Products catalog

  • Transformer temperature-controlled fan speed controller with valve output | 2.5A | 230VAC | 5-35°C | surface-mounted | IP54 | Sentera Controls | GTH-1-25L22

    Code: GTH-1-25L22
    Barcode: 5401003017494
    Price 364.40 € VAT incl.
    ( 301.16 € VAT excl. )
    568.47 € You save 204.07 €
    Offer is valid until 2026-12-31

    Temperature-controlled transformer speed controller – a reliable and long-lasting solution for controlling the speed of single-phase AC fans according to ambient temperature. The device is intended for heating and ventilation systems where it is necessary to ensure an optimal microclimate, reduce energy consumption, and extend the service life of fans.

    The controller operates on the autotransformer principle, ensuring stable, quiet, and motor-safe speed adjustment. It can control one or several fans with a total current not exceeding 2.5 A, and additionally control an external heating or cooling valve. 

  • Transformer temperature-controlled fan speed controller with valve output | 2.5A | 230VAC | 5-35°C | surface-mounted | IP54 | Sentera Controls | GTH-1-25L22

    GTH-1-25L22 – a Sentera Controls temperature-controlled transformer fan speed controller for motors fed with single-phase 230 VAC up to 2.5 A. It has a 7-position selector switch (off, 5 manual steps, automatic mode), a temperature setting of 5–35 °C and an unregulated 230 VAC output for a hot water valve.

    Key idea:
    A simple controller for a water air heater or ventilation fan: based on the temperature of the PT500 sensor it switches the fan speed steps and activates the valve, and the sinusoidal transformer voltage ensures quiet motor operation even at the lowest step. This model is intended for smaller fans and air heaters – up to 2.5 A total motor current.
    Max. motor current
    2.5 A
    Steps
    80 / 110 / 140 / 170 / 230 VAC
    Control
    Based on temperature 5–35 °C
    Protection
    IP54, surface mounting

    Operating principle

    The controller is wall-mounted via the integrated external plate (4 holes Ø6 mm). Connect the 230 VAC power supply (L, N, PE), the motor (U1, U2), the hot water valve to the unregulated output (Lout, N) and the external PT500 sensor (T1; not included); the circuit is protected by a T4 A-H (5×20 mm) fuse.

    The autotransformer with taps supplies the motor with fixed sinusoidal voltages: a 7-position knob selects 0 (off), 80, 110, 140, 170, 230 VAC or automatic mode (the 190 VAC tap exists but is not connected). In automatic mode the speed is switched in steps according to temperature around the setpoint (5–35 °C, proportional band 2 °C), and Lout supplies 230 VAC in heating mode when the temperature is below the setpoint, and the opposite in cooling mode (jumper P7 1–2 removed).

    Result – the fan and the water valve are controlled from a single temperature setpoint, and the sinusoidal voltage ensures quiet motor operation even at low speed, including for motors that hum or overheat with an electronic controller. Engineer's note: control is stepped, so after commissioning check that the motor starts reliably on the 80 VAC step.

    Benefits GTH-1-25L22?
    Fan speed and hot water valve from a single temperature setting – no separate thermostat, with quiet sinusoidal motor operation.

    Technical specifications

    Product type Temperature-based transformer fan speed controller
    Manufacturer / code Sentera Controls / GTH-1-25L22
    Series GTH-1 (2.5 / 5 A)
    Supply voltage 230 VAC, 50–60 Hz
    Max. motor current 2.5 A
    Energy consumption 65 W
    Output voltage steps 0 – 80 – 110 – 140 – 170 – (190) – 230 VAC (the 190 VAC tap is present but not connected)
    Output voltage waveform Sinusoidal (autotransformer)
    Modes 7-position rotary switch: off, 5 manual steps, automatic
    Valve output (Lout) Unregulated 0 / 230 VAC based on temperature (for a hot water valve)
    Operating logic Heating / cooling – jumper P7 (1–2) on the board
    Temperature setpoint 5–35 °C, potentiometer
    Proportional band 2 °C
    Temperature sensor External PT500 (not included), terminal T1
    Fuse T4 A-H (5×20 mm)
    Housing ABS, UL94-V0, grey RAL 7035
    Installation On a wall, integrated external plate, 4 holes Ø6 mm
    Protection class IP54 (EN 60529), for indoor use only
    Operating environment -10…+35 °C, < 95 % rH non-condensing
    Packaging dimensions 341×256×156 mm
    Weight 5.2 kg net / 6.8 kg gross
    Compliance LVD 2014/35/EU (EN 60335-1), EMC 2014/30/EU (EN 61000-6-2, EN 61000-6-3), WEEE 2012/19/EU, RoHS

    Manufacturer documentation

    ✔ Recommended by Elektrotechnikos sprendimai

    Original manufacturer documentation – technical data, wiring diagrams and installation instructions.

    Main functions

    • Speed according to temperature – automatic step control around the set temperature (proportional band 2 °C).
    • Hot water valve output – 230 VAC switched on / off according to temperature.
    • Heating / cooling logic – selectable with jumper P7 on the board.
    • Manual mode – 5 steps (80 / 110 / 140 / 170 / 230 VAC) and the off position.
    • Sinusoidal output voltage – quiet motor operation at all steps.
    • Easy installation – integrated plate for wall mounting.

    Where is it used?

