- -9.39€

Passive temperature sensor with stainless steel probe | PT100 | 1m | -20-60°C | Sentera Controls | FLTSN-P100-100
Code: FLTSN-P100-100Offer is valid until 2026-12-31Price 16.76 € VAT incl.( 13.85 € VAT excl. )26.15 €You save 9.39 €Want another price? Suggest yours! -
Passive temperature sensor with stainless steel probe | PT100 | 1m | -20-60°C | Sentera Controls | FLTSN-P100-100
FLTSN-P100-100 – a Sentera Controls passive platinum PT100 temperature sensor: resin-insulated Ø8 mm element in a stainless steel tube with 1 m wires. Intended for measuring temperature in HVAC systems – in thermowells, ducts, on pipes.
Key idea:
A stainless steel probe with 1 m wires – a classic HVAC solution for a controller with a PT100 input: placed in a thermowell or fixed in a duct, with no power supply or settings.Sensing element
PT100 (100 Ω at 0 °C)Wire length
1 mOperating temperature
-20…+60 °CProbe
Stainless steel, Ø8 mmOperating principle
The platinum PT100 element is resin-sealed and housed in a Ø8 mm, 53 mm long stainless steel tube with 1 m 0.5 mm² leads. The probe is inserted into a thermowell or duct, or fixed to a surface, and the leads are connected to the controller's PT100 input (a shielded cable for extension).
Resistance increases with temperature (positive coefficient): 100 Ω at 0 °C. The controller supplies a 0.1–1.0 mA measuring current and calculates the temperature from the resistance.
Result – temperature within -20…+60 °C with F0.3 class accuracy (±0.30 °C at 0 °C … ±0.60 °C at 60 °C), long-term stability < ±0.04 %, insulation resistance > 10 MΩ. The probe has no active output, and hot water circuits above +60 °C require a different solution.
Benefits FLTSN-P100-100?
A stainless steel probe with a standard PT100 element – reliable, compact and suitable for both a thermowell and an air duct.Technical specifications
Product type Passive temperature sensor with wires (platinum resistance, RTD) Manufacturer / code Sentera Controls / FLTSN-P100-100 Series FLTSN-P (PT100 / PT500 / PT1000, stainless steel probe, 1 / 4 m) Sensing element PT100, R0 = 100 Ω at 0 °C Measuring range -20…+60 °C Accuracy class F0.3: ±0.30 °C at 0 °C … ±0.60 °C at 60 °C; R0 tolerance ±0.30 % Measuring current (DC) 0.1–1.0 mA Self-heating ≤ 0.8 K/mW Long-term stability < ±0.04 % Insulation resistance > 10 MΩ Probe Stainless steel, Ø8 mm, 53 mm; resin-insulated element Wires 1 m, 0.5 mm²; use shielded cable for extension Operating environment -20…+60 °C, < 95 % rH non-condensing Weight 0.04 kg (net, 1 pc.) Compliance LVD 2006/95/EC, EMC 2004/108/EC (EN 61326), WEEE 2012/19/EU, RoHS (EU) 2015/863 Manufacturer documentation
✔ Recommended by Elektrotechnikos sprendimaiOriginal manufacturer documentation – technical data, wiring diagrams and installation instructions.
Main functions
- Platinum PT100 element – standardized characteristic, no calibration needed.
- Stainless steel probe Ø8 mm – sturdy, suitable for a thermowell and damp environments.
- Resin-insulated element – long-term stability < ±0.04 %.
- Accuracy class F0.3 – ±0.30 °C at 0 °C … ±0.60 °C at 60 °C.
- Insulation resistance > 10 MΩ – reliable measurement without leakage into the enclosure.
- Self-heating ≤ 0.8 K/mW – the measuring current practically does not distort the readings.
- 1 m wires – can be extended with a shielded cable.
Where is it used?
- Heating and cooling pipework up to +60 °C (with thermowell)
- Hot water tanks and heat substations up to +60 °C
- Water heater coil circuits of ventilation units
- Underfloor heating circuits
- Control cabinets and technical rooms
- BMS temperature monitoring
- Replacing existing PT100 probes in thermowells
On-demand operation
For heat substation service engineers.
The PT100 stainless steel probe replaces an old sensor of the same type in a thermowell without reprogramming the controller.For industrial controller integrators.
The PT100 per IEC 60751 connects to a standard RTD input without a converter.For designers.
