Modular switch-disconnector for generators (selector switch 1-0-2) | 4P | 63A | 230/400V AC | AC-22 | IEC 60947-3 | DIN | IP20 | Promfactor Baltic | FSD24063
Code: FSD24063Price 18.17 € VAT incl.( 15.02 € VAT excl. )Promfactor Baltic FSD24063 – modular 4P 63 A selector switch 1-0-2 for generators, 230/400 V AC, AC-22, IEC 60947-3; safely transfers the load between mains and generator.
-
Modular switch-disconnector for generators (selector switch 1-0-2) | 4P | 63A | 230/400V AC | AC-22 | IEC 60947-3 | DIN | IP20 | Promfactor Baltic | FSD24063
FSD24063 – a Promfactor Baltic FSD2 series four-pole modular load changeover switch with positions 1-0-2, rated current 63 A, voltage 230/400 V AC, 50/60 Hz, utilisation category AC-22. Designed to switch a load between two power sources – e.g. the distribution grid and a generator; complies with IEC 60947-3, mounted on a 35 mm DIN rail, IP20.
Key idea:
A manual selector switch with a centre 0 position ensures that the load is never connected to the mains and the generator at the same time: from position 1 (mains) to 2 (generator) the switch passes only through 0, when all four poles – L1, L2, L3 and N – are disconnected. This way the generator does not energise the grid and the mains voltage does not reach the generator.Rated current
63 APoles / positions
4P, 1-0-2Voltage / category
230/400 V AC, AC-22Standard
IEC 60947-3, DIN, IP20Operating principle
The selector switch is mounted on a 35 × 7.5 mm DIN rail in the control panel between the two sources and the load: the mains incomer (1) is connected to one set of terminals, the generator output (2) to the other, and the common terminals supply the load control panel. Cables up to 16 mm², tightening torque 0.8 Nm.
The knob selects the position: 1 – the load is supplied from the first source, 0 – all four poles disconnected, 2 – the load is supplied from the second source. Since both the phases and the neutral are switched, the sources remain completely separated. Category AC-22 allows switching mixed resistive and slightly inductive loads up to 63 A.
Result – safe manual backup power changeover: when the mains fails, the operator transfers the load to the generator, and when the mains returns – back again, with no risk of connecting the sources to each other.
Benefits FSD24063?
A compact DIN modular 4P 63 A selector switch with a mandatory 0 position – a simple and inexpensive solution for connecting a generator in a house or small facility control panel, with no need for two switch-disconnectors with an interlock.Technical specifications
Product type Modular load selector switch (switch-disconnector) 1-0-2 Manufacturer / code Promfactor Baltic / FSD24063 Series FSD2 (1P, 2P, 3P, 4P; 16–63 A; 1-0-2) Number of poles 4 Positions 1-0-2 Rated current (In) 63 A Rated voltage (Un) 230/400 V AC Frequency 50/60 Hz Utilization category AC-22 Insulation voltage (Ui) 500 V Impulse voltage (Uimp) 6000 V Terminals for cable up to 16 mm²; tightening torque 0.8 Nm Endurance, electrical / mechanical 4000 / 20 000 cycles Installation 35 × 7.5 mm DIN rail Degree of protection IP20 Operating temperature -22…+55 °C Storage temperature -25…+70 °C Standard IEC 60947-3 Main functions
- Changeover between two sources – the load is supplied from the mains (1) or the generator (2) with a single movement of the knob.
- Centre position 0 – the sources are never interconnected, and the load can be completely disconnected.
- 4 poles – all three phases and the neutral are switched – the sources are completely separated.
- 63 A, AC-22 – suitable for switching mixed resistive and slightly inductive loads up to 63 A.
- Isolation for maintenance – in position 0, the load control panel is disconnected from both sources.
- DIN mounting – fits into a standard modular control panel next to circuit breakers.
Where is it used?
- Detached house panels with a backup generator
- Farms and livestock facilities – supplying livestock equipment during a mains failure
- Rural guesthouses, allotments and summer houses
- Small offices, shops and workshops with backup power
- Construction site control panels with mains and generator incomers
- Pumping stations and boiler rooms that require backup power
- Dual-supply panels where the load is switched between two lines
On-demand operation
For electricians in houses and homesteads.
