Products catalog

  • Single-phase voltage and current relay | 1F | 1P+N | 63 A | V + A display | 1 module | DIN | TAXNELE | ES-TCVP1-63VA

    Code: ES-TCVP1-63VA

    The TAXNELE ES-TCVP1-63VA is a single-phase digital voltage relay for DIN-rail mounting in a distribution board.

  • Single-phase voltage and current relay | 1F | 1P+N | 63 A | V + A display | 1 module | DIN | TAXNELE | ES-TCVP1-63VA

    The TAXNELE ES-TCVP1-63VA is a single-phase digital voltage relay for DIN-rail mounting in a distribution board. The full load of the protected circuit passes through its contact, so it directly disconnects an apartment, a house circuit or a single appliance. In addition to voltage, it measures the load current and disconnects the circuit when the set limit is exceeded.

    Key point:
    A broken neutral in a three-phase supply or a sustained over- or undervoltage is the most common cause of damage to expensive appliances. A power relay disconnects such voltage before boiler electronics, a fridge or a computer are harmed.
    Load current
    63 A
    Voltage limits
    ~120–300 V
    Network / supply
    1F (1P+N), 220–230 V AC
    Functions
    current limit

    How it works

    The relay is installed after the main circuit breaker: phase and neutral to the input, the protected load to the output. A microcontroller continuously measures the mains voltage and shows it on the display.

    When the voltage leaves the set U> / U< limits, the load is disconnected after the set delay. When the set current limit is exceeded, the load is also disconnected – this limits the power drawn.

    When the parameters return to normal, the load is reconnected after the set delay. For compressors set a delay of at least 3 min.

    Why choose the TAXNELE ES-TCVP1-63VA?
    One power relay protects all appliances connected after it against a broken neutral and voltage fluctuations, without an additional contactor.

    Technical specifications

    Product type Single-phase digital voltage and current relay (power type)
    Manufacturer / code TAXNELE / ES-TCVP1-63VA
    Network 1F (1P+N), 220–230 V AC
    Rated current 63 A
    Measured voltage ~120–300 V
    Display / indication LED (V, A)
    Width (DIN modules) 1 (18 mm)
    Operating temperature −20…+55 °C
    Mounting DIN 35 mm

    Main functions

    • Power relay – the full load passes through the relay, no additional contactor needed.
    • Over- and undervoltage protection – appliances are disconnected when the neutral breaks or the network fails.
    • Current limit – an overloaded circuit is disconnected, the power drawn is limited.
    • Event memory – you see why and when it disconnected.
    • Digital display or indication – the status is visible at once.

    Where is it used?

    • Apartment and house supplies (after the main circuit breaker)
    • Boiler and heat pump electronics
    • Fridges, freezers, air conditioners
    • Country houses with a weak network
    • Offices, servers, security systems
    • Rental properties and unattended sites

    Use by need

    For the home or apartment owner.
    One device protects all appliances against a broken neutral and voltage surges.
    For the electrician.
    Simple installation after the main circuit breaker, limits set with buttons.
    For the country house owner.
    On a weak network the real voltage is visible and equipment does not cycle needlessly.

    Practical use

    A house has a three-phase supply with single-phase equipment distributed among the phases. If the neutral contact burns out, the voltage on one phase rises to 300–380 V – the TAXNELE ES-TCVP1-63VA disconnects the load before the boiler controller and power supplies burn out, and after the neutral is restored the equipment is switched on after the set delay.

    Pros

    • Full load through the relay
    • Adjustable limits and delays
    • Automatic reconnection
    • Compact DIN housing
    • Event memory

    Cons / limitations

    • Does not protect against lightning and short surges – an SPD is needed
    • Does not replace a circuit breaker or RCD
    • Single-phase – a three-phase house needs a relay per phase
    • IP20 – dry board only
    • The manufacturer does not publish a full datasheet – parameters per supplier specification

    Safety and installation notes

    • Install only after disconnecting the supply and checking that no voltage is present; work must be done by a qualified electrician.
    • Upstream – a circuit breaker with a current not higher than the relay's rated current.
    • Do not swap phase and neutral.
    • Install the surge protective device (SPD) before the relay.
    • For compressors set a switch-on delay of at least 3 min.

    Quick selection guide

    1F
    1P+N
    63 A
    V + A display
    1 module
    Suitable when you need:
    • to protect an apartment, house or circuit against a broken neutral
    • to protect a boiler, fridge, electronics
    • to see the mains voltage
    Check before use:
    • main circuit breaker current ≤ 63 A
    • whether a surge protective device (SPD) is installed
    Important reminder: a voltage relay does not replace a surge protective device, a circuit breaker or an RCD.

    FAQ

    Does the relay protect against lightning?
    No – a surge protective device (SPD) protects against lightning impulses.
    What current should I choose?
    The relay's rated current must be at least that of the upstream circuit breaker – the TAXNELE ES-TCVP1-63VA suits a breaker up to 63 A.
    What switch-on delay should I set?
    For compressors at least 3 min; 10–30 s is enough for electronics and lighting.
    Why does the relay trip often?
    Most likely the limits are too narrow for a weak network – measure the mains voltage first.
    Is it suitable for a three-phase house?
    Yes – a relay is installed on each phase supplying the protected equipment, or choose a three-phase relay.
    Does the relay replace an RCD?
    No – only a residual current device (RCD) protects people from electric shock.

    Single-phase voltage and current relay | 1F | 1P+N | 63 A | V + A display | 1 module | DIN | TAXNELE | ES-TCVP1-63VA

    TAXNELE ES-TCVP1-63VA – protection against a broken neutral, overvoltage and undervoltage for a single-phase circuit.

    Published: 2026-11-13 · Data verified against the supplier specification: 2026-11-13

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • Alternative products

    Perforated DIN rail | profile for modular equipment mounting in a distribution cabinet | 35x7.5mm | 15cm
    Code: DR750150

    A perforated DIN rail is a mounting profile designed for quick and reliable installation of modular electrical equipment, such as circuit breakers, residual current relays, power supplies, or automation components, in distribution panels.
    Thanks to the perforations, the rail can be easily mounted with screws directly onto the panel base, ensuring a firm and stable hold of the structure even under vibration or heavier loads. 

    Price 0.52 € VAT incl.
    ( 0.43 € VAT excl. )
    Non-perforated DIN rail | profile | for mounting modular equipment in a distribution board | 35x7mm | 1m | BAKS | EURO | SZB35H 7/1 | 0613310
    Code: 0613310

    BAKS EURO SZB35H 7/1 – a non-perforated steel DIN rail designed for mounting modular electrical and automation equipment in distribution boards and control cabinets. Profile dimensions – 35 × 7 mm, steel thickness – 1.0 mm, length – 1000 mm (1 m). The solid non-perforated base allows mounting points to be selected according to the specific construction; the price is indicated per 1 metre. 

    Price 0.88 € VAT incl.
    ( 0.73 € VAT excl. )
  • Subscribtion to new arrivals

    privacy policy

    Information