The Ø8 mm probe suits standard thermowells, and the F0.3 class is sufficient for HVAC control.Practical application
If the existing PT100 sensor in a thermowell in a heat substation has failed, then the FLTSN-P100-100 (Ø8 mm, 53 mm) is inserted into the same thermowell and the controller continues to measure temperature without any settings changes.Application guide: how it is used in practice
FLTSN-P100-100 is a universal probe with cable; it can be placed in a thermowell, fixed in a duct or in a room:
Site What is connected Result Installer's note Heating substation, tank FLTSN-P100-100 in a thermowell → controller PT100 input The controller regulates according to water temperature Use thermally conductive paste in the thermowell Air handling unit chamber FLTSN-P100-100 in the airflow → controller Supply or outdoor air temperature measurement Secure the wire so that it is not strained Heating circuit FLTSN-P100-100 on the pipe surface → controller Return water temperature control Insulate the sensor location so that the readings are not reduced BMS modernization The existing PT100 probe is replaced with FLTSN-P100-100 Same characteristic – no need to change settings Check the controller's input type How to choose a sensing element and cable length
Sensing element / probe / cable Recommended model PT100, stainless steel probe, 1 m FLTSN-P100-100 (PT100, 1 m) ← this model PT500, stainless steel probe, 1 m FLTSN-P500-100 (PT500, 1 m) PT500, stainless steel probe, 4 m FLTSN-P500-400 (PT500, 4 m) PT1000, stainless steel probe, 1 m FLTSN-P1K0-100 (PT1000, 1 m) PT1000, stainless steel probe, 4 m FLTSN-P1K0-400 (PT1000, 4 m) PT500, ABS probe, IP65, 1 m FLTSN-P500P100 (PT500, 1 m) PT500, ABS probe, IP65, 4 m FLTSN-P500P400 (PT500, 4 m) PT500, ABS probe, IP65, 8 m FLTSN-P500P800 (PT500, 8 m) PT500, ABS probe, IP65, 16 m FLTSN-P500P1K6 (PT500, 16 m) PT1000, ABS probe, IP65, 1 m FLTSN-P1K0P100 (PT1000, 1 m) NTC 3 kΩ (25 °C), 1 m FLTSN-N3K3A1-100 (NTC, 1 m) NTC 10 kΩ (25 °C), 1 m FLTSN-N1K4A1-100 (NTC, 1 m) Rule: the sensing element (PT100 / PT500 / PT1000 / NTC) must match the controller input, and for NTC – also its resistance characteristic. Choose a cable length that avoids splices; for extension use only a shielded cable.When to choose another solution: for a room – ROTSN series (wall-mounted housing); for a duct – TUTSN series (150 / 250 mm); when the controller accepts only Modbus RTU – DTS-M (duct) or DTP-M (strap-on).Pros
- No power supply or settings needed
- Standard PT100 characteristic
- Sturdy stainless steel probe
- Suitable for a thermowell, duct or surface
- Long-term stability < ±0.04 %
- Accuracy class F0.3
Cons / limitations
- No 0-10 VDC or Modbus output – a controller with a PT100 input is required; for a Modbus pipe sensor choose DTP-M
- Operating range -20…+60 °C – not suitable for hotter media
- The thermowell is not included in the kit
- IP rating not specified in the datasheet – outdoors it is more reliable to use the IP65 FLTSN-PxxxP series
Safety and installation notes
- Installation and connection are to be carried out by a qualified installer.
- For extension use only a shielded cable, routed separately from 230 V lines.
- Do not exceed the operating temperature of -20…+60 °C and < 95 % rH non-condensing.
Quick selection guide
PT1001 mStainless steelPassive-20…+60 °CSuitable when you need:- to measure temperature for a controller with a PT100 input;
- to install a sensor in a thermowell, duct or on a surface;
- to replace an old probe of the same type.
Check before use:- the controller input type (PT100);
- the required cable length;
- the medium temperature – whether it does not exceed +60 °C.
Important reminder: FLTSN-P100-100 is a passive sensor; it works only with a controller that has a PT100 input.FAQ
Is a power supply needed?
No, it is a passive resistive sensor, and the measuring current is supplied by the controller.What size is the probe?
The probe is Ø8 mm in diameter and 53 mm long, made of stainless steel.Can the wires be extended?
Yes, extend the standard 1 m leads with a shielded cable.What is the operating temperature range?
The sensor operates within -20…+60 °C.Is the thermowell included in the kit?
No, the thermowell must be purchased separately to suit the Ø8 mm probe.How does it differ from FLTSN-P500P100?
The FLTSN-P series has a stainless steel probe, while the FLTSN-PxxxP has an ABS probe with IP65 and a shielded cable of up to 16 m.Passive temperature sensor with stainless steel probe | PT100 | 1m | -20-60°C | Sentera Controls | FLTSN-P100-100
Sentera FLTSN-P100-100 – passive PT100 temperature sensor with a Ø8 mm stainless steel probe and 1 m leads, accuracy class F0.3 for HVAC controllers and BMS.
Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.ManufacturerThis product is marked with the CE label, which confirms that it complies with all applicable European Union directives and regulations. CE marking is not just a formality – it is an important indicator of quality and safety, ensuring that the product has been properly assessed, tested, and can be safely used throughout the EU market.
CE certification means that the product has been evaluated according to the main criteria:
Safety requirements – ensures that the product does not pose a risk to the user or the environment
Electromagnetic compatibility (EMC) – the device does not interfere with other equipment and is resistant to external disturbances
Environmental standards – complies with current ecological and material usage requirements
Operational reliability – the product is suitable for long-term use according to its intended purposeCE marking allows this product to:
be legally supplied and used in all European Union countries
ensure a high level of quality and safety
be used in residential, commercial, and industrial environmentsThe CE mark is a declaration of the manufacturer’s responsibility, confirming that the product complies with all applicable standards and has been assessed according to EU legislation.
What does this mean for you as a buyer?
Safe use in everyday activities
Reliable performance and reduced risk of failure
Compliance with EU standards and requirements
Suitability for professional solutions
Love it? Share your thoughts in a review!Write Review

