Product Catalog
- Security and Surveillance Systems | accessories
- Lighting solutions for industrial | commercial | residential | outdoor environments | accessories
-
Automation and Control Systems
-
Automation control accessories
- Time voltage deviation current level network control visualization relay
- Signal towers | beacons | modules | accessories
- Power and time control relays for home automation with integrated SCHUKO sockets, designed for alternating and direct current protection and for household users.
- Boxes for signaling equipment | Signal lights
- Cam switches | for devices on/off control
- Electric motor control | protection management
- Soft starter devices for electric motors
- Energy meters
- Control components for automation and control systems
- Signal converters | controllers for automation control | for control systems
- Touchscreens | panels for automation control | control systems
- Automatic Circuit Breakers for Direct Current (DC) Circuits with Integrated Overload, Short-Circuit, and Voltage Stabilization Protection Functions
- Automation and Electrical Control Components | Contactors | Relays | SSR | Accessories
- Automation control | Data transmission | Low current
- Industrial measurement | counting | detection systems for conveyors
- Panel heaters | protection for electrical equipment against moisture and cold
- Converters-transformers from single-phase to three-phase voltage
- Silicone strip heaters | electric heating solutions for industry
- Heating elements for liquids | water | oils | food heating
- Heating elements | igniters | for stoves | boilers | heaters
- Insulation Monitoring & Power Supply Equipment for Medical IT Systems
-
Automation control accessories
- Smart Automated Products | Control | Transmission | Detection
- Electrical distribution and installation
- Solar Energy Generation and Management Equipment
- HVAC control solutions for heating and ventilation
- Accessories for cars
- Workplace Safety | Electrical Safety Equipment | LOTO
- Technical maintenance | service equipment | fire protection solutions
- Emergency safety | hygiene | sanitary solutions
- Other products
- Quality used products
Signal | Indicator Lamps 10mm | 22mm
-
Signal and indicator lights with a 10/22 mm mounting hole diameter are compact and widely used accessories in industrial and commercial automation. These lights are used as visual signals to indicate specific system statuses, warn of errors, or show the ON state, and often operate together with other control devices such as relays, controllers, or buttons. Due to their versatility, ease of installation, and durability, 10/22 mm signal lights are commonly used in industrial, automation, equipment control, and security systems.
-
Read more
Indicator lamp guide: voltage, colour, compact or modular, IP
Here you will find quick selection by situation, 4 solution levels, voltage selection, colours according to EN 60204-1, a phase indication diagram and the most common mistakes. Specific parameters are given in each product description.
Colour meanings: ■ information · ■ benefit, solution · ■ ⚠ check · ■ ⚡ safety, mistakes
Contents: What do you need? · 4 levels · Voltage · Colours · Compact or modular · Matrix · What to check · Mistakes · Diagram · FAQ⚡ Selection in 30 sELSprendimai recommendsWhat do you need? Quick selection
Situation Solution Where to look Voltage presence in the panel: L1, L2, L3 Three compact 230 V lamps between phase and neutral green 230 V, yellow 230 V, white 230 V Motor running or fault, 230 V control Compact 230 V lamp in parallel with the contactor coil or via the thermal relay contact green “running”, red “fault” 24 V control: PLC, controller outputs, safety extra-low voltage 24 V lamp, compact or modular compact red 24 V, modular green 24 V, modular white 24 V Same panel as with modular 22 mm push buttons Modular lamp – the same look and mounting as the push buttons modular green 230 V, modular red 230 V 110 V control transformer 110 V compact lamp white 110 V, blue 110 V Lamp connected between phases, 400 V 400 V compact lamp (between two phases) red 400 V, green 400 V, white 400 V 12 V battery, vehicles, low-voltage automation 12 V lamp: 22 mm or smaller 10 mm white 12 V, 22 mm, green 12 V, 10 mm Damper environment, a better sealed front is needed 220–230 V AC lamp with IP65 front green IP65, red IP65 The right lamp comes down to three decisions: voltage (must match the circuit it is connected to), colour (meaning according to EN 60204-1) and design (compact or modular, IP). Voltage is the most important: the wrong voltage burns out the LED or it does not light up.From basic to sealed: 4 solution levels
Start with level 1. A modular or sealed lamp is needed only when the panel design or the environment requires it.
