Products catalog

Lamp control ballasts

  • Ballast guide: how to choose a ballast by lamp, wattage and installation conditions

    The guide covers all products in this category. Updated 2026-10-29.

    This category sells used original ballasts. They are intended for repairing existing luminaires when a faulty control gear needs to be replaced with the same or a compatible model instead of replacing the whole luminaire. The condition of each item is stated on its product page.

    A ballast is selected by three things that must all match together: lamp type, lamp wattage and mains voltage. If even one parameter does not match, the lamp will not ignite, will operate incorrectly or will fail quickly. There is no universal ballast “for all lamps”.

    What do you need? Quick selection

    Situation Solution Where to look
    The ballast has failed in a shop, display or office spotlight with a metal halide (CDM, HCI, HQI) lamp up to 150 W An electronic HID ballast of the same wattage. Ignition is already integrated, so no separate ignitor is needed. Matrix section “Electronic ballasts for MH / CDM lamps”
    Street, warehouse, hangar or greenhouse luminaire with a sodium (SON, NAV) or metal halide lamp 70–2000 W An electromagnetic NaHJ / BSN type ballast of the same wattage and voltage. An ignitor and, in most cases, a compensation capacitor are also required. Matrix section “Electromagnetic ballasts for sodium and MH lamps”
    Office, corridor or production luminaire with T8 (26 mm) or T5 (16 mm) fluorescent lamps An electronic ballast matching the number and wattage of lamps, e.g. 2×36 W or 1×49 W. No starter is needed. Sections “T8” and “T5 / T5 HO”
    The luminaire is connected to a lighting control system (1–10 V or DALI) and its light output can be dimmed Only a dimmable ballast with the same control interface. A standard ballast will not support dimming. Section “Dimmable ballasts”
    Old T8 luminaire with a choke and starter – you only want to replace the faulty choke An electromagnetic choke of the same wattage. The existing starter and capacitor remain. Section “Chokes”
    Luminaire with a compact fluorescent lamp (PL, TC-D, TC-T, TC-L) A ballast matching the lamp type, wattage and number of pins (2-pin or 4-pin base). Section “Compact fluorescent lamps”

    Electronic or electromagnetic ballast?

    Electronic ballast

    • Ignition and power factor correction are built in, no additional components are needed.
    • The lamp operates without flicker and noise and consumes less energy.
    • Most models switch off automatically when the lamp fails or reaches the end of its life.
    • The cable to the lamp is limited, e.g. OSRAM PTi 70 I – up to 1.5 m. Check the exact length in the manufacturer’s data.
    • More sensitive to high temperature: do not exceed the case temperature limit (tc).

    Electromagnetic ballast (choke)

    • Simple and robust, suitable for high wattages up to 2000 W and harsh conditions.
    • HID lamps require a separate ignitor, and T8 lamps – a starter.
    • A compensation capacitor is connected to improve the power factor. Its capacitance is stated on the ballast label.
    • Heavier, runs warm and may hum audibly.
    • When replacing a faulty electromagnetic ballast, it is worth checking the ignitor and capacitor at the same time.

    How to determine which ballast you need

    1. Lamp
    Read the lamp marking, e.g. CDM-T 70W, SON-T 150W, T8 36W
    →
    2. Old ballast
    Take a photo of the label: model, wattage, voltage, wiring diagram, capacitor capacitance
    →
    3. Mains
    230 V single-phase or 400 V phase-to-phase (high-wattage HID)
    →
    4. Equivalent
    Choose the same model or a ballast with the same three parameters

