Duct temperature and humidity transmitter | -30…70°C | 0-100%rH | 3×0-10VDC/0-20mA/PWM | Modbus RTU | 18-34VDC | IP54 | Sentera Controls | DSTHF-3
Code: DSTHF-3Offer is valid until 2026-12-31Price 119.29 € VAT incl.( 98.59 € VAT excl. )186.10 €You save 66.81 €Want another price? Suggest yours!-
Duct temperature and humidity transmitter | -30…70°C | 0-100%rH | 3×0-10VDC/0-20mA/PWM | Modbus RTU | 18-34VDC | IP54 | Sentera Controls | DSTHF-3
DSTHF-3 – a Sentera Controls duct temperature and relative humidity transmitter with three analog / modulating outputs and Modbus RTU. It measures -30…+70 °C and 0–100 % rH in the duct and passes the measurements to a controller, BMS or speed controller as 0-10 VDC, 0-20 mA or PWM signals. Supply – 18–34 VDC (4-wire connection).
Key idea:
This is a “measuring” rather than a “deciding” device: it controls nothing itself, but delivers temperature and humidity accurately and stably as separate signals. The control logic stays in the controller or BMS, so the transmitter suits both new projects and the replacement of old sensors in existing automation.Measurement
-30…+70 °C / 0–100 % rHOutputs
3 × 0-10 VDC / 0-20 mA / PWM + Modbus RTUPower supply
18–34 VDCProtection
housing IP54, probe IP20Operating principle
The transmitter is mounted on the duct, and the probe is inserted into the airflow (at least 1 m/s). Connect the supply 18–34 VDC (VIN, GND), analog outputs AO1–AO3 (each with its own GND) and, if needed, Modbus RTU (A, /B); terminals – for wires up to 1.5 mm².
An integrated digital sensor measures temperature and relative humidity: AO1 continuously outputs temperature, AO2 humidity, and AO3 is assigned to either temperature or humidity. The type of each output is selectable – 0-10 VDC (≥ 50 kΩ), 0-20 mA (≤ 500 Ω) or 1 kHz PWM (open collector, 3.3 or 12 VDC); all parameters are changed over Modbus RTU, which is also used to update the firmware.
Result – the controller or BMS receives accurate (±0.4 °C, ±3 % rH) supply or extract air data and uses it to control fans, humidifiers, heaters or dampers; duct measurement is the most reliable indicator for heat recovery unit or humidification control.
Benefits DSTHF-3?
One transmitter replaces two separate sensors: temperature and humidity are delivered as separate signals, with a third configurable output and Modbus RTU in addition, so the same device suits both analog and digital automation.Technical specifications
Product type Duct temperature and humidity transmitter Manufacturer / code Sentera Controls / DSTHF-3 Series DSTHX-3 (DSTHF-3 / DSTHG-3) Measured quantities Temperature, relative humidity Temperature range -30…+70 °C Humidity range 0–100 % rH, non-condensing Accuracy ±0.4 °C (-30…+70 °C); ±3 % rH (0–100 %) Analog outputs AO1 – temperature, AO2 – humidity, AO3 – temperature or humidity (selectable) Output signals 0-10 VDC (RL ≥ 50 kΩ); 0-20 mA (RL ≤ 500 Ω); PWM 1 kHz, open collector, 3.3 or 12 VDC (RL ≥ 50 kΩ) Communication Modbus RTU (RS485), terminals A, /B; firmware update via Modbus RTU Supply voltage 18–34 VDC Max. current (Imax) 80 mA Connection 4-wire, separate supply and output grounds (-F) Terminals For wires up to 1.5 mm² Min. air velocity 1 m/s Protection class IP54 housing, IP20 probe tube (EN 60529) Operating conditions -30…+70 °C, 0–100 % rH non-condensing Weight 0.15 kg (net) Compliance LVD 2014/35/EU, EMC 2014/30/EU, WEEE 2012/19/EU, RoHS 2011/65/EU Manufacturer documentation
✔ Recommended by Elektrotechnikos sprendimaiOriginal manufacturer documentation – technical data, wiring diagrams and installation instructions.
Main functions
- Three analog outputs – temperature and humidity are passed on separately, the third output is freely assignable.
