    The PSW--200-PVC is a Sentera Controls adjustable differential pressure switch for the 20–200 Pa range. It monitors overpressure, vacuum or pressure difference in air and, when the set limit is reached, switches a dry changeover contact. The kit includes PSET-PVC connection nozzles, PVC tubes and mounting screws.

    Key idea:
    This is the simplest and most reliable way to obtain a “pressure present / no pressure” signal: a clogged filter, a stalled fan or insufficient flow is passed straight to the automation or an alarm – without power supply or programming.
    Control range
    20–200 Pa
    Contact
    Changeover, 1.5 (0.4) A / 250 VAC
    Switching differential
    ΔP 10 Pa
    Protection class
    IP54 (with cover)

    Operating principle

    The switch is mounted on a suitable surface. Nozzle P1 is connected to the higher-pressure (or lower-vacuum) point, P2 to the lower-pressure (or higher-vacuum) point. The wires are routed through the PG 11 gland to terminals 1 (NC), 2 (NO), 3 (COM).

    A silicone diaphragm responds to the pressure difference between P1 and P2. The switching threshold is set with a graduated, calibrated knob under the cover. As the pressure difference increases and reaches the set threshold, contact 3–2 closes and 3–1 opens. The switching differential (hysteresis) is 10 Pa. The contact is voltage-free, so it can be connected to a controller input, a relay coil or a signalling circuit.

    Result – the automation or signalling circuit receives a clear binary signal about a clogged filter, a stopped fan or an interrupted airflow. Engineer's note: when the switching threshold is below 50 Pa, the switch must not be mounted upside down – the weight of the diaphragm would affect the switching point. Accuracy per EN 1854 – ≤ ±15 % (min. ±10 Pa), so the switch is intended for monitoring and protection, not for precise measurement.

    Benefits PSW--200-PVC?
    A simple pressure monitor that is independent of the power supply, with a changeover contact and a mechanical life of 10 000 000 cycles – with everything needed for connection to the duct.

    Technical specifications

    Product type Differential pressure switch (pressure switch)
    Manufacturer / code Sentera Controls / PSW--200-PVC
    Series PSW (20–200 Pa / 50–500 Pa; with or without the PVC kit)
    Control range 20–200 Pa (0.2–2.0 mbar)
    Switching differential ΔP 10 Pa (0.1 mbar)
    Contact Changeover: 1 – NC, 2 – NO, 3 – COM
    Switching capacity Max. 1.5 (0.4) A / 250 VAC (VDE 0630)
    Max. operating pressure 10 kPa
    Accuracy ≤ ±15 %, min. ±10 Pa (EN 1854)
    Mechanical life 10 000 000 cycles
    Diaphragm Silicone
    Medium Air and other non-flammable, non-aggressive gases
    Pressure connections + (P1) and − (P2)
    Cable entry PG 11
    Protection class IP54 with cover, IP00 without cover (EN 60529)
    Operating temperature -20…+85 °C
    Storage temperature -40…+85 °C
    Humidity < 95 % rH non-condensing
    Scope of delivery Switch, PSET-PVC nozzles (r-ABS, 83 mm, connection end Ø6.4 mm), PVC tubes Ø7 mm (max. 10 000 Pa, up to 60 °C), mounting screws
    Compliance LVD 2014/35/EU, WEEE 2012/19/EU, RoHS (EU) 2015/863, Gas Appliances Regulation 2016/426/EU, EN 1854

    Main functions

    • Adjustable switching point – graduated knob within 20–200 Pa.
    • Changeover contact – NO and NC – suitable for both alarm and interlock.
    • No power supply needed – the relay is mechanical – it works independently of the automation power supply.
    • Long service life – 10 000 000 switching operations.
    • Silicone diaphragm – no outgassing, stable operation.
    • Complete set – nozzles, tubes and screws – install straight away with no extra purchases.

    Where is it used?

    • Range 20–200 Pa – for low-pressure monitoring: residential and small ventilation units, clean filters
    • Air filter contamination monitoring
    • Fan operation monitoring (flow presence)
    • Overheat protection for duct electric heaters
    • Heat exchanger frost protection in air handling units
    • Control of air and fire dampers

    On-demand operation

    For ventilation installers.
    Includes PSET-PVC nozzles, PVC tubes and screws, so the switch can be installed straight away with no extra purchases.
    For the installer of electric duct heaters.
    The NO contact allows the heater to be switched on only when there is airflow, and the 20–200 Pa range suits low-pressure ducts.
    For building technicians.
    A timely clogged-filter signal reduces energy consumption and the risk of faults.

