Differential pressure PI controller for fans | 0-2000Pa | 0-10VDC/0-20mA/PWM | Modbus RTU | 24VAC/VDC | IP65 | Sentera Controls | HPSPG-2K0
Code: HPSPG-2K0Offer is valid until 2026-12-31Price 144.74 € VAT incl.( 119.62 € VAT excl. )225.81 €You save 81.07 €Want another price? Suggest yours!-
Differential pressure PI controller for fans | 0-2000Pa | 0-10VDC/0-20mA/PWM | Modbus RTU | 24VAC/VDC | IP65 | Sentera Controls | HPSPG-2K0
HPSPG-2K0 – a Sentera Controls differential pressure controller with an integrated PI control algorithm, measuring range 0–2000 Pa. It measures the pressure difference itself and, via its 0-10 VDC / 0-20 mA analog or PWM output, directly controls EC fans, frequency converters or AC fan speed controllers to maintain the set value.
Key idea:
This is a sensor and a controller in one housing: no separate pressure transmitter, PLC or BMS logic is needed. The controller itself changes the fan speed until the pressure, airflow or air velocity in the duct matches the setpoint – the system adapts to damper positions and filter fouling.Measuring range
0–2000 PaOutput
0-10 VDC / 0-20 mA / PWM + Modbus RTUPower supply
24 VAC / VDC, 3-wireProtection class
IP65Operating principle
The controller is mounted on a wall or duct structure; the measuring points are connected to the aluminium nozzles "+" and "−" with tubes (PSET-PVC-200, PSET-QF-200 or the Pitot tube kit PSET-PTS-200 / PSET-PTL-200). Power (Vin, GND), the Modbus RTU line (A, /B) and the analog output AO1 to the fan are connected at the terminals. The G type is connected with 3 wires – the analog output GND is internally connected to the power GND, so do not connect this common GND to other DC-powered devices (the equipment may be permanently damaged), and do not mix F and G types in the same network.
An integrated high-resolution digital sensor measures the pressure difference within the 0–2000 Pa range, and the controller, depending on the mode selected over Modbus RTU, works by pressure difference (Pa), air volume (m³/h – when the fan K factor is known, otherwise Q = A × V) or air velocity (m/s – with a Pitot tube kit). The PI algorithm with anti-windup compares the measured value with the setpoint and changes the AO1 signal of 0-10 VDC (RL ≥ 50 kΩ), 0-20 mA (RL ≤ 500 Ω) or 0–100 % PWM (1 kHz); the P and I coefficients, response time (0.1–10 s), min. / max. interval and alarm limits are set over Modbus RTU.
Result – the fan speed is varied until the pressure, airflow or air velocity matches the setpoint, so the system adapts to damper positions and filter fouling without a separate sensor and PLC. Four LEDs show whether the value is stable within the interval, outside it or in the alarm zone, and the same status is available via Modbus RTU.
Benefits HPSPG-2K0?
One compact IP65 device replaces a pressure transmitter and a separate controller: it measures, regulates, signals with LED indicators and integrates into a BMS via Modbus RTU.Technical specifications
Product type Differential pressure PI controller for fans Manufacturer / code Sentera Controls / HPSPG-2K0 Series HPSP-2 (0–1000 / 2000 / 4000 / 10 000 Pa) Measuring range 0–2000 Pa Controlled quantities Pressure difference (Pa), airflow (m³/h), air velocity (m/s) Control PI with anti-windup; integrated K factor Power supply 18–34 VDC (max. 1.71 W, Imax 95 mA) or 15–24 VAC ±10 % (max. 3.3 W, Imax 220 mA) Connection 3-wire connection (common GND) Analog / modulating output AO1 0-10 VDC (RL ≥ 50 kΩ) / 0-20 mA (RL ≤ 500 Ω) / 0–100 % PWM, 1 kHz (RL ≥ 50 kΩ) PWM internal voltage source 3.3 or 12 VDC (jumper JP1) Accuracy ±2 % of the measuring range Response time 0.1–10 s (selectable) Communication Modbus RTU (RS485), configuration with 3SModbus or Sensistant Indication 4 LEDs (green – power / Modbus, green – within range, yellow – out of range, red – alarm / sensor fault) Button SW1 – sensor zero calibration and Modbus register reset Pressure nozzles Aluminium, “+” and “−” Housing ASA, grey (RAL 9002) Protection class IP65 (EN 60529) Operating environment -5…+65 °C, < 95 % rH non-condensing Wire cross-section 1.5 mm² (recommended) Weight 0.12 kg (net) Compliance EMC 2014/30/EU (EN 61326-1, EN 61326-2-3), WEEE 2012/19/EU, RoHS 2011/65/EU Manufacturer documentation
✔ Recommended by Elektrotechnikos sprendimaiOriginal manufacturer documentation – technical data, wiring diagrams and installation instructions.
