Panel digital ammeter with relay output | no CT, x/5 A up to 800/5 A | 150–270 V AC | 91×91 mm cut-out | ES-DA-VIP04
Code: ES-DA-VIP04Price 35.07 € VAT incl.( 28.98 € VAT excl. )Panel digital ammeter with adjustable current limit and relay output (5 A / 250 V AC). Used with an x/5 A current transformer (ratio settable up to 800/5 A). Supply 150–270 V AC, panel cut-out 91×91 mm.
-
Panel digital ammeter with relay output | no CT, x/5 A up to 800/5 A | 150–270 V AC | 91×91 mm cut-out | ES-DA-VIP04
A door-mounted ammeter that not only shows current but also monitors a set limit: when it is exceeded, the output relay operates and the ERR indicator lights up. Current is measured through an x/5 A current transformer (selected separately for the line), so the meter suits lines from a few to hundreds of amperes.
Main idea:
This is not a circuit breaker but a monitoring device: its 5 A relay drives a contactor coil or an alarm. This lets you shed a less important load before the main breaker trips, or get an overload warning.Measurement
via x/5 A current transformerCurrent transformer
not included; ratio up to 800/5 ARelay output
5 A / 250 V AC (resistive load)Supply / cut-out
150–270 V AC / 91×91 mmOperating principle
The meter is fitted into a 91×91 mm cut-out in a panel door or control panel and supplied with 150–270 V AC. The current transformer is placed on the monitored phase conductor and its 5 A secondary is wired to the meter terminals.
Using the buttons (3 s long press) you set the transformer ratio, then the upper current limit. The display shows the primary current in amperes.
When current exceeds the limit, the output relay switches and the ERR indicator lights. When current falls 0.5 A below the limit, the relay returns automatically. A warning-only mode without relay action is also available.
What does the DA-VIP04 give you?
It turns simple current display into a control function: overload is visible at once, and a contactor can automatically disconnect a chosen load – no PLC or separate current relay module needed.Technical specifications
Product type Panel digital ammeter with adjustable limit and relay output Manufacturer / model Tense Electronic / DA-VIP04 Product code ES-DA-VIP04 Measuring principle Via x/5 A current transformer Current transformer Not included; settable ratio 5/5–800/5 A Measuring range per CT, up to 800 A Accuracy ±2 % Display 3-digit LED, ERR indicator Output Relay, 5 A / 250 V AC (resistive load) Relay reset (hysteresis) When current falls 0.5 A below the limit Supply 150–270 V AC, 50/60 Hz Power consumption < 4 VA Mounting Into a 91×91 mm panel cut-out, front mounting Wire connection Plug-in terminals, up to 1.5 mm² Operating temperature −20…+55 °C Operating altitude up to 2000 m Weight up to 300 g Key functions
- Adjustable current limit – you set the trip threshold for the line or equipment.
- 5 A relay output – drives a contactor coil, signal lamp or siren.
- Automatic reset – the relay returns by itself when current drops, no manual reset needed.
- Warning-only mode – can be used as an alarm without disconnecting the load.
- Settable CT ratio – suitable for 5/5–800/5 A transformers.
Where is it used?
- Main and distribution boards with limited supply capacity
- Compressor, pump and fan lines
- Generator and inverter outputs – for load limiting
- Production line and machine tool control panels
- Heating and boiler power management (load shedding)
- Farm, warehouse and workshop boards
Use by need
For electricians and panel builders.
A simple way to add current monitoring with automatic load disconnection via a contactor.For energy managers and facility staff.
See the real load and get a signal before the main protection trips.For generator or inverter users.
Limits the load so the source is not overloaded – excess load is disconnected automatically.Practical use
If a site is supplied through a limited-capacity connection and heating, a boiler and machines run at the same time, a DA-VIP04 with the limit set at about 85 % of the main breaker rating will disconnect the heating group via a contactor as the total current approaches the limit, and reconnect it when current drops – the main breaker does not trip.Pros
- Shows current and controls load in one device
- Adjustable limit and warning mode
- Automatic relay reset
- Suits 5/5–800/5 A transformers
- Compact panel mounting
Cons / limitations
- Not a protective device – does not replace a circuit breaker or fuse
- 5 A relay – a contactor is required for larger loads
- Monitors one phase – a three-phase load needs three meters or a three-phase relay
- Shows current only – does not measure voltage, power or energy
Safety and installation notes
- Install only with the power off; work must be done by a qualified electrician.
- Never open the CT secondary while current flows in the primary – short the CT terminals first (dangerous voltage appears).
- Protect the supply circuit with a separate fuse and disconnect switch.
- Do not switch loads above 5 A directly through the relay contacts – use a contactor.
- Do not install in damp locations; terminals must stay inside a closed enclosure.
Quick selection guide
x/5 A CTCT selected separately5 A relay150–270 V AC91×91 mm cut-outSuitable when you need:- to see line current and automatically disconnect load via a contactor
- to limit generator or supply load
- an overload signal
Check before use:- the CT ratio suits the line (up to 800/5 A)
- the contactor coil current does not exceed 5 A
- there is a 91×91 mm space and 150–270 V AC supply in the board
- one phase is monitored
Important reminder: the device drives a contactor but does not itself protect against short circuit or overload – a circuit breaker or fuses must remain in the line.FAQ
Does it disconnect the load by itself?
Not directly – its 5 A relay drives a contactor, and the contactor disconnects the load.Does it replace a circuit breaker?
No, it is a monitoring device; short-circuit and overload protection remain with the breaker or fuses.Which current transformer should I use?
Any x/5 A transformer up to 800/5 A; the ratio is set with the buttons.Can it be used for alarm only?
Yes, there is a warning mode in which only the indication operates, without relay action.Does the relay reset by itself?
Yes, when current falls 0.5 A below the set limit.Is it suitable for a three-phase supply?
One meter monitors one phase; a three-phase supply needs three meters or a three-phase current monitoring relay.Panel digital ammeter with relay output | no CT, x/5 A up to 800/5 A | 150–270 V AC | 91×91 mm cut-out | ES-DA-VIP04
DA-VIP04 is a panel digital ammeter with adjustable current limit and 5 A relay output for x/5 A transformers up to 800/5 A: it shows the load and disconnects it via a contactor when the limit is exceeded.
Published: 2026-11-06 · Data checked against manufacturer (Tense Electronic) and supplier specification: 2026-11-06
Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.This product is marked with the CE label, which confirms that it complies with all applicable European Union directives and regulations. CE marking is not just a formality – it is an important indicator of quality and safety, ensuring that the product has been properly assessed, tested, and can be safely used throughout the EU market.
CE certification means that the product has been evaluated according to the main criteria:
Safety requirements – ensures that the product does not pose a risk to the user or the environment
Electromagnetic compatibility (EMC) – the device does not interfere with other equipment and is resistant to external disturbances
Environmental standards – complies with current ecological and material usage requirements
Operational reliability – the product is suitable for long-term use according to its intended purposeCE marking allows this product to:
be legally supplied and used in all European Union countries
ensure a high level of quality and safety
be used in residential, commercial, and industrial environmentsThe CE mark is a declaration of the manufacturer’s responsibility, confirming that the product complies with all applicable standards and has been assessed according to EU legislation.
What does this mean for you as a buyer?
Safe use in everyday activities
Reliable performance and reduced risk of failure
Compliance with EU standards and requirements
Suitability for professional solutions
Love it? Share your thoughts in a review!Write Review Alternative products