- Selectable signal type – 0-10 VDC, 0-20 mA or PWM – suitable for most controller, BMS and speed controller inputs.
- Modbus RTU – all measurements and settings are accessible over a digital link; it can be used with Modbus only or together with the analog outputs.
- Firmware update – over the Modbus RTU network, without removing the transmitter.
- Duct probe – measures directly in the airflow – in a supply, extract or outdoor air duct.
- Configuration – Configuration and monitoring – the free Sentera 3SModbus software (via the CNVT-USB-RS485 converter) or the Sensistant Modbus configurator.
Where is it used?
- Supply and extract air ducts in ventilation units
- Automation of heat recovery units and air handling units
- Control of humidification and dehumidification systems
- Extraction ducts of swimming pools, warehouses and production areas
- BMS / SCADA systems with Modbus RTU
- Replacing old duct sensors in existing automation
On-demand operation
For air handling unit automation designers.
Three separate signals and Modbus RTU in a single duct transmitter reduce the number of sensor items in the specification.For the assembler of 24 VDC control panels.
The -F version is wired with 4 wires with separate supply and output grounds, so the analog signal stays stable on long lines.For the existing HVAC automation modernizer.
A single transmitter replaces two old duct sensors, and the signal type is selected to match the existing controller input.Practical application
If a heat recovery unit controller needs supply air temperature and humidity as 0-10 VDC signals and the panel has a 24 VDC power supply, then the DSTHF-3 is wired with 4 wires: AO1 – temperature -30…+70 °C, AO2 – 0–100 % rH, and AO3 can duplicate humidity for the humidifier controller.Application guide: how it is used in practice
The same DSTHF-3 adapts to different sites – only what is connected to its outputs changes:
Site What is connected Result Installer's note Air handling unit with a controller AO1 (T) and AO2 (rH) → controller analog inputs The controller sees the supply air temperature and humidity and uses them to control a heater or humidifier Install where the airflow is ≥ 1 m/s and uniform Extraction from humid rooms AO2 (rH) → EC fan 0-10 VDC input or speed controller Extraction increases as the extract air humidity rises Insert the probe into the extract duct upstream of the fan Building with BMS Modbus RTU → A, /B Temperature and humidity are displayed and archived in the BMS without analog cables A separate Modbus address for each device Modernization of existing automation AO1 / AO2 0-20 mA → in place of an old sensor Two old transmitters are replaced by one, keeping the controller inputs Select the signal type according to the controller input Panel with a 24 VDC power supply VIN, GND ← 18–34 VDC; separate AO GND Separate grounds – stable analog signal on long lines Not suitable for 3-wire systems and AC power How to choose a duct temperature and humidity transmitter
Installation / output / power supply Recommended model Duct, 3 analog outputs (T / rH / T or rH), 18–34 VDC, 4 wires DSTHF-3 (duct transmitter, -F) ← this model Duct, 3 analog outputs, 18–34 VDC or 15–24 VAC, 3 wires DSTHG-3 (duct transmitter, -G) Duct, Modbus RTU only, Power over Modbus (PoM), RJ45 DSTHM-2 (duct Modbus transmitter) Duct, direct fan / damper control with 1 output, 18–34 VDC DCTHF-2 (smart duct sensor, -F) Duct, direct control with 1 output, 18–34 VDC or 15–24 VAC DCTHG-2 (smart duct sensor, -G) Duct, control signal via Modbus RTU, PoM, RJ45 DCTHM-2 (smart duct sensor, PoM) Rule: first decide where the measurement is made (duct, room, outdoors), then what you need from the transmitter: separate analog signals for a controller (transmitter, 3 outputs), data only to a BMS (Modbus / PoM version), or direct fan control with a single output (smart sensor). Finally – the supply and number of wires: -F – 24 VDC, 4-wire, separate grounds; -G – AC or DC, 3-wire, common ground; -M / -H – power over the Modbus cable (RJ45).When to choose another solution: for power over the Modbus cable – DSTHM-2; for direct control of an EC fan or damper with a single signal – smart DCTH-2 series sensors; for a room – RSTH-3 series; when CO2 is also needed – RSMF-3 / DSCDG series.Pros
- Three analog outputs + Modbus RTU
- Selectable signal 0-10 VDC / 0-20 mA / PWM
- Accuracy ±0.4 °C, ±3 % rH
- Firmware is updated via Modbus
- Wide range -30…+70 °C, 0–100 % rH
- IP54 housing
Cons / limitations
- It does not control the fan according to a setting by itself – a controller or a smart DCTH / RCTH sensor is required
- IP20 probe – do not install where water or condensate can get into the duct
- An airflow of at least 1 m/s is required
- The -F version is not suitable for 3-wire systems or AC supply
Safety and installation notes
- Installation and connection are to be carried out by a qualified electrician / automation specialist with the power disconnected.