LEVEL 1Compact 22 mm, IP54
For: distribution and automation panels, phase and status indication
What you get: one-piece housing, 2 terminals, 12 / 24 / 110 / 230 / 400 V AC/DC, 5 colours
Price from €1.49 incl. VAT
230 V: green · yellow · blue · white
24 V: red · 400 V: green · redLEVEL 2Modular 22 mm, IP54
For: panels with modular push buttons and selector switches – a uniform look
What you get: front part and LED block with holder, 24 V or 230 V AC/DC
Price from €2.75 incl. VAT
LEVEL 3With IP65 front, 220–230 V AC
For: damper rooms, dust, machine control panels
What you get: better sealed front, 6 colours including orange
Price from €1.92 incl. VAT
Voltage: the key parameter
An indicator lamp is connected directly to the circuit whose status it shows. Its voltage must match that circuit.
Where it is connected Choose Examples Phase–neutral 230 V, contactor coil 230 V 230 V green 230 V, modular green 230 V Between two phases (400 V) 400 V green 400 V, red 400 V PLC outputs, 24 V DC power supply 24 V red 24 V, modular green 24 V 110 V control transformer 110 V white 110 V, yellow 110 V 12 V battery or power supply 12 V white 12 V, green 12 V, 10 mm ⚠ A 230 V lamp connected between phases (400 V) will burn out. A 24 V lamp on 230 V burns out immediately. A 230 V lamp on 24 V will not light up.
Colours according to EN 60204-1
Colour Meaning Example Red Emergency, hazard – immediate action required Motor overload, emergency STOP pressed Yellow Abnormal condition, approaching critical High temperature, low level Green Normal condition Machine running, system ready Blue Mandatory operator action required Reset required (RESET), replace filter White Neutral information Voltage present, mode switched on
KibirkštisAnd how should I indicate phases L1, L2, L3? Does it have to be red–yellow–green?
FazėThe standard does not define colours for phase lamps. What matters is that it is consistent and labelled in the panel. Three lamps of the same colour or three different colours with L1, L2, L3 labels are commonly used.Compact or modular?
Compact (one-piece)A single housing with the LED inside. Cheaper, takes little space and comes in a wide voltage range from 12 to 400 V. Suitable for most distribution panels.
ModularFront part and LED block with holder, like modular push buttons. The panel looks uniform and the LED block can be replaced without removing the front part.
Selection matrix: all lamps in the group
Prices are “from”. Links next to the colours lead to products in stock or supplied to order.
Type Voltage Hole IP Colours Price from Products Compact 12 V AC/DC 22 mm IP54 white, blue, yellow, red, green 1,49 € white blue yellow Compact 24 V AC/DC 22 mm IP54 5 colours 1,49 € red Compact 110 V AC/DC 22 mm IP54 5 colours 1,49 € white blue yellow Compact 230 V AC/DC 22 mm IP54 5 colours 1,49 € green yellow blue white Compact 400 V AC/DC 22 mm IP54 5 colours 1,49 € green red yellow blue white Modular 24 V AC/DC 22 mm IP54 5 colours 2,75 € green red yellow white Modular 230 V AC/DC 22 mm IP54 5 colours 2,75 € green Compact, sealed 220–230 V AC 22 mm IP65 6 colours incl. orange 1,92 € green red orange Small 12 V 10 mm — yellow, green, red 1,21 € green yellow red ⚠ What to check before buying
KibirkštisBefore ordering lamps I always check these points, otherwise you end up making a second trip.What to check Why it matters Voltage and where it is connected (phase–neutral or between phases) The wrong voltage burns out the LED or it does not light up AC, DC or AC/DC Most of our lamps are marked AC/DC, IP65 lamps are AC only Colour Meaning according to EN 60204-1: red – emergency, green – normal condition Mounting hole 22 mm standard, 10 mm for small lamps Compact or modular Modular – when the panel already has modular push buttons and you want a uniform look IP IP54 – dry and moderate conditions, IP65 – dust and water jets from the front ✗ Most common mistakes
Mistake Consequence 230 V lamp connected between phases The lamp gets 400 V and burns out 24 V lamp in a 230 V circuit Burns out immediately Indication circuit without its own protection A short circuit in the lamp trips the whole incoming supply or burns the wires Green lamp indicating an emergency The operator misreads the status Lamp connected before the main switch Shows voltage even with the panel switched off – misleading when working in the panel
⚡ Safe installation – Fazė’s advice
- Before installation, disconnect the panel and verify that there is no voltage.