    Selection matrix: all ballasts in this category

    Product Lamp Wattage Note
    Electronic ballasts for metal halide (MH / CDM) lamps
    Philips PrimaVision Mini HID-PV m 20 /I CDM CDM 20 W Compact, for small spotlights
    Philips HID-PV C 35 /S CDM CDM 35 W Built into the luminaire
    Philips PrimaVision Compact HID-PV C 35 /I CDM CDM 35 W Version with cable clamp
    OSRAM POWERTRONIC PTi 70/220–240 S HCI, HQI 70 W Automatic shutdown on lamp failure
    OSRAM POWERTRONIC PTi 70/220–240 I HCI, HQI 70 W Cable to the lamp – up to 1.5 m
    OSRAM POWERTRONIC PT-FIT 70/220–240 S HCI, HQI 70 W Small dimensions, for slim luminaires
    Tridonic PCI 070 B011 CDM, HCI 70 W —
    Philips HID-PV 150 /S MH/CDM MH, CDM 150 W —
    Electronic ballast for white-light sodium lamps
    Philips HID-PV 100 /S SDW-TG SDW-TG 100 W For SDW-TG lamps only. Not suitable for standard SON lamps
    Electromagnetic ballasts for sodium and metal halide lamps – ignitor and capacitor required
    Vossloh-Schwabe VNaHJ 70PZTG.566 SON, MH 70 W —
    Hellas MHS 70W NAHJ SON, MH 70 W Rated voltage 240 V
    Vossloh-Schwabe NaHJ 100.941 SON, MH 100 W 230/240 V
    Hellas MHS 100W NAHJ SON, MH 100 W Rated voltage 240 V
    Hellas MHS 150W NAHJ SON, MH 150 W Rated voltage 240 V
    Philips BSN 150 K407-ITS SON, MH 150 W 230/240 V
    Hellas MHS 250W NAHJ SON, MH 250 W Rated voltage 240 V
    Hellas MHS Q400W NAHJ SON, MH 400 W Rated voltage 240 V
    Philips BSN 400 L33-A2-TS SON, MH 400 W 230 V
    Hellas MHS 600W NAHJ SON, MH 600 W Often used in greenhouses
    Hellas MHS 1000W NAHJ Q102 SON, MH 1000 W Rated voltage 240 V
    Philips BHL 2000 L78 MH 2000 W 230/240 V
    Hellas MHS 2000W NAHJ SON, MH 2000 W 380–400 V – connected between two phases
    Other HID control gear
    Philips ECP330 control unit SON-T 1000 W Separate IP65 housing for mounting outside the luminaire
    Hellas Q1000W-417.7 HQL (mercury vapour) 1000 W For repairing existing installations
    Electronic ballasts for T8 (26 mm) fluorescent lamps
    OSRAM QUICKTRONIC QTz8 1x18 T8 1×18 W —
    OSRAM QUICKTRONIC FIT 8 QT-FIT8 1x18 T8 1×18 W —
    Tridonic PC 1x58 T8 TOP T8 1×58 W —
    Tridonic PC 2x36 T8 PRO T8 2×36 W —
    KLiTE ECO 2x36W T8 2×36 W —
    KLiTE 2x36 220–240V T8 2×36 W —
    OSRAM QUICKTRONIC FIT 8 QT-FIT8 2x58–70 T8 2×58 W —
    Electronic ballasts for T5 (16 mm) / T5 HO lamps
    OSRAM QTP5 3x14/4x14 T5 HE 3×14 or 4×14 W For 600×600 Armstrong office ceiling luminaires
    OSRAM QTP5 1x24/39 T5 HO 1×24 or 1×39 W —
    OSRAM QTP5 1x49 T5 HO 1×49 W —
    OSRAM QT-FIT5 1x49 T5 HO 1×49 W —
    OSRAM QTP5 2x49 T5 HO 2×49 W —
    OSRAM QTP5 1x80 T5 HO, TC-L 1×80 W For high-bay spaces
    Dimmable ballasts (1–10 V and DALI)
    Philips HF-R 118 TL-D EII T8 (TL-D) 1×18 W 1–10 V control
    Philips HF-R 218 PL-T/C EII PL-T, PL-C 2×18 W 1–10 V control
    OSRAM QTi DALI 1x14/24 DIM T5, TC-L, TC-F 1×14–24 W DALI control
    Ballasts for compact fluorescent lamps
    Philips, electromagnetic Compact (PL) 18 W Connected with a starter
    ELT BE-226-TC TC-D/E, TC-T/E 2×18–26 W 4-pin lamps only
    OSRAM QUICKTRONIC QTP-M 1x26–42 TC-T/E, TC-D/E 1×26–42 W Supply 198–264 V AC/DC
    Electromagnetic chokes for fluorescent lamps – connected with a starter
    Hellas L36-843H.B2 T8 1×36 W 230 V, 50 Hz
    Hellas L58-803H T8 1×58 W 230 V, 50 Hz

    See each product page for stock availability and item condition.

    ● LED equivalents: when it is worth replacing the light source rather than the ballast

    Replacing the ballast makes sense when the luminaire is in good condition and needs to be restored quickly. If the lamp has also failed, or the luminaire runs many hours a year, it is often worth switching to LED: 50–70 % less energy, no ballast, ignitor or capacitor needed, and the light comes on instantly without warm-up.