- Supply voltage – 18–34 VDC; must not be exceeded.
- The -F version: 4-wire connection, separate supply and analog output grounds – not suitable for 3-wire systems and must never be connected to an alternating current (AC) supply.
- Do not mix -F and -G type products on the same network.
- Install the probe in the airflow, away from humidifier nozzles and condensation zones.
Quick selection guide
-30…+70 °C0–100 % rH3 × 0-10 VDC / 0-20 mA / PWMModbus RTU18–34 VDCIP54Suitable when you need:- to measure temperature and humidity in a duct and pass them to a controller as separate signals;
- to integrate measurements into a BMS via Modbus RTU;
- to replace old separate temperature and humidity sensors with a single device.
Check before use:- the controller input type (0-10 VDC, 0-20 mA or PWM);
- the supply voltage and the number of wires (-F – 4-wire DC, -G – 3-wire AC/DC);
- whether the airflow in the duct is not less than 1 m/s.
Important reminder: The DSTHF-3 is a measuring transmitter: it passes on data but does not itself control the fan according to a setpoint.FAQ
Which signals can be obtained?
Each of the three outputs – 0-10 VDC, 0-20 mA or 1 kHz PWM, plus Modbus RTU.What is AO3 for?
It can be assigned to temperature or humidity, for example for a second controller or indicator.How does it differ from DSTHG-3?
The -F version is powered at 18–34 VDC and wired with 4 wires with separate grounds, while -G is powered at 18–34 VDC or 15–24 VAC and wired with 3 wires with a common ground.Can it be connected via Modbus only?
Yes, analog outputs do not have to be used, and if power over the Modbus cable is needed – choose the DSTHM-2.How do I reset the Modbus settings?
With a jumper on PROG contacts 1 and 2 for at least 5 seconds.What airflow is needed?
At least 1 m/s.Duct temperature and humidity transmitter | -30…70°C | 0-100%rH | 3×0-10VDC/0-20mA/PWM | Modbus RTU | 18-34VDC | IP54 | Sentera Controls | DSTHF-3
Sentera DSTHF-3 – duct temperature and humidity transmitter: -30…+70 °C, 0–100 % rH, three 0-10 VDC / 0-20 mA / PWM outputs and Modbus RTU, 18–34 VDC supply. Suitable for ventilation, humidification and BMS automation.
Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.ManufacturerThis product is marked with the CE label, which confirms that it complies with all applicable European Union directives and regulations. CE marking is not just a formality – it is an important indicator of quality and safety, ensuring that the product has been properly assessed, tested, and can be safely used throughout the EU market.
CE certification means that the product has been evaluated according to the main criteria:
Safety requirements – ensures that the product does not pose a risk to the user or the environment
Electromagnetic compatibility (EMC) – the device does not interfere with other equipment and is resistant to external disturbances
Environmental standards – complies with current ecological and material usage requirements
Operational reliability – the product is suitable for long-term use according to its intended purposeCE marking allows this product to:
be legally supplied and used in all European Union countries
ensure a high level of quality and safety
be used in residential, commercial, and industrial environmentsThe CE mark is a declaration of the manufacturer’s responsibility, confirming that the product complies with all applicable standards and has been assessed according to EU legislation.
What does this mean for you as a buyer?
Safe use in everyday activities
Reliable performance and reduced risk of failure
Compliance with EU standards and requirements
Suitability for professional solutions
Love it? Share your thoughts in a review!Write Review