Differential pressure controller with 2 setpoints | 0-6000Pa | 0-10VDC/0-20mA/PWM | Modbus RTU | 24VAC/VDC | IP65 | Sentera Controls | SPS2G-6K0
The SPS2G-6K0 is a Sentera Controls differential pressure controller with two setpoints and integrated PI control, range 0–6000 Pa. It directly controls EC fans, frequency converters or other devices and maintains the set pressure or air volume, while switching between the two setpoints is done with a dry contact or via Modbus RTU.
Key idea:
Two setpoints are a simple day / night or high / low mode solution: a timer, switch or motion sensor switches the contact, and the controller immediately moves to the other pressure value. No BMS logic or second controller needed.Measuring range
0–6000 PaOutput
0-10 VDC / 0-20 mA / PWM (OC) + Modbus RTUPower supply
24 VAC / VDC, 3-wireSetpoints
2 (switched by OC contact or Modbus)Operating principle
The controller is wall-mounted; pressure tubes (PSET-PVC-200 or PSET-QF-200) are connected to the aluminium nozzles "+" and "−", and power (Vin, GND), Modbus RTU (A, /B), output AO1 and a dry contact OC for setpoint switching are connected at the terminals. The G type is powered with 24 VAC or VDC and connected with 3 wires; if G and F types are powered from the same AC transformer with a common GND, a short circuit is possible – use separate transformers or controllers of the same type.
The sensor measures the pressure difference within the 0–6000 Pa range, the controller works in pressure difference or air volume mode (when the fan K factor is known), and the measuring range is selected automatically according to the active setpoint. The integrated PI algorithm with an autotune function compares the measured value with the active setpoint and changes the output signal 0-10 VDC, 0-20 mA or PWM (open collector) – the type is selected with switch SW1.
Result – closing the OC contact (or a command via Modbus RTU) activates the second setpoint, so the same system runs in day / night or high / low pressure mode without an additional controller or BMS programming.
Benefits SPS2G-6K0?
Two pressure setpoints, PI control, selectable output and Modbus RTU in one IP65 enclosure – simple energy-saving day / night ventilation without additional automation.Technical specifications
Product type Differential pressure controller with 2 setpoints Manufacturer / code Sentera Controls / SPS2G-6K0 Series SPS2 (0–2000 / 0–6000 Pa; F – 24 VDC, G – 24 VAC / VDC) Measuring range 0–6000 Pa Power supply 15–24 VAC ±10 % or 18–34 VDC, 3-wire connection; max. 1.2 W, Imax 50 mA No-load current 10–20 mA (18–34 VDC); 10–15 mA (15–24 VAC) AO1 output 1 analog 0-10 VDC / 0-20 mA or digital PWM (open collector), selectable with switch SW1 Setpoints 2 – switched by dry contact OC or via Modbus RTU; High/Low, Day/Night modes Control PI, autotune, K factor setting Controlled quantities Pressure difference or airflow (when the K-factor is known) Accuracy ±3 % (analog voltage output) Long-term stability ±1 % per year Communication Modbus RTU (RS485), NBT line-end jumper; configuration with Sensistant or 3SModbus Indication Power LED (green), status LED5 (blue), Modbus LED (green) Button SW2 – sensor calibration and Modbus register reset Pressure nozzles Aluminium Protection class IP65 (EN 60529) Operating environment +10…+60 °C, < 95 % rH non-condensing Wires / cable gland 0.75 / 1.5 mm²; cable gland clamping range 3–6 mm Weight 0.13 kg (net) Compliance LVD 2014/35/EU, EMC 2014/30/EU, RoHS 2011/65/EU Manufacturer documentation
✔ Recommended by Elektrotechnikos sprendimaiOriginal manufacturer documentation – technical data, wiring diagrams and installation instructions.
Main functions
- Two setpoints – day / night or high / low pressure mode without additional controllers.
- Switching by OC contact – a timer, switch, motion sensor or BMS relay switches the setpoint.
- PI control and autotune – stable pressure maintenance and quick start-up.
- Selectable output – 0-10 VDC, 0-20 mA or PWM (open collector) – via switch SW1.
- Air volume mode – constant m³/h by the fan K-factor.
- Modbus RTU – setpoints and parameters are changed from the BMS; NBT jumper for the end of the line.
- Automatic range selection – the measuring range adapts to the selected setpoint.
Where is it used?
- Range 0–6000 Pa – for higher-pressure systems and fans
- Ventilation of offices and schools with day / night mode
- VAV and CAV systems with EC fans
- Clean room pressure and airflow control
- Sites that need two operating modes without a BMS
- Rooms with a motion sensor – a higher setpoint only when people are present
- Duct pressure maintenance with frequency-converter-controlled fans
On-demand operation
For the high-pressure fan installer.
The 0–6000 Pa range allows two-mode control where 2000 Pa is not enough.For building administrators.
Day/night mode is switched by a timer, switch or motion sensor via an OC contact – no BMS programming.For ventilation installers.
