Lighting guide: how to choose the luminaire, power, colour and IP rating
Here you will find quick selection by situation, the parameters worth comparing, illuminance standards (lx), calculating the number of luminaires, an IP / IK table, replacing lamps with LED, the most common mistakes and answers to practical questions. Specific data – in each product description.
Colour meanings: ■ information · ■ benefit, solution · ■ ⚠ check · ■ ⚡ safety, mistakes
What do you need? Quick selection
|
Situation |
Solution |
Where to look |
|
Warehouse, workshop, hangar – ceiling 6–12 m |
UFO-type LED high-bay luminaires 100–240 W, ≥140 lm/W, IP65; above 8 m – a narrower 60–90° beam |
UFO luminaires |
|
Warehouse aisles between racks |
Linear suspended luminaires along the aisle – light falls on the shelves, not on top of the racks |
Suspended industrial |
|
Office, classroom, meeting room |
LED panels 600×600 or linear luminaires, 4000K, UGR ≤ 19, 500 lx at the workstation |
LED panels, office luminaires |
|
Shop, shop window, gallery |
Adjustable track luminaires, CRI ≥ 90 – product colours look natural |
Track luminaires |
|
Garage, basement, boiler room, car wash |
Weatherproof IP65 luminaires, 4000K; for unheated rooms – operating temperature from −20 °C |
Weatherproof luminaires, for basements |
|
Staircase, corridor, common areas |
Luminaires with a radar or motion sensor – the light is on only when people are present |
For corridors, radar luminaires |
|
Home: living room, kitchen, bedroom |
Pendant and wall luminaires, LED bulbs 2700–3000K, CRI ≥ 90 |
Interior lighting, LED bulbs |
|
Furniture, stairs, niches, cornices |
LED strip + aluminium profile + 24 V power supply with headroom + switch or sensor |
LED strips and accessories |
|
House entrance, terrace, facade |
Wall-mounted or accent outdoor luminaires IP54–IP65, 2700–3000K |
Outdoor luminaires |
|
Paths, lawn, trees, garden steps |
In-ground recessed luminaires IP67, impact-resistant glass (IK08 and higher) |
In-ground luminaires |
|
Company yard, car park, loading area |
LED floodlights at 6–10 m height, aimed downwards; in remote areas – with a motion sensor |
LED floodlights, with sensor |
|
Street, driveway, park |
LED street luminaires on a pole with asymmetric optics |
Street and park luminaires |
|
Existing luminaires stay, only lamps are replaced |
LED equivalent by base and luminous flux (lm); HQL / NAV – E27 / E40 LED equivalents |
Lamps and accessories |
|
Escape routes, exits |
Emergency luminaires and exit signs, 1 h or 3 h autonomy, preferably with self-test |
Emergency lighting |
|
Existing lighting needs automatic control |
Motion / presence sensor on the ceiling or wall; for the yard – a photo relay |
Sensors, photo relays |
Good lighting means even light in the right place at the lowest cost per kWh
Replacing old HQL, NAV or fluorescent luminaires with LED usually cuts lighting costs by half or more, and with sensors by a further 20–50 %. But the savings only come when the luminaire is chosen for the room, not by the wattage on the box.
-
Warehouses and production: UFO or linear luminaires, ≥140 lm/W, with sensors in the aisles.
-
Offices: UGR ≤ 19 panels and daylight-dependent dimming.
-
Homes: warm 2700–3000K light, layered approach – general, task and accent lighting.
-
Outdoors: IP65 and higher, light aimed downwards, controlled by a photo relay or sensor.
Parameters for comparing luminaires
Watts show how much a luminaire consumes, not how much light it gives. Compare these parameters – you will find them in each product description or in the manufacturer's datasheet.
■ How much and how it shines
-
Luminous flux, lm – how much light the luminaire emits. The key figure for calculating quantity.
-
Efficacy, lm/W – how much light you get from 1 W. Industry ≥ 140 lm/W, offices ≥ 110 lm/W.
-
Beam angle, ° – the higher the mounting, the narrower the beam needed (see table below).
-
UGR – glare rating. Offices and classrooms ≤ 19, production ≤ 22–25.
■ What kind of light and how long it lasts
-
Colour temperature, K – 2700–3000K warm, 4000K neutral, 5000–6500K cool.
-
CRI (Ra) – colour rendering. Workplaces ≥ 80, retail and homes ≥ 90.
-
IP / IK – protection against dust and water / impact resistance.