    Current lamp LED equivalent What to do with the ballast Where to look
    T8 fluorescent (18, 36, 58 W) LED T8 tube of the same length (60, 120 or 150 cm) Depends on the LED tube type: some work with the existing electronic ballast, others are connected directly to 230 V with the ballast bypassed, and others work with an electromagnetic choke after replacing the starter with an LED starter. The type is specified by the manufacturer. LED T8 tubes
    T5 fluorescent (14–80 W) LED T5 tube Usually the T5 ballast is disconnected and the tube is connected directly to 230 V. Check compatibility with a specific ballast in the manufacturer’s list. LED T5 tubes
    Mercury vapour HQL (E27, E40) LED HQL replacement, e.g. 41 W instead of HQL 125 W or 90 W instead of HQL 250 W Wiring is specified by the lamp manufacturer: some replacements work with the existing HQL choke, others are connected only directly to 230 V. HQL E27, HQL E40
    Sodium NAV / SON (E27, E40) LED NAV replacement, e.g. 40 W, 7500 lm instead of NAV 100 W. Amber 1800 K versions retain the familiar street-light colour. The ignitor must be removed. Disconnect the ballast and capacitor and connect directly to 230 V, unless the lamp manufacturer specifies otherwise. NAV E27, NAV E40
    Metal halide / HID in high-bay spaces (E40, 250–400 W) UFO-type LED lamp E40, e.g. 105 W instead of HID 250 W or 150 W instead of HID 400 W The ballast, ignitor and capacitor are disconnected and the lamp is connected directly to 230 V. Check that the existing lampholder can bear the weight of the lamp. UFO E40 lamps
    Entire luminaire outdated or not worth repairing New LED luminaire: UFO-type high-bay, floodlight, street light or LED panel instead of a T5/T8 600×600 Armstrong office luminaire No ballast needed any more. This is often cheaper than replacing the ballast, ignitor, capacitor and lamp together. UFO luminaires, floodlights, street lights, LED panels

    ⚠ Before fitting an LED lamp into an old HID luminaire

    • The ignitor’s high-voltage pulse destroys an LED lamp instantly, so the ignitor must be removed from the circuit.
    • Always take the wiring diagram from the specific LED lamp manufacturer’s instructions, not from the old luminaire.
    • Mark the converted luminaire with a “LED 230 V only” sticker so that nobody fits a discharge lamp later.

    ⚠ What to check before buying

    What to check Why it matters
    Lamp type Sodium, metal halide, mercury vapour and fluorescent lamps have different ignition and operating characteristics. For example, the Philips HID-PV 100 /S SDW-TG is intended only for SDW-TG lamps and is not suitable for a standard SON lamp.
    Wattage The ballast wattage must match the lamp wattage. A 150 W ballast with a 100 W lamp will overload it, and with a 250 W lamp it will not let it reach its rated luminous flux.
    Voltage Most ballasts are rated 220–240 V, but the Hellas MHS 2000W is rated 380–400 V. If connected to 230 V, the lamp will not ignite. Electromagnetic ballasts rated 240 V deliver slightly less power to the lamp on a 230 V network.
    Ignitor and capacitor An electromagnetic HID ballast requires an ignitor matched to the ballast and lamp, plus a compensation capacitor. The wiring diagram and capacitor capacitance are stated on the ballast label.
    Cable length to the lamp Electronic HID ballasts have a cable length limit, because the ignition pulse weakens over an overly long cable. When mounting the ballast separately from the luminaire, check the manufacturer’s data.
    Dimensions and fixing The replacement must fit inside the luminaire housing and match the fixing holes. Measure the old ballast before ordering.
    Control interface 1–10 V and DALI ballasts are not interchangeable. If a dimmable luminaire is fitted with a standard ballast, the dimming function will be lost.

    ✗ Most common mistakes

    • The old ignitor is left in place with an electronic HID ballast. The electronic ballast already has integrated ignition, so the external ignitor must be removed.
    • The ballast is chosen by wattage but not by lamp type, e.g. a SON lamp is connected to a ballast intended only for CDM lamps.
    • A T5 lamp is connected to a T8 ballast. These lamps have different electrical parameters and are not compatible, even if the wattage is similar.
    • Only the ballast is replaced, although the ignitor has failed or the lamp has reached end of life. Flickering and cycling usually indicate an ageing lamp.
    • An LED tube is connected to an electronic ballast without checking compatibility. Many LED T8 tubes work only with specific ballast models or without a ballast.

    Frequently asked questions

    Can I replace an electromagnetic HID ballast with an electronic one?
    Yes, if the electronic ballast is intended for the same lamp and wattage. The luminaire must be rewired and the external ignitor and capacitor removed. This work must be carried out by a qualified electrician.