Type G is powered at 24 VAC or VDC and wired with 3 wires, so it suits an existing 24 VAC transformer.Practical application
If a high-pressure fan has to operate in high and low pressure modes, then the SPS2G-6K0 with a 0–6000 Pa range switches setpoints via a motion sensor or a BMS relay contact on OC and controls the frequency converter with a 0-20 mA signal. The controller can be powered from an existing 24 VAC transformer, wired with 3 wires.Application guide: how it is used in practice
The SPS2G-6K0 adapts to different sites – only what switches the setpoints and what is connected to the output change:
Site What is connected Result Installer's note Office, school (day / night) Timer or BMS relay → OC contact; AO1 → EC fan Higher pressure is maintained during working hours, lower at night Write the setpoint values via Modbus RTU Room with a motion sensor Motion sensor contact → OC When people are present, a higher setpoint is switched on OC – dry contact, no external voltage Constant air volume PSET-PVC-200 at the fan measuring points, K factor The fan delivers the set m³/h K factor – in the fan manufacturer's data Frequency converter AO1 0-10 VDC / 0-20 mA → converter analog input The converter controls the motor based on pressure Select the signal type with switch SW1 Building with BMS Modbus RTU → A, /B Setpoints are switched and changed centrally Close the NBT jumper at the end of the line How to choose the range of a pressure controller and power supply
Range / supply Recommended model 0–2000 Pa, 24 VDC (4-wire) SPS2F-2K0 (0–2000 Pa, 24 VDC) 0–6000 Pa, 24 VDC (4-wire) SPS2F-6K0 (0–6000 Pa, 24 VDC) 0–2000 Pa, 24 VAC / VDC (3-wire) SPS2G-2K0 (0–2000 Pa, 24 VAC / VDC) 0–6000 Pa, 24 VAC / VDC (3-wire) SPS2G-6K0 (0–6000 Pa, 24 VAC / VDC) ← this model Rule: choose the range according to the maximum operating pressure – 0–2000 Pa for most systems, 0–6000 Pa for higher-pressure systems. Choose the supply according to the site's power source: type F only 24 VDC, type G 24 VAC or VDC (the twin of this model is SPS2F-6K0).When to choose another solution: for a single setpoint with a wide choice of ranges – HPSP-2 / DPSP-2 (with display) controllers; for damper actuators – HPSA-2 / DPSA-2; for measurement only – HPS-2 / DPS-2 transmitters; for simple on/off control – PSW pressure switches.Pros
- Two setpoints with contact switching
- PI control and autotune
- 0-10 VDC / 0-20 mA / PWM output
- Modbus RTU
- IP65, aluminium nozzles
Cons / limitations
- No display – setpoint values and PI parameters are changed only via Modbus RTU (Sensistant or 3SModbus)
- Accuracy ±3 % – if a single setpoint is sufficient, the more accurate (±2 %) HPSP-2 / DPSP-2 controllers
- Operating environment from +10 °C – not suitable for unheated locations
- The pressure connection kit is not included – choose PSET-PVC-200 or PSET-QF-200
- Only for clean air and non-aggressive, non-flammable gases
Safety and installation notes
- Installation and connection are to be carried out by a qualified specialist with the power disconnected.
- Power supply – 15–24 VAC ±10 % or 18–34 VDC.
- Do not power G and F types from the same AC transformer with a common GND – a short circuit is possible.
- If AC power is used in the Modbus network, do not connect the GND terminal to other devices or to the CNVT-USB-RS485 converter – the communication electronics or the computer may be damaged.
- Ambient temperature +10…+60 °C, < 95 % rH non-condensing.
Quick selection guide
0–6000 Pa2 setpointsPI controller0-10 VDC / 0-20 mA / PWMModbus RTU24 VAC / VDCIP65Suitable when you need:- to implement day / night or high / low pressure mode;
- to maintain a constant pressure or airflow in the 0–6000 Pa range;
- to control an EC fan or frequency converter without BMS logic.
Check before use:- whether the operating pressure fits within 0–6000 Pa;
- what the setpoints will be switched with (dry contact or Modbus);
- the supply type (24 VDC or 24 VAC) and the number of wires;
- whether the ambient temperature is not below +10 °C.
Important reminder: The SPS2G-6K0 has no display – the setpoint values and PI parameters are set via Modbus RTU (Sensistant or 3SModbus).FAQ
How are the setpoints switched?
By a dry contact OC (timer, switch, motion sensor or BMS relay) or via Modbus RTU.What signal does the output provide?
0-10 VDC, 0-20 mA or PWM (open collector) – selected with switch SW1.Can air volume be controlled?
Yes, when the fan K-factor is known.What is the difference between F and G?
F – 24 VDC only, 4 wires; G – 24 VAC or VDC, 3 wires.Are pressure tubes included in the kit?
No, choose the PSET-PVC-200 or PSET-QF-200.In what environment can it be installed?
Operating environment +10…+60 °C, < 95 % rH non-condensing, so the controller is not suitable for unheated locations.Differential pressure controller with 2 setpoints | 0-6000Pa | 0-10VDC/0-20mA/PWM | Modbus RTU | 24VAC/VDC | IP65 | Sentera Controls | SPS2G-6K0
Sentera SPS2G-6K0 – differential pressure controller with 2 setpoints, 0–6000 Pa, PI control, 0-10 VDC / 0-20 mA / PWM output, Modbus RTU, 24 VAC / VDC, IP65 – for day / night ventilation with EC fans.
Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.ManufacturerThis product is marked with the CE label, which confirms that it complies with all applicable European Union directives and regulations. CE marking is not just a formality – it is an important indicator of quality and safety, ensuring that the product has been properly assessed, tested, and can be safely used throughout the EU market.
CE certification means that the product has been evaluated according to the main criteria:
Safety requirements – ensures that the product does not pose a risk to the user or the environment
Electromagnetic compatibility (EMC) – the device does not interfere with other equipment and is resistant to external disturbances
Environmental standards – complies with current ecological and material usage requirements
Operational reliability – the product is suitable for long-term use according to its intended purposeCE marking allows this product to:
be legally supplied and used in all European Union countries
ensure a high level of quality and safety
be used in residential, commercial, and industrial environmentsThe CE mark is a declaration of the manufacturer’s responsibility, confirming that the product complies with all applicable standards and has been assessed according to EU legislation.