IP67 rating.

    Installation environment Assessment Important
    Inside a distribution board Intended use Enclosure protection and proper wire fixing
    Insulating conduit indoors According to the design Conduit fill and mechanical protection
    Damp indoor location Only with a suitable installation system Connections, entries, enclosures and protection
    Hot equipment Assess temperature limits The +90 °C limit of the wire is not unlimited heat resistance
    Direct UV exposure Not suitable without separate confirmation A UV-resistant system is required
    Direct contact with soil or water Not intended Use a cable specifically designed for the environment

    H05V2-K / H07V2-K, H05V-K, H07V-K and other wires

    Wires of the same colour and cross-section may have a different voltage class, conductor construction and insulation heat resistance.

    Group Main difference Link
    H05V2-K / H07V2-K Single-core flexible copper wires with 90 °C PVC insulation This group →
    H07V-K Single-core flexible copper wires with standard PVC insulation, 450/750 V H07V-K →
    H05V-U / H07V-U / V2-U Single-core wires with a solid copper conductor; V2 versions are more heat-resistant Solid-conductor wires →
    H03VV-F / H05VV-F Multi-core flexible cables with a common outer PVC sheath Flexible cables →
    H07Z1-K Halogen-free flexible copper wire; different insulation construction Copper cable catalogue →

    Installation: eight practical steps

    1. Define the circuit
    Voltage, purpose, current and type of protection.
    2. Choose H05 or H07
    According to rated voltage and suitable construction.
    3. Calculate the cross-section
    According to current, installation method and voltage drop.
    4. Check the colour
    Marking of L, N, PE and control circuits.
    5. Choose the terminal
    Compatibility with a class 5 stranded copper conductor.
    6. Protect the wire
    Enclosure, trunking or insulating conduit according to the environment.
    7. Observe temperature limits
    Do not exceed the permissible mode of the conductor and connection devices.
    8. Check the installation
    Insulation condition, PE continuity and operation of protection.

    What to check before buying wires?

    Rated voltage
    300/500 V or 450/750 V?
    Cross-section
    Is the continuous current-carrying capacity sufficient?
    Colour
    Does it match the L, N, PE and diagram marking?
    Terminal class
    Does it accept a class 5 stranded conductor?
    Temperature
    Do the insulation, terminals and environment allow it?
    Length to order
    Have all wire runs and reserves been taken into account?
    CPR
    Does it meet the requirements of the specific building?
    Mechanical protection
    Will the wires be in an enclosure, trunking or conduit?

    Most common wire selection and installation mistakes

    ✗ Wrong ✓ Correct
    H05V2-K and H07V2-K are considered identical. Assess the 300/500 V and 450/750 V classes separately.
    90 °C insulation is taken as a 90 °C terminal guarantee. Check the temperature class of the connection equipment.
    An unsheathed single-core wire is routed through an unprotected area. Use a suitable trunking, conduit or enclosure.
    A flexible conductor is connected to an incompatible terminal. Choose a permitted terminal and a ferrule where required.
    The PE conductor colour is used for a phase. The green-yellow insulated core is reserved for PE.
    The circuit breaker rating is determined from the cross-section alone. Permissible current, cooling and disconnection conditions are checked.
    The wire is considered suitable for continuous vibration and movement. A construction tested accordingly is chosen for movement.
    PVC insulation is called halogen-free. If LSOH is required, choose a wire designed for it.

    Fazė’s recommendations for electricians and panel builders

    Fazė
    Fazė advises

    In panel wiring, the most common practical mistake is to choose a wire by colour and cross-section without assessing the terminal. Before installation, check whether it accepts a class 5 conductor, how much insulation must be stripped and whether a crimp ferrule is permitted. Then assess the wire temperature, grouping, protection and the thermal regime of the whole cabinet.

    Need 90 °C insulation?

    Choose H05V2-K or H07V2-K according to voltage and purpose.

    Need a standard flexible wire?

    H07V-K group →

    Need a solid conductor?

    H05V-U / H07V-U / V2-U →

    Need a sheathed cable?

    H03VV-F / H05VV-F →

    Diagram: wrong and correct wire connection

    ✗ WRONG
    Flexible class 5 wire
    ↓
    Improperly prepared strands
    Unclear terminal compatibility
    ↓
    The contact may overheat

    Improper clamping, excessive insulation stripping or mechanical pull increase the risk of failure.

    ✓ RIGHT
    H05V2-K or H07V2-K
    ↓
    Compatible terminal
    Proper preparation and a ferrule if required
    ↓
    Verified electrical contact

    Suitable connection device, protection, cross-section and insulation temperature class.

    FAQ – Kibirkštis asks, Fazė answers

    15 practical questions about H05V2-K and H07V2-K copper wires: their differences, V2 insulation, temperature, panel wiring, terminals, load and electrical safety.

    Kibirkštis
    KIBIRKŠTIS ASKS · 01

    What is the difference between H05V2-K and H07V2-K wires?