- Protect the indication circuit with a separate fuse or circuit breaker sized for the wire cross-section.
- A lamp that is off does not mean there is no voltage. Always measure before work.
- Label the lamps: L1, L2, L3, RUNNING, FAULT.
- Metal doors must be connected to PE.
☝ Elsprendimai.eu recommends: complement the lamps with push buttons, selector switches, enclosures, signal towers and audible signals.Diagram: phase and running indication – wrong and right
Three 230 V lamps show phases L1, L2, L3. Numbers correspond to the explanations below the diagram.
✗ WrongL1, L2, L3
before the main switch 3→no protection 2→230 V lamp
between L1 and L2 = 400 V 11 The lamp gets 400 V and burns out 2 A short circuit trips the incoming supply 3 The lamp stays lit even with the panel switched off
✓ RightMain switch
L1, L2, L3 3→Fuse / circuit breaker
for the indication circuit 2→3 × 230 V lamp
L1–N, L2–N, L3–N 11 Each lamp between phase and neutral (230 V) 2 Separate protection of the indication circuit 3 The lamps show whether the panel is switched on
The diagram is schematic and simplified and may contain inaccuracies. Before connecting, check against the manufacturer’s instructions and the markings on the devices. The qualified electrician performing the installation is responsible for it. UAB “Elektrotechnikos sprendimai” is not responsible for the connection or possible errors.
Why – explanation by diagram numbers
1 ✗ 230 V lamp between phases → ✓ Phase–neutral or a 400 V lamp
Why: the voltage between two phases is 400 V. If there is no neutral, choose 400 V lamps.2 ✗ No protection → ✓ Separate fuse or circuit breaker
Why: thin indication wires must be protected according to their cross-section, not the incoming supply current.3 ✗ Before the main switch → ✓ After the main switch
Why: then the lamps show whether the panel is switched on. If you need to show the incoming supply voltage, label it clearly.Frequently asked questions
Kibirkštis – a young, curious electrician – asks. Fazė – an experienced master electrician – answers.
KibirkštisWhy does an LED lamp glow faintly even when the circuit is switched off?
FazėThe most common cause is induced voltage in long control wires or leakage through a switch contact. Shorten the wires, route them away from power cables, or connect the lamp so that it is disconnected on both poles.
KibirkštisCan I connect a 230 V lamp to 400 V between phases?
FazėNo, it will burn out. If there is no neutral, choose 400 V lamps.
KibirkštisIs a modular lamp better than a compact one?
FazėIt is not better, just different. A modular lamp looks like the modular push buttons and its LED block can be replaced without removing the front part. A compact lamp is cheaper and available in more voltages – from 12 to 400 V.
KibirkštisWhat colour lamp should I use for “machine running”?
FazėGreen – normal condition according to EN 60204-1. Keep red for an emergency or fault. For the running indication use e.g. green 230 V.
KibirkštisDo I need an illuminated push button if I have a lamp?
FazėAn illuminated push button saves one hole in the door. When you need many statuses or different colours, separate lamps are often more convenient. See the push button guide.
KibirkštisDo you help select indication for a whole panel?
FazėYes. Send us the diagram or a list of statuses and the control voltage. We will select lamps, push buttons, selector switches and protection devices and send you a quote. Contact us.Other related guides: Push button guide · Selector switch guide · All product selection guides
Sources
- EN 60204-1 – Electrical equipment of machines (indicator colours)
- IEC/EN 60947-5-1 – Control circuit devices
- IEC 60529 – Degrees of protection (IP code)
- Promfactor Baltic manufacturer data and product markings
This guide is for information purposes only and does not replace a design or the manufacturer’s instructions. UAB “Elektrotechnikos sprendimai” accepts no responsibility for product selection based on this guide. The final decision is made by the designer or a qualified electrician. Published: 2026-11-06.
Lamps, push buttons and selector switches – in one order
Send us a diagram or a list and we will prepare a quote. Can’t find the model you need in the catalogue? Some products are supplied to order.
Get a quote +370 658 01033