    Practical application

    If an electric duct heater must switch on only when there is airflow, then the PSW--200-PVC with the supplied nozzles is connected to the pressure side of the fan, and the NO contact (3–2) is wired into the heater's enable circuit.

    Application guide: how it is used in practice

    The PSW--200-PVC adapts to different monitoring tasks – only the connection points and the use of the contact change:

    Site What is connected Result Installer's note
    Filter fouling monitoring P1 before the filter, P2 after the filter When the filter becomes clogged, the contact switches and gives a “replace filter” signal Set the limit according to the filter manufacturer's final pressure drop
    Fan operation monitoring P1 on the fan pressure side, P2 in the atmosphere or on the suction side Alarm if the fan is not turning or the belt has broken Use contact 3–2 as "flow present"
    Electric duct heater Relay NO contact → heater enable circuit The heater is switched on only when there is airflow Install according to the heater manufacturer's instructions
    Heat exchanger in winter P1 / P2 before and after the heat exchanger A rising pressure drop indicates frosting – the automation starts defrosting Protect the tubes from condensate freezing

    How to choose the range of a pressure switch

    Switching range / package contents Recommended model
    20–200 Pa, relay only PSW--200 (20–200 Pa)
    20–200 Pa, with PVC connection kit PSW--200-PVC (20–200 Pa, with tubes) ← this model
    50–500 Pa, relay only PSW--500 (50–500 Pa)
    50–500 Pa, with PVC connection kit PSW--500-PVC (50–500 Pa, with tubes)
    Rule: the desired switching point should be closer to the middle of the range: up to ~150 Pa – PSW--200, for higher limits – PSW--500. If nozzles and tubes are not available on site, choose the version with the PVC kit.
    When to choose another solution: version without a connection kit – PSW--200; for smooth pressure measurement with an analog output – HPS-2 / DPS-2 transmitters; for pressure maintenance by a fan – HPSP-2 / DPSP-2 controllers.

    Pros

    • Mechanical, no power supply required
    • Changeover NO / NC contact
    • Adjustable switching point
    • 10 000 000 cycle service life
    • IP54 with cover
    • Nozzles and tubes included

    Cons / limitations

    • Accuracy ≤ ±15 % – not suitable for precise measurement
    • Binary signal only, no analog output
    • With a limit < 50 Pa it must not be mounted upside down
    • Only for air and non-flammable, non-aggressive gases

    Safety and installation notes

    • Installation and connection must be carried out by a qualified electrician with the power disconnected.
    • Contact load – no more than 1.5 (0.4) A / 250 VAC.
    • Do not operate without the cover – without it the protection class is IP00.
    • Max. operating pressure – 10 kPa; for air and non-flammable, non-aggressive gases only.
    • When the switching threshold is below 50 Pa, do not mount upside down.
    • Max. operating temperature of the PVC tubes – 60 °C.

    Quick selection guide

    20–200 Pa
    ΔP 10 Pa
    NO / NC
    250 VAC
    IP54
    Suitable when you need:
    • to monitor filter fouling and fan operation;
    • to interlock the electric heater when there is no airflow;
    • to obtain a simple pressure signal without power supply and programming.
    Check before use:
    • whether the desired switching threshold fits within 20–200 Pa;
    • the contact load (up to 1.5 (0.4) A / 250 VAC);
    • whether connection nozzles and tubes are needed.
    Important reminder: The PSW--200-PVC provides only an on / off signal; for smooth pressure measurement or control, a pressure transmitter or controller is required.

    FAQ

    How is the switching pressure set?
    Graduated knob under the cover.
    Which contact closes as the pressure increases?
    As the pressure difference increases, 3–2 closes and 3–1 opens.
    Where do I connect P1 and P2?
    P1 – to the higher pressure (lower vacuum), P2 – to the lower pressure (higher vacuum).
    Is a power supply needed?
    No, the relay is mechanical.
    Are tubes included in the kit?
    Yes – PSET-PVC nozzles, PVC tubes and screws.
    What load can the contact switch?
    No more than 1.5 (0.4) A at 250 VAC (VDE 0630).