Products catalog

  • Differential pressure connection kit | aluminium nozzles | PVC tube 2m | up to 10000Pa | Sentera Controls | PSET-QF-200

    Code: PSET-QF-200
    Price 11.39 € VAT incl.
    ( 9.41 € VAT excl. )
    17.76 € You save 6.37 €
    Offer is valid until 2026-12-31
    Want another price? Suggest yours!
  • Differential pressure connection kit | aluminium nozzles | PVC tube 2m | up to 10000Pa | Sentera Controls | PSET-QF-200

    The PSET-QF-200 is a Sentera Controls differential pressure connection kit used to connect a pressure transmitter, controller or pressure switch to a duct. The kit contains 2 aluminium nozzles (46.4 mm, connection end Ø4 mm), a 200 cm transparent PVC tube and 2 galvanised M5 washers.

    Key idea:
    The right measuring point is half of accurate pressure control. The kit allows the “+” and “−” points in a duct or at a filter to be installed quickly and neatly to measure the pressure difference, and, when the fan K-factor is known, the airflow as well.
    Nozzles
    Aluminium, Ø4 mm
    Tube
    PVC, Ø5 × 7 mm, 200 cm
    Max. pressure
    10 000 Pa
    Max. temperature
    60 °C

    Operating principle

    Holes are drilled in the duct wall, the nozzles are inserted and secured with washers. The PVC tube is cut in two: one piece connects the higher pressure point to the device's "+" port, the other connects the lower pressure point to the "−" port.

    The device measures differential pressure (Pa). Connected to the fan measuring points and with its K factor known, it can measure or control air volume (m³/h).

    Result – stable measuring points from which the transmitter, controller or PSW switch obtains the true pressure difference. Engineer's note: place the nozzles away from sources of turbulence – bends, branches and cross-section changes; the required distance depends on the duct diameter.

    Benefits PSET-QF-200?
    Everything needed to install pressure difference measuring points in one kit – suitable for Sentera pressure transmitters, controllers and switches.

    Technical specifications

    Product type Differential pressure connection kit
    Manufacturer / code Sentera Controls / PSET-QF-200
    Nozzles 2 aluminium nozzles (46.4 mm, Ø4 mm connection end)
    Tube 1 × clear PVC, Ø5 × 7 mm, 200 cm
    Mounting 2 galvanized M5 washers (Ø15 mm)
    Max. operating pressure 10 000 Pa
    Max. operating temperature 60 °C
    Compliance WEEE 2012/19/EU

    Manufacturer documentation

    ✔ Recommended by Elektrotechnikos sprendimai

    Original manufacturer documentation – technical data, wiring diagrams and installation instructions.

    Main functions

    • Pressure difference measurement – for monitoring filters, duct static pressure and room pressure differences.
    • Air volume based on the K factor – together with an HPSP / DPSP controller – constant m³/h.
    • Universal – suitable for Sentera pressure transmitters, controllers and switches.
    • Quick installation – nozzles, tube and mounting hardware in a single bag.
    • Working pressure up to 10 000 Pa – suitable for all Sentera pressure ranges, including the 10K models.

    Where is it used?

    • Filter fouling monitoring
    • Duct static pressure measurement and control
    • Air volume measurement via the fan K factor
    • Connecting PSW pressure switches
    • Clean room pressure difference control
    • Heat exchanger pressure drop (frosting) monitoring in air handling units

    On-demand operation

    For industrial air system installers.
    Aluminum nozzles and a working pressure of up to 10 000 Pa also suit high-pressure 10K controllers and transmitters.
    For air handling unit manufacturers.
    Compact 46.4 mm nozzles with a Ø4 mm connection end, fastened with M5 washers.
    For HVAC commissioning engineers.
    When connected to the fan measuring points and with the K factor known, the controller measures and maintains the airflow in m³/h.

    Practical application

    If an HPSPF-10K or DPSPG-10K controller is used to maintain high process fan pressure, then the PSET-QF-200 aluminum nozzles and PVC tube ensure a connection for a working pressure of up to 10 000 Pa and a temperature of 60 °C.