    Fazė
    FAZĖ ANSWERS

    The main difference is the rated voltage. H05V2-K is rated 300/500 V, while H07V2-K is rated 450/750 V . Both are single-core, flexible class 5 copper wires with V2-type PVC insulation, whose maximum continuous conductor operating temperature is +90 °C. A higher rated voltage does not by itself mean a higher permissible load current.

    Kibirkštis
    KIBIRKŠTIS ASKS · 02

    What does V2 mean and how do these wires differ from ordinary H05V-K or H07V-K?

    Fazė
    FAZĖ ANSWERS

    V2 stands for PVC insulation with increased heat resistance. Ordinary H05V-K and H07V-K wires have a maximum continuous conductor temperature of +70 °C, while H05V2-K and H07V2-K have +90 °C. This property is useful for internal wiring of higher-temperature electrical equipment. However, even a V2-insulated wire must be protected from improper mechanical and environmental effects.

    Kibirkštis
    KIBIRKŠTIS ASKS · 03

    Does +90 °C insulation mean I can use a higher-rated MCB?

    Fazė
    FAZĖ ANSWERS

    Not automatically. The +90 °C insulation of the wire allows a higher conductor temperature, but the operating regime of the whole connection may be limited by the terminals, connected equipment and cooling conditions. In closed trunking or a panel with many loaded wires, heat dissipates less effectively. Therefore, the protective device is selected according to the actual continuous current-carrying capacity, conductor cross-section, installation method and disconnection requirements.

    Kibirkštis
    KIBIRKŠTIS ASKS · 04

    Can I use H07V2-K inside a distribution board?

    Fazė
    FAZĖ ANSWERS

    Yes. H07V2-K is suitable for internal wiring of properly designed electrical panels and control cabinets. Its flexible conductor is convenient for routing wires between MCBs, contactors, relays and terminal blocks. During installation, check the 450/750 V voltage rating, cross-section, suitable terminals, protection against mechanical damage and the thermal regime of the distribution board.

    Kibirkštis
    KIBIRKŠTIS ASKS · 05

    Does a class 5 wire mean it contains five cores?

    Fazė
    FAZĖ ANSWERS

    No. Class 5 refers to the conductor flexibility class, not the number of cores. H05V2-K and H07V2-K are single-core insulated wires. One conductor consists of many fine annealed copper strands that together form the nominal cross-section. For example, a 2.5 mm² class 5 wire has one flexible conductor, not five separate insulated cores.

    Kibirkštis
    KIBIRKŠTIS ASKS · 06

    Are crimp ferrules mandatory for H05V2-K and H07V2-K wires?

    Fazė
    FAZĖ ANSWERS

    Not in all cases. The need for a ferrule is determined by the specific terminal design and its connection requirements. Some spring terminals can accept a flexible class 5 conductor without a ferrule. Others may require a properly crimped ferrule. It is important to use a ferrule of the right size, a suitable crimping tool and to observe the insulation stripping length. Loose copper strands must not be left, and the wire must not be connected to a contact not intended for it.

    Kibirkštis
    KIBIRKŠTIS ASKS · 07

    Can these wires be laid in electrical installation conduits?

    Fazė
    FAZĖ ANSWERS

    Yes, protected fixed installation in suitable insulating conduits or closed wiring systems is one of the intended uses of these wires. Conduit fill, the number of wires, mechanical protection and cooling must be taken into account. Several loaded wires in one conduit may heat up more, so grouping correction factors may be needed when calculating the permissible current.

    Kibirkštis
    KIBIRKŠTIS ASKS · 08

    Can I run an H07V2-K wire openly on a wall?

    Fazė
    FAZĖ ANSWERS

    These wires are not universal cables intended for open installation. They have a single insulated conductor and no additional outer sheath. Therefore, in exposed locations the risk of contact and mechanical damage must be assessed. Normally a protected wiring system – conduit, trunking or a suitable electrical equipment enclosureis used. The final installation must meet the requirements of the specific installation.

    Kibirkštis
    KIBIRKŠTIS ASKS · 09

    Can H05V2-K and H07V2-K be used outdoors?

    Fazė
    FAZĖ ANSWERS

    The wire type alone cannot confirm suitability for permanent outdoor use. V2 insulation means resistance to higher temperatures, but not to UV radiation or water. If the installation is planned outdoors, the conditions of use of the specific wire and the suitability of the entire protective system must be checked. These single-core insulated wires are not intended for direct laying in the ground or in water.

    Kibirkštis
    KIBIRKŠTIS ASKS · 10

    Can these wires be used in constantly moving machines if they are flexible?

    Fazė
    FAZĖ ANSWERS

    A flexible class 5 conductor makes installation and connection easier, but this does not mean it is designed for continuous bending cycles. Moving drag chains, robots or intensively vibrating equipment require wires or cables specifically intended for such conditions. Installation flexibility and resistance to dynamic flexing are different properties.

    Kibirkštis
    KIBIRKŠTIS ASKS · 11

    Is a 1.5 mm² H07V2-K wire suitable for a 16 A circuit?