-
Lifetime (L70 / L80) and operating temperature – important for cold warehouses, hot workshops and outdoors.
How many lux do you need? Illuminance standards
Lux (lx) is how much light falls on a surface: 1 lx = 1 lm / m². Requirements for workplaces are set in EN 12464-1 (indoor) and EN 12464-2 (outdoor). Below are indicative average illuminance values:
Car park, driveway (outdoor)
5–20 lx
Living room, bedroom (recommended)
150–300 lx
WC, plant rooms, boiler room
200 lx
Sales area, dispatch
300 lx
Kitchen worktop (recommended)
300–500 lx
Workshops, production
300–500 lx
Office, classroom, meetings
500 lx
Fine assembly, quality control
750 lx
Blue – values according to EN 12464-1 / -2, green – recommendations for homes (there is no standard for residential rooms). Scale 0–750 lx.
How many luminaires do you need? Quick calculation
For a preliminary estimate, the lumen method is used:
N = E × A ÷ (Φ × UF × MF)
N – number of luminaires · E – required illuminance, lx · A – area, m² · Φ – luminous flux of one luminaire, lm · UF – utilisation factor (0.5–0.7 indoors, 0.3–0.5 outdoors) · MF – maintenance factor (0.8 for a clean room, 0.7 for a dusty one)
|
Example |
Data |
Calculation |
Result |
|
Warehouse 30 × 20 m, ceiling 8 m |
E 200 lx, UFO 150 W / 22 500 lm, UF 0.65, MF 0.8 |
200 × 600 ÷ (22 500 × 0.65 × 0.8) = 10.3 |
12 pcs (4 × 3 grid), ~1.8 kW |
|
Office 6 × 5 m |
E 500 lx, panel 600×600 / 3600 lm, UF 0.7, MF 0.8 |
500 × 30 ÷ (3600 × 0.7 × 0.8) = 7.4 |
8 pcs (2 rows of 4) |
|
Garage 6 × 4 m |
E 200 lx, weatherproof IP65 / 4000 lm, UF 0.55, MF 0.75 |
200 × 24 ÷ (4000 × 0.55 × 0.75) = 2.9 |
3 pcs |
Round the quantity up so that the luminaires form an even grid. The spacing between luminaires should normally not exceed 1–1.5 times the mounting height. For projects we carry out an accurate DIALux calculation.
⚠ The calculation is preliminary and intended for indicative estimation only. The final number and layout of luminaires are determined by the lighting designer based on the data of the specific room.
|
Mounting height |
Luminaire type |
Typical power |
Beam angle |
|
2.5–4 m |
Panel, linear, weatherproof |
20–50 W |
100–120° |
|
4–6 m |
Linear suspended, UFO |
50–100 W |
90–120° |
|
6–8 m |
UFO, industrial suspended |
100–150 W |
90° |
|
8–12 m |
UFO |
150–200 W |
60–90° |
|
> 12 m |
UFO with narrow optics, floodlight |
200–300 W |
30–60° |
Colour temperature and colour rendering (CRI)
Colour temperature describes the tint of the light, not its quantity. The same illuminance looks brighter in cool light, but in a living space it becomes tiring in the evening.
2700K
Cosy warm: living room, bedroom, restaurant
3000K
Warm white: kitchen, hallway at home, facades
4000K
Neutral: office, warehouse, garage, retail
5000K
Daylight: production, workshops, quality control
6500K
Cool: technical rooms, outdoor areas, floodlights
CRI (Ra) shows how natural colours look. Ra 80 is sufficient for a warehouse and office; Ra 90 and higher for a shop, beauty salon, kitchen, art and painting work. Do not mix luminaires of different colour temperatures in one room – the difference is obvious even between 3000K and 4000K.
IP and IK: which protection and resistance where
IP code (IEC 60529): the first digit – protection against dust and solid particles, the second – against water. IK code (EN 62262) – resistance to impacts.