Main functions
- PI control with anti-windup – the controller maintains the setpoint itself and directly controls the fan – no PLC or separate controller is needed.
- Three modes – pressure difference, airflow (by K-factor) or air velocity (with a Pitot tube).
- Selectable output – 0-10 VDC, 0-20 mA or PWM – suitable for most EC motors, frequency converters and actuators.
- Adjustable response time – 0.1–10 s – stable control even with pulsating flow.
- Range and alarm limits – LED indicators and Modbus registers immediately show when a value goes outside the permitted limits.
- Modbus RTU – setpoint, PI coefficients and status are controlled and monitored from a BMS or SCADA.
- Zero calibration – with the SW1 button – quick commissioning on site.
Where is it used?
- Measuring range 0–2000 Pa – for most ventilation systems – maintaining the pressure or air volume in the supply and extract ducts of air handling units
- Maintaining constant pressure in supply and extract ducts
- Constant air volume (CAV) / variable air volume (VAV) systems with EC fans
- Overpressure in clean rooms and stairwells (fire protection)
- Reduced pressure in restaurant kitchens and laboratories
- Ensuring the minimum ventilation air volume (m³/h) in buildings
- Ventilation modernization by replacing fans with EC fans
On-demand operation
For air handling unit commissioning technicians.
0–2000 Pa covers the working pressure of most supply and extract ducts, with an accuracy of ±40 Pa.For the BMS integrator.
A controller without a display: the setpoint, PI coefficients, alarms and status are controlled via Modbus RTU, so it connects naturally to SCADA.For ventilation modernization installers.
The 24 VAC or VDC (3-wire) power supply allows the 24 VAC transformer already on site to be used.Practical application
If an air handling unit has to supply a constant air volume regardless of filter contamination, then the HPSPG-2K0 is connected to the fan measuring points, the K factor is entered over Modbus RTU, and the controller maintains the set m³/h in the 0–2000 Pa range. The controller can be powered from an existing 24 VAC transformer, wired with 3 wires.Application guide: how it is used in practice
The same HPSPG-2K0 adapts to different sites – only the measuring points and what is connected to the output change:
Site What is connected Result Installer's note Supply duct of the air handling unit PSET-PVC-200 or PSET-QF-200 → + / −; AO1 → EC fan 0-10 VDC input The fan maintains the set static pressure regardless of damper positions and filter fouling Set the setpoint and PI coefficients via Modbus RTU Constant air volume (CAV) PSET-PVC-200 at the fan inlet measuring points; known K factor The fan delivers the set m³/h regardless of filter fouling You will find the K factor in the fan manufacturer's data Maintaining air velocity in the duct Pitot tube PSET-PTS-200 (Ø100–300 mm) or PSET-PTL-200 (Ø150–500 mm) The controller maintains the set air velocity (m/s) and, when the cross-section is known, the airflow Install the tube no closer than 7.5 D downstream of an elbow or a fan AC fan or frequency converter AO1 0-10 VDC / 0-20 mA → Sentera speed controller or frequency converter input The same controller also controls non-EC actuators Select the signal type via Modbus RTU Building with BMS / SCADA Modbus RTU (RS485) → A, /B Setpoint and alarms are changed centrally, status is monitored remotely For configuration – the CNVT-USB-RS485 converter and the 3SModbus software Power supply 24 VAC transformer or 24 VDC source → Vin, GND Stable controller operation Do not connect the common GND to other DC-powered devices How to choose the range of a pressure controller
Measuring range Recommended model -125…+125 Pa (bidirectional) HPSPG-LP (-125…+125 Pa, 24 VAC / VDC) 0–1000 Pa HPSPG-1K0 (0–1000 Pa, 24 VAC / VDC) 0–2000 Pa HPSPG-2K0 (0–2000 Pa, 24 VAC / VDC) ← this model 0–4000 Pa HPSPG-4K0 (0–4000 Pa, 24 VAC / VDC) 0–10 000 Pa HPSPG-10K (0–10 000 Pa, 24 VAC / VDC) Rule: the operating pressure must be within the range and, ideally, occupy a larger part of it – the ±2 % accuracy is calculated from the full range, so do not choose an overly large range for a low pressure. Choose the supply according to the system: type F – 24 VDC, 4-wire; type G – 24 VAC / VDC, 3-wire (the twin of this model is HPSPF-2K0).When to choose another solution: with an LED display – DPSPG-2K0; for controlling damper actuators – HPSA series; for two setpoints (day / night) – SPS2 series; for pressure measurement only, without regulation – HPS-2 / DPS-2 transmitters; for simple on / off switching by pressure – PSW pressure switches.Pros
- Sensor and PI controller in one
- Pressure, airflow or air velocity mode
- 0-10 VDC / 0-20 mA / PWM output
- Modbus RTU – all parameters remotely
- IP65 enclosure, aluminium nozzles
- Adjustable response time 0.1–10 s
Cons / limitations
- No display – the value is visible only via Modbus RTU or LED statuses (with a display – DPSPG-2K0)
- The setpoint and PI parameters are changed only via Modbus RTU – a CNVT-USB-RS485 converter and the 3SModbus software are required
- Do not connect the common GND to other DC-powered devices
- The pressure connection kit is not included – choose PSET-PVC-200, PSET-QF-200 or the Pitot kit PSET-PTS-200 / PSET-PTL-200
- Only for clean air and non-aggressive, non-flammable gases
Safety and installation notes
- Installation and connection are to be carried out by a qualified specialist with the power disconnected.
