  • Differential pressure relay 0,2-5mbar | 10A | 115-277VAC

    Code: ESLF35-2

    Differential air pressure switch 0.2–5 mbar, SPDT 10 A, −40…+82 °C. For fan, filter and burner airflow monitoring.

  • Differential pressure relay 0,2-5mbar | 10A | 115-277VAC

    Differential pressure switch for air with a setting range of 0.2–5 mbar. It proves airflow in ducts, monitors filter clogging and fan operation: when the pressure difference reaches the set point, the SPDT contact changes over and signals the controls or opens the circuit.

    Key idea:
    Ventilation and combustion systems need a clear yes/no signal: is the fan really running, is the filter still clean. This switch checks it without electronics, and the 10 A contact allows direct connection to the control circuit.
    Setting range
    0.2–5 mbar
    Contact
    SPDT, 10 A, 115–277 V AC
    Max. pressure
    30 mbar
    Operating temp.
    −40…+82 °C

    Operating principle

    The switch is mounted on a wall or duct with the diaphragm in any vertical plane. Pressure ports are connected to the measuring points with 0.25" tubing or flexible hoses.

    The pressure difference acts on the diaphragm; when the set point is reached, the microswitch changes over. The switching differential increases progressively: ≈0.05…0.25 mbar from minimum to maximum setting.

    The result is a reliable signal for the controls: fan running confirmation, filter alarm or burner airflow monitoring.

    Why choose the LF35 differential pressure switch?
    The metal construction, wide operating temperature range and 10 A contact allow use in demanding locations – outdoor units or near burners.

    Technical specifications

    Product typeDifferential air pressure switch (diaphragm, SPDT)
    Manufacturer / seriesLEFOO / LF35
    Setting range0.2–5 mbar
    Switching differential≈0.05…0.25 mbar (progressive)
    Maximum pressure30 mbar
    Mediumair
    Measured pressurepositive, negative or differential
    ContactSPDT
    Electrical rating10 A non-inductive, 277 V AC; 300 VA pilot duty 115–277 V AC
    Operating temperature−40…+82 °C
    Connections0.25" OD compression fittings for tubing or 0.25" slip-on connectors for hose
    Mounting positiondiaphragm in any vertical plane

    Main functions

    • Airflow proving – the controls know the fan is really running.
    • Filter clogging alarm – a signal when resistance exceeds the limit.
    • SPDT contact 10 A – direct connection to the control circuit.
    • Positive, negative and differential pressure – flexible connection.
    • Wide temperature range – −40…+82 °C.

    Where is it used?

    • Fan operation monitoring in air handling units
    • Filter clogging alarms
    • Burner and boiler airflow monitoring
    • Airflow monitoring in ducts and pipes
    • Tunnel and shaft ventilation
    • Building energy management systems

    Use by need

    For ventilation controls installers.
    Simple fan running confirmation without extra transmitters.
    For boiler / burner service.
    Airflow monitoring for the combustion safety circuit.
    For facility managers.
    Automatic signal when to replace a filter.

    Practical application

    If an air handling unit filter should be replaced when its resistance reaches ~2 mbar (200 Pa), choose a range that covers this value, connect “+” before the filter and “−” after it, and set the limit to 2 mbar – the contact will give an alarm when it is reached.

    Pros

    • Robust metal construction
    • 10 A SPDT contact
    • Wide temperature range −40…+82 °C
    • For positive, negative and differential pressure
    • No power supply needed

    Cons / limitations

    • Does not output a pressure value – a pressure transmitter is needed for that
    • Air only – not for liquids
    • Limited maximum pressure – 30 mbar
    • Manual setting, no display

    Safety and installation notes

    • Make electrical connections only with the voltage disconnected.
    • Do not exceed 30 mbar or the contact current.
    • Mount the diaphragm in a vertical plane.
    • Fit hoses tightly to avoid leaks.
    • After setting, verify switching under real conditions.

    Quick selection guide

    Range 0.2–5 mbar
    SPDT 10 A
    Air
    −40…+82 °C
    Suitable when you need:
    • to confirm fan operation
    • a filter clogging alarm
    • burner airflow monitoring
    Check before use:
    • the required set point is within the range
    • the pressure will not exceed 30 mbar
    • the control circuit matches the contact rating
    Important reminder: the switch only signals a pressure limit – it does not replace combustion safety controls where standards require them.

    FAQ

    What is this switch for?
    For airflow and filter clogging monitoring in ventilation and combustion systems.
    Can it measure vacuum?
    Yes, it works with positive, negative and differential pressure.
    Does it need power?
    No, the switch works mechanically.
    What is the contact rating?
    10 A non-inductive load, 115–277 V AC.
    Is it suitable for water?
    No, it is for air only.
    How should it be mounted?
    With the diaphragm in any vertical plane.

    Differential pressure relay 0,2-5mbar | 10A | 115-277VAC

    LEFOO LF35 differential air pressure switch 0.2–5 mbar, SPDT 10 A – for fan operation, filter clogging and burner airflow monitoring.

    Published: 2026-11-16 · Data verified against the manufacturer's datasheet: 2026-11-16

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • Alternative products

  • privacy policy

    Information