|
Rating |
Protection |
Where to use |
|
IP20 |
Protected against fingers and objects ≥ 12.5 mm; no protection against water |
Dry rooms: offices, living rooms |
|
IP44 |
Protected against objects ≥ 1 mm and water splashing from any direction |
Bathroom zone 2, eaves, canopies |
|
IP54 |
Dust-protected, protected against water splashing |
Facades under a canopy, workshops, warehouses |
|
IP65 |
Dust-tight, protected against water jets |
Outdoor luminaires, floodlights, garages, basements, workshops |
|
IP66 |
Dust-tight, protected against powerful water jets |
Car washes, food industry, open areas |
|
IP67 |
Protected against temporary immersion up to 1 m |
In-ground recessed luminaires |
|
IP68 |
Protected against continuous immersion (conditions specified by the manufacturer) |
Swimming pools, fountains, ponds |
|
IK08 / IK10 |
Withstands a 5 J / 20 J impact |
Sports halls, staircases, public areas, in-ground luminaires |
Replacing an old lamp with LED? Bases and equivalents
An LED equivalent is selected by three things: base, luminous flux (lm) and dimensions. The "equivalent watts" on the packaging are only a guide.
|
Base |
Typical location |
What to check when switching to LED |
Where to look |
|
E27 / E14 |
Ceiling and table lamps, candle lamps |
Bulb length inside the shade; with a dimmer – only "dimmable" |
E27, E14 |
|
GU10 |
Recessed spotlights, 230 V |
Beam angle: 36° for accent, 60–120° for general light |
GU10 |
|
GU5.3 (MR16) |
12 V spotlights |
An old electronic transformer may not work with a small LED load – flickering |
GU5.3 |
|
G9 / G4 |
Small decorative lamps, cooker hoods |
Dimensions and voltage: G9 – 230 V, G4 – usually 12 V |
G9, G4 |
|
R7s |
Halogen floodlights, floor lamps |
Length 78 or 118 mm and diameter – LED is often thicker |
R7s |
|
T8 (G13) |
Fluorescent tubes |
Single-ended or double-ended supply; remove the starter, bypass the ballast according to the diagram |
LED T8 |
|
E27 / E40 HQL, NAV |
Warehouse, street and workshop luminaires |
Ballast and ignitor are bypassed; LED lamp weight and cooling in a closed housing |
HQL / NAV equivalents |
⚠ What to check before buying
KibirkštisBefore ordering luminaires for a project, I always check these things – otherwise you end up replacing ones that are already installed.
|
What to check |
Why it matters |
|
Luminous flux (lm), not watts |
150 W at 150 lm/W gives more light than 200 W at 100 lm/W. Calculate quantity by lm. |
|
Mounting height and optics |
A wide beam mounted high scatters light onto the walls, a narrow beam mounted low leaves dark zones. |
|
IP rating for the environment |
Moisture and dust are the main causes of LED driver failure. |
|
Operating temperature |
Cold stores need from −30 °C, hot workshops up to +50 °C. |
|
UGR and CRI |
A glaring panel in an office means complaints; CRI 70 in a shop means unnatural product colours. |
|
Control: dimmer, DALI, 1–10 V, sensor |
The control method must be decided before purchase – the driver usually cannot be changed later. |
|
Inrush current and circuit breaker characteristic |
Many LED drivers in one group can trip a B-characteristic circuit breaker at switch-on. |
|
Mounting method and ceiling |
A recessed panel – only into a suspended ceiling; for concrete or plasterboard without a void – surface-mounted. |
✗ Most common mistakes
|
Mistake |
Consequence |
|
Luminaires chosen by watts or "equivalent" |
Too dark, or you pay for unnecessary power. |
|
IP20 luminaire in an unheated garage, basement or under a canopy |
Condensation and corrosion – the driver fails within a few months. |
|
IP65 luminaire recessed into the ground |
After rain or snowmelt water gets into the housing. In-ground use requires IP67. |
|
Floodlight aimed horizontally |
Dazzles drivers and neighbours, while the area itself stays dark. |
|
6500K light in a living room or bedroom |
The room looks cold and uninviting, and in the evening the light strains the eyes. |
|
LED strip without a profile, power supply without headroom |
The strip overheats and quickly loses brightness, the power supply runs at its limit and fails. |
|
Long 12 V strip fed from one end |
Voltage drop – at the far end the light is weaker and of a different tint. For long runs – 24 V or feeding from both ends. |
|
Ordinary LED bulb with an old dimmer |
Flickering, buzzing, the bulb does not switch off completely. |
|
LED T8 tube fitted without removing the starter or rewiring the circuit |
⚡ The lamp does not work or a short circuit may occur. |
⚡ Safe installation – advice from Fazė
-
Before installation, disconnect the circuit and verify that no voltage is present.
-
Protect the lighting circuit with a circuit breaker sized for the cable cross-section; for large LED groups take the inrush current into account (the number of luminaires per circuit breaker stated by the manufacturer).