    Is the same ballast suitable for both sodium and metal halide lamps?
    Electromagnetic NaHJ-type ballasts are designed for both lamp types of the same wattage, but final compatibility also depends on the ignitor and the specific lamp. Electronic ballasts are usually designed for only one lamp type, which is stated in their designation.

    Why are mercury vapour lamp ballasts still sold?
    Mercury vapour (HQL) lamps are no longer produced in the EU, but some installations are still in operation. The ballast is intended for repairing such installations. For new lighting installations we recommend LED solutions.

    I can’t find my model. What should I do?
    Send photos of the old ballast label and the lamp. We will check whether we have a compatible equivalent or suggest an LED alternative.

    Important

    This guide is for information only. Final compatibility of the ballast with the lamp, ignitor and luminaire is confirmed by the manufacturer’s technical data and the device label. UAB “Elektrotechnikos sprendimai” is not liable for product selection made solely on the basis of this guide.

    Ballasts must be installed and connected by a qualified electrician with the power disconnected.

    Sources

    Manufacturer data used in this guide. Checked 2026-10-29.

    • OSRAM POWERTRONIC INTELLIGENT PTi 70 I – manufacturer’s datasheet
    • Philips HID-PV 100 /S SDW-TG – manufacturer’s technical data
    • Product designations and parameters – elsprendimai.eu product pages

    Ballast, ignitor or LED alternative – we will select it for you

    Send a photo of the old ballast label and the lamp marking. We will check compatibility and suggest the right solution – an equivalent from stock or an upgrade to LED light sources.

    Can’t find the model you need in the catalogue? Some products are supplied to order.

    Get a quote

    Ballasts are electrical devices used to control and stabilize the operation of light sources, especially fluorescent and LED lamps. They play an important role in ensuring proper lamp functionality, making sure that it receives the necessary amount of energy and is safe to use.

    Applications: Ballasts are commonly used in the following areas:

    Lighting systems: They are essential for the operation of fluorescent lamps and certain LED lamps.
    Industry: Used in various industrial lighting applications such as factories, warehouses, and offices.
    Automotive industry: They can also be used in car headlights, where a ballast is required to ensure optimal lamp performance.
    Advantages:

    Energy savings: Modern ballasts, especially electronic ones, help reduce energy consumption.
    Longer lamp lifespan: By properly managing electric current, ballasts help extend the lifespan of the lamp.
    Stability: Ballasts ensure a stable light output, helping to prevent flickering and other lighting-related issues.
    Disadvantages:

    Type dependency: Choosing the wrong ballast can lead to poor light quality or lamp failures.
    Production costs: Some ballasts can be expensive, especially electronic models, but their benefits often justify the costs.
    Technical specifications:

    Types:
    Electromechanical ballasts: Traditional, used in fluorescent lamps, often larger and heavier.
    Electronic ballasts: More compact, lighter, and more energy-efficient.
    Power: Can range from a few watts to several hundred watts, depending on lamp requirements.
    Voltage: Ballasts can operate at various voltages, typically 120V, 230V, or 277V.
    Ballasts are an essential component in modern lighting systems, ensuring efficient and safe operation of light sources. 

    Read more
    Electronic ballast for metal halide lamps | 70W | 220-240V | PCI 0070 B011 Tridonic
    Code: 86457898

    Tridonic PCI 0070 B011 – a high-quality electronic ballast designed for efficient and reliable operation of 70W CDM (metal halide) lamps. Suitable for use in both professional lighting systems and residential or commercial spaces. The ballast ensures stable lamp performance and longer service life, reducing energy losses and maximizing efficiency.

    Price 25.63 € VAT incl.
    ( 21.18 € VAT excl. )
    Electromagnetic ballast for compact fluorescent lamps | 18W | 230V | Philips
    Code: 9137101220

    Electromagnetic ballast designed for use with compact fluorescent lamps (CFL), including PL-T, PL-S, and PL-C models. This ballast ensures stable operation, supports both 2-pin and 4-pin CFL lamps, and is an excellent choice for residential, commercial, or industrial lighting systems.

    Price 12.67 € VAT incl.
    ( 10.47 € VAT excl. )
    Electronic ballast for compact fluorescent lamps | 49W | 198–264VAC/DC | IP20 | QTP-M 1x26-42 Osram
    Code: QTP-M1X26-42

    QUICKTRONIC MULTIWATT QTP-M 1x26…42 is a reliable and efficient electronic control gear (ECG) designed for compact fluorescent lamps (CFL). Thanks to advanced technology and long service life, this ballast is ideal for use in public buildings, industrial facilities, sports halls, and is also compatible with emergency lighting systems in accordance with EN 50172 / DIN VDE 0108-100 standards.