    Fazė
    FAZĖ ANSWERS

    It cannot be answered from the cross-section alone. Check whether the wire is installed in a panel, conduit or trunking, how many conductors are loaded together, what the ambient temperature is and which terminals are used. The parameters of the protective device and the disconnection conditions of the circuit also matter. +90 °C insulation does not by itself confirm suitability for a 16 A load.

    Kibirkštis
    KIBIRKŠTIS ASKS · 12

    How to calculate the voltage drop in a 30 m control circuit?

    Fazė
    FAZĖ ANSWERS

    You need to know the circuit voltage, current, conductor cross-section and distance. For example, in a 24 V DC circuit with a current of 2 A and a one-way distance of 30 m, using two 0.75 mm² class 5 copper conductors with a resistance of 26 Ω/km at +20 °C, the voltage drop would be about 3.12 V – 13 % of 24 V. Such a drop may be too high for many control systems. The voltage tolerance of the device must be checked and a suitable cross-section chosen.

    Kibirkštis
    KIBIRKŠTIS ASKS · 13

    Can I use a wire with green-yellow insulation as a phase conductor?

    Fazė
    FAZĖ ANSWERS

    No. Green-yellow insulation colour is reserved for protective conductors. It must not be arbitrarily used for a phase or an ordinary control signal. Blue is normally used for the neutral conductor, while phase and control conductors are marked according to the applicable electrical equipment standards and the design diagram. Before connecting, the purpose and marking of the conductor must be checked.

    Kibirkštis
    KIBIRKŠTIS ASKS · 14

    Are H05V2-K and H07V2-K halogen-free or fire-resistant wires?

    Fazė
    FAZĖ ANSWERS

    No, these wires have PVC insulation, so they cannot be considered halogen-free. It is also necessary to distinguish flame-propagation limitation, CPR reaction-to-fire classification and circuit integrity during a fire. A +90 °C operating temperature does not mean the wire can work during a fire. If low smoke or a specific fire class is required, choose a wire intended for this and check its technical documents.

    Kibirkštis
    KIBIRKŠTIS ASKS · 15

    What should I state in an enquiry so you can select the right wire?

    Fazė
    FAZĖ ANSWERS

    State the required wire type H05V2-K or H07V2-K, rated voltage, copper conductor cross-section, insulation colour, required quantity in metres and intended use. For panel assembly, it helps to specify the terminal type, load current and operating temperature. This information allows suitability, possible variants and supply conditions to be assessed more accurately.

    Kibirkštis Fazė Kibirkštis and Fazė remind you

    When choosing H05V2-K or H07V2-K, check not only the voltage and temperature class but also the conductor cross-section, terminal compatibility, installation method, environmental conditions and circuit protection.

    Disclaimer: the technical tables, formulas and calculation examples are provided for information purposes. The final wire type, cross-section, protective device parameters, terminal connections and installation method must be determined by a qualified electrical specialist according to the design and applicable requirements. The liability of UAB “Elektrotechnikos sprendimai” is determined in accordance with applicable law.

    Need H05V2-K or H07V2-K wires for a panel or equipment?

    State the required voltage rating, copper conductor cross-section, insulation colour, length and operating conditions. We will help assess the right wire type, possible variants and supply conditions.

    Contact Elsprendimai.eu

    Copper Wires H05V2-K and H07V2-K are high-quality electrical wires designed for indoor and outdoor electrical installations. These wires feature excellent flexibility, reliability, and durability, making them an ideal choice for both industrial and household use.

    Construction:

    Conductors:

    The wires are made from flexible copper, ensuring good electrical conductivity and low energy losses.
    The conductors are often multi-stranded, allowing for easier installation and adaptability in various situations.
    Insulation:

    The wires have PVC (polyvinyl chloride) insulation, which protects against moisture, chemicals, and mechanical damage.
    The insulation ensures good longevity and safety when using them in complex environments.
    Specifications:

    Types:

    H05V2-K: Wires designed for use at voltages up to 300/500 V. These wires are commonly used in light industrial and household environments.
    H07V2-K: Wires designed for use at voltages up to 450/750 V. They are often used in heavy industrial sectors and other demanding environments where higher insulation and resistance are required.
    Temperature Range:

    The temperature range of the wires typically varies from -15 °C to +70 °C, but this may depend on the specific insulation material.
    Color Code:

    A color code is used that complies with standards: usually brown (phase), blue (neutral), green-yellow (earthing).
    Applications:

    Industry:

    H05V2-K and H07V2-K wires are ideal for use in industrial machinery, automation systems, lighting systems, and other electrical installations where reliable conductivity is required.
    Household Needs:

    Suitable for various household applications, such as lighting systems, electrical appliances, including refrigerators and other domestic devices.
    Construction:

    Used in electrical installations of new and renovated buildings, both indoors and outdoors, ensuring safety and reliability.
    Advantages:

    High Electrical Conductivity: Due to the quality copper conductor, the wires ensure efficient transmission of electrical energy.
    Flexibility: Their design makes the wires easy to install, allowing them to adapt to complex locations.
    Resistance: The PVC insulation ensures that the wires are resistant to moisture, chemicals, and mechanical damage, ensuring long service life.