  • Three-phase transformer fan speed controller | 400 V | 7 A | 5 steps | IP44 | Ventmatika TGRT 7

    Code: TGRT7

    Ventmatika TGRT 7 – 5-step transformer speed controller for three-phase 400 V fan motors up to 7 A, with TK motor protection, 230 V damper output and IP44 enclosure.

  • Three-phase transformer fan speed controller | 400 V | 7 A | 5 steps | IP44 | Ventmatika TGRT 7

    Ventmatika TGRT 7 is a three-phase five-step speed controller for voltage-controllable 400 V fan motors up to 7 A. Speed is changed by an autotransformer: the lower the output voltage, the slower the fan runs. It is a proven, simple solution for supply and exhaust ventilation systems.

    Key idea:
    A transformer controller has no electronics that cause motor hum or mains interference. The motor receives a sinusoidal voltage, so it runs quietly at every step. The fan is also protected via the motor thermal contacts (TK): if the motor overheats it is switched off, and automatic restart is blocked.
    Supply
    400 V / 50 Hz, 3~
    Max. current
    7.0 A
    Steps
    5: 130 / 170 / 220 / 270 / 400 V
    Protection
    IP44, TK motor protection

    Operating principle

    The controller is wall-mounted next to the fan or in a plant room. It is supplied with three-phase 400 V, and the fan motor is connected to the controller output.

    Inside is a three-phase autotransformer, fully impregnated with resin (insulation class F, 155 °C). The step switch selects one of five fixed output voltages: 130, 170, 220, 270 or 400 V. Motor speed drops together with the voltage.

    The motor thermal contacts (TK) are connected to the controller. If the motor overheats, the supply is disconnected and stays locked until service staff reset it. The operating state is shown by an LED. There is also a 230 V / 0.5 A output for controlling an air damper actuator.

    Why choose the TGRT 7?
    One unit controls the speed of a three-phase fan, protects the motor from overheating and controls the air damper at the same time. No separate motor protection relay or extra damper control circuit is needed.

    Technical specifications

    Product type Three-phase transformer fan speed controller
    Manufacturer UAB „Ventmatika“ (Lithuania)
    Model TGRT 7
    Supply voltage 400 V / 50 Hz, 3 phases
    Maximum current 7.0 A
    Output voltage steps 130 V / 170 V / 220 V / 270 V / 400 V
    Control method Autotransformer, manual 5-step switch
    Transformer Fully resin-impregnated, insulation class F (155 °C)
    Motor protection Via motor thermal contacts (TK), with locked restart
    Additional output For damper actuator: 230 V / 50 Hz, 0.5 A
    Indication LED voltage indication
    Protection class IP44
    Enclosure Steel, powder coated
    Max. ambient temperature +40 °C
    Marking CE

    Main functions

    • 5 fixed speed steps – air volume is easy to set to the room’s needs and to repeat exactly.
    • Sinusoidal output voltage – the motor does not hum or overheat from control, and there is no high-frequency interference in the mains.
    • TK protection with lock-out – an overheated motor does not restart by itself, so the windings do not burn out.
    • 230 V damper actuator output – the air damper opens and closes together with the fan.
    • LED indication – you can see at once whether the controller is energised.
    • Resin-impregnated class F autotransformer – long service life and quieter operation.

    Where is it used?

    • Supply and exhaust ventilation systems with three-phase fans
    • Duct and roof fans (400 V, up to 7 A)
    • Production halls and warehouses
    • Car workshops, paint and welding rooms
    • Pig, cattle and poultry houses, greenhouses
    • Kitchen hood exhaust fans
    • Sports halls, retail and public premises
    • As a replacement for a worn or faulty controller of the same type

    Use by need

    For ventilation installers.
    They get a speed controller, motor protection and damper control in one enclosure. Installation is simpler and fewer devices are needed in the panel.
    For building operators.
    A faulty controller is easily replaced with the same model: wiring and steps stay the same, so the system does not need re-commissioning.
    For farmers.
    In a barn or greenhouse, the fan runs as much as needed and is protected from overheating.

    Practical use

    If a production hall has a three-phase exhaust fan with a 5.5 A rated current and TK contacts, the TGRT 7 lets it run on the 170–220 V step in winter so heat is not blown out, and on the 400 V step in summer. The 230 V air damper opens and closes at the same time. If the motor overheats it is switched off and stays off until an electrician checks it.

    Pros

    • Quiet operation – sinusoidal voltage
    • Motor TK protection with lock-out
    • 230 V damper actuator output
    • IP44 enclosure – suitable for plant rooms
    • Simple, durable design without electronics
    • Made in Lithuania, CE marked

    Cons / limitations

    • Step control only, not stepless
    • Not suitable for EC motors or single-phase 230 V motors
    • Max. current 7 A – for larger motors choose a bigger TGRT model
    • No 0–10 V input for automatic control – for automation choose a frequency inverter

    Safety and installation notes

    • Installation and connection must be done by a qualified electrician with the power off.
    • Before connecting, check that the motor manufacturer allows voltage speed control.
    • The motor rated current must not exceed 7.0 A.
    • See the manufacturer’s manual for how to connect the TK. Do not bypass the protection without reason.
    • The controller warms up – install it where air circulates freely and the ambient temperature does not exceed +40 °C.
    • Install a protective device in the supply circuit according to the motor current.

    Quick selection guide

    400 V 3~
    up to 7.0 A
    5 steps
    TK protection
    IP44
    Suitable when you need:
    • manual speed control of a three-phase 400 V fan;
    • motor protection via TK without a separate relay;
    • control of a 230 V air damper together with the fan.
    Check before use:
    • the motor rated current (≤ 7.0 A);
    • whether the motor allows voltage speed control;
    • whether the motor has TK contacts.
    Important reminder: The TGRT 7 does not replace short-circuit protection of the supply line and is not a frequency inverter for stepless or automatic control.

    FAQ

    Is the TGRT 7 suitable for a single-phase fan?
    No, it is designed for three-phase 400 V motors. TGRV series controllers are used for single-phase motors.
    What are the output voltages?
    Five steps: 130, 170, 220, 270 and 400 V.
    What is the largest motor that can be connected?
    A motor with a rated current of no more than 7.0 A.
    What happens when the TK protection trips?
    The motor is disconnected and restart stays locked until service staff reset it.
    Can it control an air damper?
    Yes, there is a 230 V / 0.5 A output for the damper actuator.
    Can it be installed outdoors?
    The enclosure is IP44, so installation indoors or under a canopy, where the ambient temperature does not exceed +40 °C, is recommended.

    Ventmatika TGRT 7 – three-phase speed controller 400 V / 7 A

    Five-step transformer fan speed controller for three-phase 400 V motors up to 7 A, with TK motor protection, 230 V damper output and IP44 enclosure. Designed for ventilation systems, production, agricultural and public premises.

    Published: 2026-11-17 · Data verified against the manufacturer’s catalogue: 2026-11-17

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • privacy policy

    Information