    Price 36.37 € VAT incl.
    ( 30.06 € VAT excl. )
    Electronic ballast for metal halide lamps | 150W | 220-240V | HID-PV 150/S MH/CDM Philips
    Code: 1713070358

    The HID-PV 150/S MH/CDM electronic ballast is a professional solution designed for the efficient powering and control of high-intensity discharge (HID) lamps, such as metal halide (MH) and ceramic discharge (CDM) lamps. This ballast ensures not only stable operation and extended lamp lifespan but also energy efficiency, reduced costs, and optimal light quality.

    Suitable for industrial, commercial, and residential systems where a reliable and precisely controlled light source is required – from production facilities to outdoor lighting or showcases. 

    Price 39.28 € VAT incl.
    ( 32.46 € VAT excl. )
    Electronic ballast for compact fluorescent lamps | 2x18-26W | 220-240V | BE-226-TC ELT
    Code: BE-226-TC

    High-quality electronic ballast designed for powering two compact fluorescent lamps (CFL), ensuring reliable ignition, constant light output, and extended lamp lifespan. It is ideal for use in both professional lighting projects and domestic applications, especially where efficient energy management and compatibility with emergency lighting systems according to the VDE 0108 standard are required.

    Price 19.59 € VAT incl.
    ( 16.19 € VAT excl. )
    Electronic ballast for CDM metal halide lamp | 35 W | 220–240 V | Philips PrimaVision Compact HID-PV C 35/S CDM | 9137006044 | 9610327651 | 9610327714 | 9610327847
    Code: 9137006044

    Used product. Philips PrimaVision Compact electronic ballast for one 35 W CDM metal halide lamp, 220–240 V, 50/60 Hz, with integrated ignition. Dimensions 109.6 × 74.4 × 32.2 mm.

    Price 15.95 € VAT incl.
    ( 13.18 € VAT excl. )
    Electronic ballast for metal halide lamps | 70 W | 220–240 V | IP20 | OSRAM POWERTRONIC PT-FIT 70/220–240 S
    Code: PT-FIT 70/220-240 S

    Used product. 70 W electronic ballast for metal halide (HCI / HQI) lamps with integrated ignition and automatic lamp shutdown on failure or at end of life. Dimensions 110 × 75 × 30 mm.

    Price 11.20 € VAT incl.
    ( 9.26 € VAT excl. )
    Electronic ballast for metal halide lamps | 70 W | 220–240 V | IP20 | OSRAM POWERTRONIC PTi 70/220–240 S
    Code: PTi 70/220-240 S

    Used product. 70 W electronic ballast for metal halide (HCI / HQI) lamps with integrated ignition and automatic lamp shutdown on failure or at end of life. Dimensions 110 × 75 × 30 mm.

    Price 9.90 € VAT incl.
    ( 8.18 € VAT excl. )
    Electromagnetic ballast for sodium and metal halide lamps | 70 W | Vossloh-Schwabe VNaHJ 70PZTG.566 | 535657
    Code: VNaHJ 70PZTG.566 535657

    Used product. Vossloh-Schwabe electromagnetic ballast for 70 W high-pressure sodium (SON / NAV) and metal halide lamps, in a plastic housing. Dimensions 175 × 70 × 64 mm.

    Price 22.75 € VAT incl.
    ( 18.80 € VAT excl. )
    Electronic ballast for metal halide lamps | 70 W | 220–240 V | IP20 | OSRAM POWERTRONIC PTi 70/220–240 I
    Code: PTi 70/220-240 I

    Used product. 70 W electronic ballast for metal halide (HCI / HQI) lamps with integrated ignition and automatic lamp shutdown on failure or at end of life. Suitable for 9 OSRAM HCI / HQI 70 W lamp types.

    Price 17.99 € VAT incl.
    ( 14.87 € VAT excl. )
    Electronic ballast for sodium lamps | 100W | 220-240V | HID-PV 100/S SDW-TG Philips
    Code: 9137006565

    PrimaVision HID-PV 100/S is a high-quality electronic ballast designed for 100W SDW-TG (mini White SON) high-pressure sodium lamps.

    This ballast features a compact, lightweight one-piece housing and is CE, ENEC, and CB certified. It is ideal for use in retail environments, exhibition lighting, and showcase systems where the balance of warm white light quality and energy efficiency is essential. 

    Price 123.90 € VAT incl.
    ( 102.40 € VAT excl. )