The 4P 63 A 1-0-2 changeover switch allows a portable or stationary three-phase generator to be safely connected to a house panel.For farm and livestock facility owners.
when the mains fails, a single turn of the knob through the 0 position transfers the load to the generator, and when the mains returns – back again.For control panel assemblers.
the modular 4P selector switch is mounted on a DIN rail together with circuit breakers, so no separate enclosure or two switch-disconnectors with an interlock are needed.Practical application
If a house's 3 × 400 V incomer is protected up to 63 A and a backup three-phase generator needs to be connected, then FSD24063 is mounted in the panel: the mains is connected to position 1 and the generator to 2, and when switching via 0 all four poles (L1–L3 and N) are disconnected, so the sources are never connected together.Application guide: how it is used in practice
FSD24063 adapts to different sites – only the sources connected to positions 1 and 2 change:
Site What is connected Result Installer's note Detached house 1 – mains supply after the meter, 2 – generator plug-in inlet Manual changeover to the generator via the 0 position Upstream of the selector switch on the mains side – incomer protection, no more than 63 A Farm / livestock facility 1 – mains, 2 – stationary generator Critical equipment supplied during a mains failure Select the generator power according to the connected load Construction site 1 – temporary mains supply, 2 – mobile generator Quick source changeover without rewiring Install in an enclosed control panel – the selector switch is IP20 Dual-line panel 1 – main line, 2 – backup line The load is switched between two supplies Make sure that the N system of both lines is coordinated How to select an FSD2 1-0-2 changeover switch
Poles, current, positions Recommended model 1P, 16 A, 1-0-2 FSD21016 (FSD2 1P 16A 1-0-2) 1P, 20 A, 1-0-2 FSD21020 (FSD2 1P 20A 1-0-2) 1P, 25 A, 1-0-2 FSD21025 (FSD2 1P 25A 1-0-2) 1P, 40 A, 1-0-2 FSD21040 (FSD2 1P 40A 1-0-2) 1P, 50 A, 1-0-2 FSD21050 (FSD2 1P 50A 1-0-2) 1P, 63 A, 1-0-2 FSD21063 (FSD2 1P 63A 1-0-2) 2P, 16 A, 1-0-2 FSD22016 (FSD2 2P 16A 1-0-2) 2P, 20 A, 1-0-2 FSD22020 (FSD2 2P 20A 1-0-2) 2P, 25 A, 1-0-2 FSD22025 (FSD2 2P 25A 1-0-2) 2P, 40 A, 1-0-2 FSD22040 (FSD2 2P 40A 1-0-2) 2P, 50 A, 1-0-2 FSD22050 (FSD2 2P 50A 1-0-2) 2P, 63 A, 1-0-2 FSD22063 (FSD2 2P 63A 1-0-2) 3P, 16 A, 1-0-2 FSD23016 (FSD2 3P 16A 1-0-2) 3P, 20 A, 1-0-2 FSD23020 (FSD2 3P 20A 1-0-2) 3P, 25 A, 1-0-2 FSD23025 (FSD2 3P 25A 1-0-2) 3P, 40 A, 1-0-2 FSD23040 (FSD2 3P 40A 1-0-2) 3P, 50 A, 1-0-2 FSD23050 (FSD2 3P 50A 1-0-2) 3P, 63 A, 1-0-2 FSD23063 (FSD2 3P 63A 1-0-2) 4P, 16 A, 1-0-2 FSD24016 (FSD2 4P 16A 1-0-2) 4P, 20 A, 1-0-2 FSD24020 (FSD2 4P 20A 1-0-2) 4P, 25 A, 1-0-2 FSD24025 (FSD2 4P 25A 1-0-2) 4P, 40 A, 1-0-2 FSD24040 (FSD2 4P 40A 1-0-2) 4P, 50 A, 1-0-2 FSD24050 (FSD2 4P 50A 1-0-2) 4P, 63 A, 1-0-2 FSD24063 (FSD2 4P 63A 1-0-2) ← this model Rule: choose the number of poles according to the network: 1P – for switching a single phase, 2P – for a single-phase network with N, 3P – for three-phase without N, 4P – for three-phase with N (for generator connection, switching the neutral as well is recommended). The current must be no lower than the rated current of the protection upstream of the selector switch.When to choose another solution: lower currents of the same series – FSD24040 / FSD24050; for three-phase without neutral – FSD23063; for single-phase – FSD22063; for simple isolation (without 1-0-2 changeover) – FSD3 modular switch-disconnector (e.g. FSD34063 in the 1P–4P series); for incomer and line protection – ECO FB1-63 circuit breakers.Pros
- Centre 0 position – the sources are never interconnected
- 4 poles: phases and neutral are switched
- 63 A, AC-22, 230/400 V AC
- Complies with IEC 60947-3
- Mechanical endurance 20,000 cycles
- DIN mounting in a modular enclosure
Cons / limitations
- Manual changeover only – automatic transfer switching (ATS) requires contactors or automation
- No overload or short-circuit protection – circuit breakers are required
- Cables only up to 16 mm²
- IP20 – for closed panels only
Safety and installation notes
- Installation and connection must be carried out only by a qualified electrician after disconnecting both power sources.
