    Code: 211801

    3-pole modular miniature circuit breaker (MCB) designed for the protection of electrical circuits against overloads and short circuits. Thanks to its high rated current, C characteristic, and up to 20kA breaking capacity, this circuit breaker is ideal for industrial, commercial, and higher-power electrical distribution applications.

    The device complies with strict international standards and ensures reliable protection of the electrical network even under demanding operating conditions. The compact modular housing allows easy installation on a standard DIN rail in electrical distribution boards. 

  • Technical Specifications

    Manufacturer: Eaton
    Product type: Miniature Circuit Breaker (MCB)
    Number of poles: 3P
    Rated current (In): 80A
    Tripping characteristic: C
    Rated operational voltage (Ue): 230/400V AC
    Maximum operational voltage: 400V AC
    Rated insulation voltage (Ui): 440V
    Rated impulse withstand voltage (Uimp): 4kV
    Frequency: 50–60Hz
    Rated short-circuit breaking capacity: 20kA
    Mounting: 35mm DIN rail
    Standards: IEC/EN 60947-2
    Protection function: overload and short-circuit protection
    Application: protection of electrical distribution and power circuits

    Functions

    Overload protection – automatically disconnects the circuit when the current exceeds the permissible limit and may damage cables or equipment.
    Short-circuit protection – quickly interrupts the power supply during a fault, protecting the installation and connected equipment.
    Three-phase protection (3P) – simultaneously protects all three phases, ensuring safe operation of three-phase electrical systems.
    C characteristic – suitable for circuits with moderate inrush currents, such as electric motors, pumps, and fans.
    High 20kA breaking capacity – suitable for facilities where high short-circuit currents may occur, such as factories, industrial facilities, substations, or high-power distribution boards.
    DIN rail mounting – ensures quick and convenient installation in electrical distribution boards.
    Manual switching ON and OFF – can be used not only for protection but also for circuit isolation during maintenance.

    Applications

    For homeowners: Suitable for protecting three-phase electrical circuits in private houses, garages, workshops, and outbuildings. Commonly used for three-phase sockets, electric heating equipment, compressors, and other high-power devices.

    For electricians: Used for assembling electrical panels, installing new electrical systems, and replacing existing circuit breakers. A reliable choice for protecting three-phase lines and power circuits.

    For electrical engineers: Suitable for designing electrical distribution systems in residential, commercial, and industrial facilities. Can be used for protecting three-phase loads, technological equipment, and power supply lines.

    For industrial and commercial facilities: Designed for protecting electric motors, pumps, ventilation systems, compressors, manufacturing equipment, and other three-phase loads against overloads and short circuits.

    For panel builders: Suitable for assembling new distribution, control, and automation panels where reliable protection of three-phase circuits according to IEC/EN 60898-1 is required.

    Advantages
    Three-phase protection in one device
    High 20kA short-circuit breaking capacity
    Easy DIN rail installation
    Suitable for residential, workshop, commercial, and industrial applications
    Disadvantages
    Additional RCCB or RCBO device is required for residual current protection
    Not suitable for extremely high short-circuit currents
    Not designed for voltage monitoring – does not protect against voltage fluctuations, overvoltages, or phase loss
    Frequently Asked Questions
    Does this circuit breaker provide residual current protection?

    No, this is a standard MCB circuit breaker that protects against overloads and short circuits. An RCCB or RCBO device is additionally required for residual current protection.

    Where is this circuit breaker most commonly used?

    This model is most commonly used for protecting three-phase electrical lines, electric motors, pumps, ventilation systems, commercial facilities, and industrial equipment.

    What does the C characteristic mean?

    C characteristic circuit breakers trip at approximately 5–10 times their rated current. They are ideal for circuits with moderate inrush currents, such as motors, pumps, and fans.

    Can this circuit breaker be used in a residential building?

    Yes, it is suitable for protecting three-phase circuits in private houses, garages, workshops, and auxiliary buildings. 