    • Warehouses, workshops and production premises with water air heaters
    • Greenhouses
    • Farm buildings
    • Ventilation systems with a single-phase AC fan where quiet operation is important
    • Small workshops and garages with a single air heater (up to 2.5 A)
    • Service bays with a water-based air heater

    On-demand operation

    For heating and ventilation installers.
    The fan and valve of a single water air heater are controlled from a single temperature setpoint.
    For the workshop and garage owner.
    A simple knob: automatic mode or a fixed speed set by hand.
    For the electrician replacing a humming electronic controller.
    Sinusoidal voltage eliminates low-speed humming in motors up to 2.5 A.

    Practical application

    If a workshop has a single water-based air heater whose fan current does not exceed 2.5 A, then the GTH-1-25L22 in automatic mode switches the fan steps according to the PT500 temperature (setting 5–35 °C, proportional band 2 °C), and when the set temperature is reached, the Lout output closes the hot water valve.

    Application guide: how it is used in practice

    Typical GTH-1-25L22 applications:

    Site What is connected Result Installer's note
    Warehouse with a water air heater Heater fan → U1, U2; valve → Lout; PT500 → T1 Cold – the valve is open, the fan runs; when the set temperature is reached, the valve closes Heating mode – jumper P7 (1–2) fitted
    Greenhouse ventilation Fan → U1, U2; PT500 → in the plant zone As the temperature rises, the fan speeds up in steps Cooling mode – remove jumper P7
    Room where silence is important Fan → U1, U2; knob – step 1 or 2 The fan runs slowly and quietly on sinusoidal voltage Check that the motor starts reliably at the 80 VAC step
    Farm building Multiple fans of the same type → U1, U2 The set temperature is maintained Total motor current – up to 2.5 A

    How to select the controller current

    Rated current of the motor(s) Recommended model
    up to 2.5 A GTH-1-25L22 (2.5 A) ← this model
    2.5–5 A GTH-1-50L22 (5 A)
    5–7.5 A (with Modbus RTU) GTH21-75L22 (7.5 A)
    7.5–10 A (with Modbus RTU) GTH21100L22 (10 A)
    Rule: controller max. current ≥ rated current of the motor (or the sum of several motors) from the motor nameplate. For a transformer controller the motor starting current is already taken into account by the manufacturer, so no additional margin is needed. Connect several fans only with AC motors of the same type that are voltage-controllable.
    When to choose another solution: for a different current – GTH-1-50L22 (5 A); for higher current and Modbus RTU / SenteraWeb – GTH21 series (7.5 / 10 A); for an electric heater – GTTE1 series; fan only with an integrated sensor – GTT-1 series; smooth electronic temperature control – GTE series.

    Pros

    • Sinusoidal output voltage – quiet operation
    • Hot water valve output 230 VAC
    • Heating / cooling logic
    • Automatic and manual 5-step mode
    • Temperature setting 5–35 °C
    • IP54 enclosure

    Cons / limitations

    • Stepped, not smooth control – for smooth control use the GTE series
    • PT500 sensor not included
    • The valve is controlled by on / off only (230 VAC), not 0-10 VDC
    • No Modbus RTU – for that choose the GTH21 series
    • Heavy (5.2 kg); only for single-phase AC motors, not suitable for EC fans

    Safety and installation notes

    • Installation and connection must be carried out by a qualified electrician with the power disconnected.
    • Always connect the protective earth (PE).
    • The total rated current of the connected motors must not exceed 2.5 A.
    • Replace the fuse only with one of the same type: T4 A-H (5×20 mm).
    • For indoor use only, in clean air without aggressive or flammable gases; operating environment -10…+35 °C.

    Quick selection guide

    2.5 A
    230 VAC
    5–35 °C
    Valve output
    IP54
    Suitable when you need:
    • for controlling a water air heater with a fan up to 2.5 A;
    • for fan speed by temperature in heating or cooling mode;
    • for sites where quiet motor operation at low speed is important.
    Check before use:
    • the motor rated current and whether it is voltage-controllable;
    • the valve actuator type (230 VAC on / off);
    • whether you have a PT500 sensor;
    • the ambient temperature (-10…+35 °C).
    Important reminder: The GTH-1-25L22 does not control EC fans, three-phase motors and 0-10 VDC valves; the PT500 sensor is purchased separately.

    FAQ

    What are the step voltages?
    1 – 80 VAC, 2 – 110 VAC, 3 – 140 VAC, 4 – 170 VAC, 5 – 230 VAC; the 190 VAC tap is present but not connected.
    Is the sensor included?
    No, an external PT500 sensor is required, connected to terminal T1.
    How is the water valve controlled?
    With the unregulated 230 VAC output: in heating mode it switches on when the temperature is below the setpoint and switches off when it is exceeded.
    How do I switch to cooling mode?
    Remove the jumper between pins 1–2 of connector P7 on the board.
    Can it be connected to a BMS?
    No, the GTH-1 has no Modbus; the GTH21 series is intended for that.
    How does it differ from GTH-1-50L22?
    The GTH-1-50L22 is for motors up to 5 A and has a T8 A-H fuse, with the same functions.

    Transformer temperature-controlled fan speed controller with valve output | 2.5A | 230VAC | 5-35°C | surface-mounted | IP54 | Sentera Controls | GTH-1-25L22

    Sentera GTH-1-25L22 – transformer temperature-controlled fan speed controller, up to 2.5 A, 230 VAC, 5 steps 80–230 VAC, hot water valve output, setpoint 5–35 °C, IP54 – for water air heaters and ventilation.

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • Alternative products

  • Subscribtion to new arrivals

    privacy policy

    Information