- Coordinate the connection of the generator to the building installation with the grid operator's requirements.
- Make sure that the generator and mains incomers are connected to different positions (1 and 2), never in parallel.
- Install protection rated no more than 63 A upstream of the selector switch; tighten the terminals to 0.8 Nm.
- Install only in an enclosed control panel (IP20), operating temperature -22…+55 °C.
Quick selection guide
4P63 A1-0-2AC-22IEC 60947-3DINSuitable when you need:- manually transfer the load between the mains and the generator;
- completely separate the two sources, including the neutral;
- isolate the load control panel for maintenance (position 0).
Check before use:- the incomer protection current – whether it is no higher than 63 A;
- the cable cross-section – whether it fits terminals rated up to 16 mm²;
- whether the neutral must also be switched (4P) or 3P is sufficient.
Important reminder: FSD24063 – a manual changeover switch without overload or short-circuit protection; each source and the load must be protected by circuit breakers.FAQ
What is FSD24063 intended for?
For manually switching a load of up to 63 A between two sources, e.g. mains and generator, via the middle 0 position.How many poles does FSD24063 switch?
Four – three phases and neutral.What is the utilization category?
AC-22, for switching mixed resistive and slightly inductive loads.What cable cross-sections can be connected?
The terminals accept cables up to 16 mm², tightening torque 0.8 Nm.Does the changeover switch protect against short circuits?
No, protection against overload and short circuit requires separate circuit breakers.Who is the manufacturer of FSD24063?
The manufacturer is Promfactor Baltic, FSD2 series.Modular switch-disconnector for generators (selector switch 1-0-2) | 4P | 63A | 230/400V AC | AC-22 | IEC 60947-3 | DIN | IP20 | Promfactor Baltic | FSD24063
Promfactor Baltic FSD24063 – modular switch-disconnector for generators, load selector switch FSD2 4P 63 A 1-0-2, 230/400 V AC, AC-22, IEC 60947-3, for DIN rail – for safe manual changeover between mains and a backup generator.
Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.ManufacturerThis product is marked with the CE label, which confirms that it complies with all applicable European Union directives and regulations. CE marking is not just a formality – it is an important indicator of quality and safety, ensuring that the product has been properly assessed, tested, and can be safely used throughout the EU market.
CE certification means that the product has been evaluated according to the main criteria:
Safety requirements – ensures that the product does not pose a risk to the user or the environment
Electromagnetic compatibility (EMC) – the device does not interfere with other equipment and is resistant to external disturbances
Environmental standards – complies with current ecological and material usage requirements
Operational reliability – the product is suitable for long-term use according to its intended purposeCE marking allows this product to:
be legally supplied and used in all European Union countries
ensure a high level of quality and safety
be used in residential, commercial, and industrial environmentsThe CE mark is a declaration of the manufacturer’s responsibility, confirming that the product complies with all applicable standards and has been assessed according to EU legislation.
What does this mean for you as a buyer?
Safe use in everyday activities
Reliable performance and reduced risk of failure
Compliance with EU standards and requirements
Suitability for professional solutions
Love it? Share your thoughts in a review!Write Review Alternative products