-
Outdoors, enter cables from below; use sealed junction boxes or gel-filled connectors for joints.
-
When replacing HQL / NAV or T8 lamps with LED, rewire according to the LED lamp manufacturer's instructions and label the luminaire so that an old lamp is not fitted later.
-
Secure suspended industrial luminaires with a safety cable.
-
Connection to the 230 V mains must be carried out by a qualified electrician.
Frequently asked questions
The questions are asked by Kibirkštis – a young, curious electrician who dares to ask what others won't. The answers come from Fazė – an experienced engineer.
KibirkštisHow many watts of LED luminaire do I need per 1 m² of warehouse?
FazėCalculate in lux, not watts. For a warehouse with 150 lm/W luminaires, 200 lx is usually reached at 2–3 W/m², and 500 lx for production at 5–7 W/m². But this is only a guide: everything depends on the height, the racking and the colour of the walls.
KibirkštisUFO or linear luminaire for a warehouse?
FazėFor open space and high ceilings – UFO: fewer points, faster installation. For narrow aisles between tall racks – linear luminaires along the aisle, because the light falls on the shelves, not on top of the racks.
KibirkštisWhat is the difference between a recessed and a surface-mounted LED panel?
FazėA recessed panel is fitted into a suspended ceiling (Armstrong 600×600) or a plasterboard ceiling with a void. A surface-mounted panel is fixed directly to concrete or a flat ceiling. The lighting parameters are the same, only the mounting differs.
KibirkštisCan I simply screw an E40 LED lamp into an old HQL luminaire?
FazėUsually not without rewiring – the ballast and ignitor have to be bypassed so that the LED lamp receives direct 230 V. Also check that the lamp fits into the housing and that there is enough ventilation. If the housing is old and rusty, it is more economical to replace the whole luminaire.
KibirkštisWhy do LED luminaires flicker or glow after being switched off?
FazėThe most common causes – the switch breaks the neutral instead of the phase, the switch has an indicator light, or a long cable in which voltage is induced. Check that the switch breaks the phase; if that does not help, you need a switch rated for LED loads or a low-load compensator.
Kibirkštis12 V or 24 V LED strip?
FazėFor short runs in furniture both are fine. From 5 m and longer choose 24 V – the current is halved, so the voltage drop is smaller and the light is even along the whole length. Power supply rating = strip W/m × length × 1.25. E.g. 10 m × 9.6 W/m → at least 120 W.
KibirkštisHow much light must emergency lighting provide?
FazėAccording to EN 1838, at least 1 lx is required along the centre line of the escape route, and 0.5 lx in open areas. Autonomy is usually 1 h, for some buildings 3 h; the exact requirement is set by the design and fire safety regulations. Choose luminaires with self-test – fewer manual checks.
KibirkštisDo you help select lighting for a project?
FazėYes. Send us the floor plan or room dimensions, ceiling height and purpose – we will select the luminaires, calculate the quantity and send you an offer. For larger projects we prepare a DIALux calculation.
Contact us.
⚠ This guide is for reference only
The illuminance standards, calculation examples and selection advice in this guide are indicative and may contain inaccuracies. They do not replace a lighting design, the manufacturer's instructions or the requirements of applicable legislation. Before purchase and installation, check the parameters in the specific product description and the manufacturer's datasheet.
Responsibility for the selection of the lighting solution, compliance with standards and installation lies with the designer or qualified electrician carrying out the work. UAB „Elektrotechnikos sprendimai“ accepts no responsibility for the selection of products based on this guide, for installation or for possible errors.
Sources
Standards and regulations on which this guide is based. Checked 2026-10-24.
-
EN 12464-1:2021 – Light and lighting. Lighting of work places. Part 1: Indoor work places
-
EN 12464-2 – Light and lighting. Lighting of work places. Part 2: Outdoor work places
-
EN 1838 – Lighting applications. Emergency lighting
-
IEC 60529 – Degrees of protection provided by enclosures (IP code)
-
EN 62262 – Degrees of protection provided by enclosures for electrical equipment against external mechanical impacts (IK code)
-
Commission Regulation (EU) 2019/2020 – ecodesign requirements for light sources
Luminaires, sensors and mounting accessories – in a single order
Industrial, office, outdoor and emergency luminaires, LED strips, lamps and controls – all in one place. Send us the room dimensions or a list of luminaires: we will select them, calculate the quantity and send you an offer. The model you need is not in the catalogue? Some products are supplied to order.
Get an offer