- Power supply – only 18–34 VDC or 15–24 VAC ±10 %; do not exceed the specified limits.
- Do not connect the common GND of a G-type controller to other DC-powered devices – the equipment may be irreversibly damaged.
- Do not use type F and G controllers in the same network.
- For clean air and non-aggressive, non-flammable gases only; ambient temperature -5…+65 °C, non-condensing.
- Before start-up, perform zero calibration of the sensor (button SW1) with the pressure tubes disconnected.
Quick selection guide
0–2000 PaPI controller0-10 VDC / 0-20 mA / PWMModbus RTU24 VAC / VDCIP65Suitable when you need:- to maintain a constant pressure or airflow in the 0–2000 Pa range by controlling a fan;
- to avoid tuning a separate sensor and controller;
- to integrate pressure control into a BMS via Modbus RTU.
Check before use:- the operating pressure – whether it fits within the 0–2000 Pa range;
- the input signal of the controlled device (0-10 VDC, 0-20 mA or PWM);
- the supply type and connection: 24 VAC / VDC, 3-wire (type G);
- whether a pressure connection kit is needed (PSET-PVC-200, PSET-QF-200, PSET-PTS-200, PSET-PTL-200).
Important reminder: The HPSPG-2K0 regulates to a single setpoint; the setpoint and parameters are set via Modbus RTU, so commissioning requires a CNVT-USB-RS485 converter and the 3SModbus software.FAQ
How do I set the setpoint?
Via Modbus RTU – with the CNVT-USB-RS485 converter and the free Sentera 3SModbus software or Sensistant.Can it be controlled by air volume in m³/h?
Yes, if the fan K-factor is known; otherwise the airflow is calculated from the air velocity and the duct cross-section (Q = A × V) using a Pitot tube kit.What is the difference between the F and G types?
F – 24 VDC, separate supply and output GND, connected with 4 wires; G – 24 VAC or VDC, common GND, connected with 3 wires.Are pressure tubes included in the kit?
No, choose the PSET-PVC-200, PSET-QF-200 or the Pitot tube kit PSET-PTS-200 / PSET-PTL-200.What is the accuracy?
±2 % of the measuring range – for the HPSPG-2K0 model this is ±40 Pa.Can it be installed outdoors?
IP65 housing; the datasheet specifies an operating environment of -5…+65 °C, < 95 % rH non-condensing.Differential pressure PI controller for fans | 0-2000Pa | 0-10VDC/0-20mA/PWM | Modbus RTU | 24VAC/VDC | IP65 | Sentera Controls | HPSPG-2K0
Sentera HPSPG-2K0 – differential pressure PI controller 0–2000 Pa, directly controlling EC fans, frequency converters or AC fan speed controllers with a 0-10 VDC / 0-20 mA / PWM signal, with Modbus RTU, 24 VAC / VDC supply and IP65 housing.
Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.ManufacturerThis product is marked with the CE label, which confirms that it complies with all applicable European Union directives and regulations. CE marking is not just a formality – it is an important indicator of quality and safety, ensuring that the product has been properly assessed, tested, and can be safely used throughout the EU market.
CE certification means that the product has been evaluated according to the main criteria:
Safety requirements – ensures that the product does not pose a risk to the user or the environment
Electromagnetic compatibility (EMC) – the device does not interfere with other equipment and is resistant to external disturbances
Environmental standards – complies with current ecological and material usage requirements
Operational reliability – the product is suitable for long-term use according to its intended purposeCE marking allows this product to:
be legally supplied and used in all European Union countries
ensure a high level of quality and safety
be used in residential, commercial, and industrial environmentsThe CE mark is a declaration of the manufacturer’s responsibility, confirming that the product complies with all applicable standards and has been assessed according to EU legislation.
What does this mean for you as a buyer?
Safe use in everyday activities
Reliable performance and reduced risk of failure
Compliance with EU standards and requirements
Suitability for professional solutions
Love it? Share your thoughts in a review!Write Review