    Application guide: how it is used in practice

    The PSET-QF-200 is used in various systems – only the connected device and the measuring point change:

    Site What is connected Result Installer's note
    Filter monitoring Nozzles before and after the filter → transmitter or PSW pressure switch Filter pressure drop is visible, filters are replaced on time Route the tubes without bends and kinks
    Constant duct pressure One nozzle in the duct (+), the other in the atmosphere (−) → HPSP / DPSP The fan maintains the set static pressure Install the nozzle away from elbows
    Constant air volume Fan measuring points → controller with K-factor The set m³/h is supplied You will find the K factor in the fan data

    How to choose a pressure connection kit

    Measurement task / duct Recommended model
    Pressure difference, airflow by K-factor – plastic nozzles PSET-PVC-200 (ABS nozzles, 2 m tube)
    Pressure difference, airflow by K-factor – aluminium nozzles PSET-QF-200 (aluminium nozzles, 2 m tube) ← this model
    Air velocity / air volume, duct Ø100–300 mm PSET-PTS-200 (Pitot tube 150 mm)
    Air velocity / air volume, duct Ø150–500 mm PSET-PTL-200 (Pitot tube 250 mm)
    Rule: for pressure difference (filter, duct static pressure) and airflow by fan K-factor – PSET-PVC-200 or PSET-QF-200; for air velocity and airflow by duct cross-section – Pitot tube: PSET-PTS-200 for Ø100–300 mm ducts, PSET-PTL-200 for Ø150–500 mm. For a rectangular duct calculate the equivalent diameter.
    When to choose another solution: plastic version – PSET-PVC-200; for measuring air velocity – Pitot tube kits PSET-PTS-200 and PSET-PTL-200; for additional tubing – TUBE-PVC0705-100 reel (100 m).

    Pros

    • Complete set for a single measurement
    • Up to 10 000 Pa
    • Suitable for all Sentera pressure devices
    • Aluminum nozzles
    • Compact 46.4 mm nozzles

    Cons / limitations

    • Operating temperature up to 60 °C
    • A Pitot tube is needed to measure air velocity
    • One kit – for one device

    Safety and installation notes

    • Before drilling the duct, make sure there are no cables or other services behind the wall.
    • Do not exceed an operating pressure of 10 000 Pa and a temperature of 60 °C.
    • Fix the tubes so that they are not kinked or pinched.

    Quick selection guide

    10 000 Pa
    PVC tube 2 m
    Aluminium nozzles
    60 °C
    Suitable when you need:
    • to install pressure difference measuring points in a duct or at a filter;
    • to connect a Sentera transmitter, controller or pressure switch;
    • to control airflow by fan K-factor.
    Check before use:
    • whether the pressure does not exceed 10 000 Pa;
    • whether the medium temperature is not higher than 60 °C;
    • whether a 200 cm tube length is enough.
    Important reminder: The PSET-QF-200 measures differential pressure; to measure air velocity in a duct, a Pitot tube kit is required.

    FAQ

    Is it suitable for PSW pressure switches?
    Yes, the kit is intended for pressure transmitters, controllers and switches.
    What is the maximum operating pressure?
    Up to 10 000 Pa.
    Can air volume be measured?
    Yes, together with a controller, when the fan K-factor is known.
    Is there only one tube?
    Yes, the 200 cm tube is cut in two for the “+” and “−” connections.
    How are the nozzles fixed?
    With two galvanized M5 washers (Ø15 mm), which are included in the kit.
    What is the maximum operating temperature?
    Up to 60 °C.

    Differential pressure connection kit | aluminium nozzles | PVC tube 2m | up to 10000Pa | Sentera Controls | PSET-QF-200

    Sentera PSET-QF-200 – differential pressure connection kit with aluminium nozzles and a 2 m PVC tube, up to 10 000 Pa – for connecting pressure transmitters, controllers and switches to a duct.

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • privacy policy