    Code: ES-DA-VIP04

    Panel digital ammeter with adjustable current limit and relay output (5 A / 250 V AC). Used with an x/5 A current transformer (ratio settable up to 800/5 A). Supply 150–270 V AC, panel cut-out 91×91 mm.

  • Panel digital ammeter with relay output | no CT, x/5 A up to 800/5 A | 150–270 V AC | 91×91 mm cut-out | ES-DA-VIP04

    A door-mounted ammeter that not only shows current but also monitors a set limit: when it is exceeded, the output relay operates and the ERR indicator lights up. Current is measured through an x/5 A current transformer (selected separately for the line), so the meter suits lines from a few to hundreds of amperes.

    Main idea:
    This is not a circuit breaker but a monitoring device: its 5 A relay drives a contactor coil or an alarm. This lets you shed a less important load before the main breaker trips, or get an overload warning.
    Measurement
    via x/5 A current transformer
    Current transformer
    not included; ratio up to 800/5 A
    Relay output
    5 A / 250 V AC (resistive load)
    Supply / cut-out
    150–270 V AC / 91×91 mm

    Operating principle

    The meter is fitted into a 91×91 mm cut-out in a panel door or control panel and supplied with 150–270 V AC. The current transformer is placed on the monitored phase conductor and its 5 A secondary is wired to the meter terminals.

    Using the buttons (3 s long press) you set the transformer ratio, then the upper current limit. The display shows the primary current in amperes.

    When current exceeds the limit, the output relay switches and the ERR indicator lights. When current falls 0.5 A below the limit, the relay returns automatically. A warning-only mode without relay action is also available.

    What does the DA-VIP04 give you?
    It turns simple current display into a control function: overload is visible at once, and a contactor can automatically disconnect a chosen load – no PLC or separate current relay module needed.

    Technical specifications

    Product type Panel digital ammeter with adjustable limit and relay output
    Manufacturer / model Tense Electronic / DA-VIP04
    Product code ES-DA-VIP04
    Measuring principle Via x/5 A current transformer
    Current transformer Not included; settable ratio 5/5–800/5 A
    Measuring range per CT, up to 800 A
    Accuracy ±2 %
    Display 3-digit LED, ERR indicator
    Output Relay, 5 A / 250 V AC (resistive load)
    Relay reset (hysteresis) When current falls 0.5 A below the limit
    Supply 150–270 V AC, 50/60 Hz
    Power consumption < 4 VA
    Mounting Into a 91×91 mm panel cut-out, front mounting
    Wire connection Plug-in terminals, up to 1.5 mm²
    Operating temperature −20…+55 °C
    Operating altitude up to 2000 m
    Weight up to 300 g

    Key functions

    • Adjustable current limit – you set the trip threshold for the line or equipment.
    • 5 A relay output – drives a contactor coil, signal lamp or siren.
    • Automatic reset – the relay returns by itself when current drops, no manual reset needed.
    • Warning-only mode – can be used as an alarm without disconnecting the load.
    • Settable CT ratio – suitable for 5/5–800/5 A transformers.

    Where is it used?

    • Main and distribution boards with limited supply capacity
    • Compressor, pump and fan lines
    • Generator and inverter outputs – for load limiting
    • Production line and machine tool control panels
    • Heating and boiler power management (load shedding)
    • Farm, warehouse and workshop boards

    Use by need

    For electricians and panel builders.
    A simple way to add current monitoring with automatic load disconnection via a contactor.
    For energy managers and facility staff.
    See the real load and get a signal before the main protection trips.
    For generator or inverter users.
    Limits the load so the source is not overloaded – excess load is disconnected automatically.

    Practical use

    If a site is supplied through a limited-capacity connection and heating, a boiler and machines run at the same time, a DA-VIP04 with the limit set at about 85 % of the main breaker rating will disconnect the heating group via a contactor as the total current approaches the limit, and reconnect it when current drops – the main breaker does not trip.

    Pros

    • Shows current and controls load in one device
    • Adjustable limit and warning mode
    • Automatic relay reset
    • Suits 5/5–800/5 A transformers
    • Compact panel mounting

    Cons / limitations

    • Not a protective device – does not replace a circuit breaker or fuse
    • 5 A relay – a contactor is required for larger loads
    • Monitors one phase – a three-phase load needs three meters or a three-phase relay
    • Shows current only – does not measure voltage, power or energy

    Safety and installation notes

    • Install only with the power off; work must be done by a qualified electrician.
    • Never open the CT secondary while current flows in the primary – short the CT terminals first (dangerous voltage appears).
    • Protect the supply circuit with a separate fuse and disconnect switch.
    • Do not switch loads above 5 A directly through the relay contacts – use a contactor.
    • Do not install in damp locations; terminals must stay inside a closed enclosure.

    Quick selection guide

    x/5 A CT
    CT selected separately
    5 A relay
    150–270 V AC
    91×91 mm cut-out
    Suitable when you need:
    • to see line current and automatically disconnect load via a contactor
    • to limit generator or supply load
    • an overload signal
    Check before use:
    • the CT ratio suits the line (up to 800/5 A)
    • the contactor coil current does not exceed 5 A
    • there is a 91×91 mm space and 150–270 V AC supply in the board
    • one phase is monitored
    Important reminder: the device drives a contactor but does not itself protect against short circuit or overload – a circuit breaker or fuses must remain in the line.

    FAQ

    Does it disconnect the load by itself?
    Not directly – its 5 A relay drives a contactor, and the contactor disconnects the load.
    Does it replace a circuit breaker?
    No, it is a monitoring device; short-circuit and overload protection remain with the breaker or fuses.
    Which current transformer should I use?
    Any x/5 A transformer up to 800/5 A; the ratio is set with the buttons.
    Can it be used for alarm only?
    Yes, there is a warning mode in which only the indication operates, without relay action.
    Does the relay reset by itself?
    Yes, when current falls 0.5 A below the set limit.
    Is it suitable for a three-phase supply?
    One meter monitors one phase; a three-phase supply needs three meters or a three-phase current monitoring relay.

    Panel digital ammeter with relay output | no CT, x/5 A up to 800/5 A | 150–270 V AC | 91×91 mm cut-out | ES-DA-VIP04

    DA-VIP04 is a panel digital ammeter with adjustable current limit and 5 A relay output for x/5 A transformers up to 800/5 A: it shows the load and disconnects it via a contactor when the limit is exceeded.

    Published: 2026-11-06 · Data checked against manufacturer (Tense Electronic) and supplier specification: 2026-11-06

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • Alternative products

  • Subscribtion to new arrivals

    privacy policy

    Information