  • Selection guide · flexible connection cable

    BVV-LL cables: where they are suitable, where they are not, and how to select the cross-section

    BVV-LL is a soft, easily flexible cable intended for connecting appliances and luminaires. Its strength is flexibility; its limitation is the 300/300 V rated voltage and light PVC sheath. This guide will help you select the number of cores, cross-section and length, and avoid using it where a different cable is required.

    29
    sizes and colours in the range
    2–7
    cores: L, N, PE, control
    0,75–2,5 mm²
    copper conductor cross-section
    300/300 V
    rated voltage U₀/U
    Class 5
    flexible stranded conductors
    KibirkštisFazėQuestion from Kibirkštis – a young electrician who is not afraid to ask. Answer from Fazė – an experienced engineer.
    Key point:
    Choose BVV-LL when the cable needs to flex: from a socket or junction box to an appliance, luminaire, extension lead or control panel. The correct cable is determined by number of cores (whether PE is required and how many controlled circuits are needed), cross-section (load current) and length (voltage drop). A fixed line in a wall and three-phase 400 V supply require another cable – see the voltage section.
    Information and selectionSuitable / benefit⚠ Check⚡ Safety and mistakes

    What do you need? Quick selection

    Situation Solution Where to find it
    Table lamp, night light, small electronics (Class II) 2×0,75–1 mm² – when the appliance does not require PE 2×1
    Pendant luminaire, luminaire with metal housing 3G1 mm² (L, N, PE) 3G1 white · black
    Extension lead, power strip up to 16 A 3G1,5 mm²; for longer lengths – 3G2.5 3G1,5 · 3G2,5
    Higher-power single-phase appliance: heater, kettle, compressor 230 V 3G2,5 mm² 3G2.5 black · white
    Fan with separate control, luminaire with 2 circuits (L, L', N, PE) 4G1 / 4G1,5 mm² – 230 V only 4G1 · 4G1,5
    Blinds, damper actuators, control panel (several commands) 5G0,75 / 5G1 mm² – 230 V and lower only 5G0,75 · 5G1
    Multiple control lines in one sheath: alarm, control panel, machine control 7G1 / 7G1,5 mm² 7G1 · 7G1,5
    Three-phase 400 V appliance, portable equipment Not BVV-LL → H05VV-F (300/500 V) or rubber cable H05VV-F group
    Fixed line in a wall, under plaster, in the ground Not BVV-LL → NYM-J or CYKY-L NYM-J · CYKY-L
    Why it is worth choosing correctly from the start: the correct BVV-LL cross-section does not overheat under prolonged load, the flexible cable does not break near the plug or appliance inlet, and the correct number of cores allows PE to be connected – keeping a metal enclosure safe. We cut exactly the number of metres you need, so you do not pay for a reel you will not use.

    Complete range in one matrix

    Click the colour – the product page with manufacturer data (diameter, bending radius) will open. All sizes are sold by the metre.

    Cores \ mm² 0,75 1 1,5 2,5 Typical application
    2 cores –
    2×1
    2×1,5
    2×2,5
    L, N – without PE (for Class II appliances)
    3 cores –
    3G1
    3G1,5
    3G2,5
    L, N, PE – single-phase appliances, extension leads
    4 cores –
    4G1
    4G1,5
    4G2,5
    L, L', N, PE – two controlled outputs, 230 V
    5 cores
    5G0,75
    5G1
    5G1,5
    5G2,5
    Several control lines + N, PE, 230 V
    7 cores –
    7G1
    7G1,5
    – Multicore control, signals

    A green cell means the size is available in the range. “G” indicates that one core is green-yellow (PE); “×” means without a PE core. Need another colour or a larger quantity for a project? Contact us – we will prepare an offer.

    Where BVV-LL is suitable – and where it is not

    ✓ Appliance connection
    From a plug or junction box to a household appliance, tool or fan. The flexible Class 5 conductor withstands movement well.
    ✓ Luminaires
    For pendant and wall luminaires, internal luminaire wiring and furniture lighting (within the temperature limit).
    ✓ Extension leads and power strips
    3G1.5 or 3G2.5 cable with plug and socket – indoors, for medium loads.
    ✓ Control circuits
    4G–7G – for blinds, dampers, control panels and alarm systems when the circuits operate at 230 V or lower.
    ⚠ Outdoors, on construction sites
    The light PVC sheath is not intended for prolonged UV exposure, cold or severe mechanical stress. For outdoor work use a rubber cable (H07RN-F).
    ✗ Fixed installation in a wall
    Use NYM-J or CYKY-L under plaster, in walls and in the ground. BVV-LL is only for the connection from a box or socket to the appliance.
    ✗ Three-phase 400 V
    Voltage between phases is 400 V, while the BVV-LL rated voltage U is 300 V. For a three-phase appliance use a 300/500 V or higher-rated cable.
    ✗ Hot locations
    The PVC conductor insulation is intended for up to +70 °C. Near heating elements and halogen lamps use heat-resistant wires.

    300/300 V: why BVV-LL is not suitable for three-phase 400 V

    Cable rated voltage is written as U₀/U: U₀ is the voltage between conductor and earth, U is the voltage between two conductors. In a single-phase 230 V system both values are 230 V, so BVV-LL (300/300 V) is suitable. In a three-phase system there is 400 V between phases – this exceeds U = 300 V even if the cable has 5 cores.

    BVV-LL U₀/U = 300/300 V →230 V between L and N
    ≤ 300 V ✓
    230 V between L and PE
    ≤ 300 V ✓
    400 V between L1 and L2
    > 300 V ✗
    ⚡ Important: 4G and 5G BVV-LL cables are intended for several controlled outputs on the same phase (e.g. blinds up / down, fan speeds), not for three-phase supply. For a portable three-phase appliance choose H05VV-F 5G (300/500 V) or a rubber cable; for fixed installation – CYKY-L.
    Kibirkštis
    KibirkštisThe tool is three-phase and I already have 5G1.5 BVV-LL. Surely there are enough cores?
    Fazė
    FazėThere are enough cores, but not enough insulation rating. There is 400 V between phases, while this cable is tested and intended for 300 V between conductors. Use H05VV-F 5G1.5 or a rubber cable.

    How many cores are required: 2, 3, 4, 5 or 7?

    2 cores – without PE
    L and N only. Suitable for Class II (double-insulated ⧈) appliances. Not suitable for metal enclosures or socket outlets.
    3G – standard
    L, N and PE (green-yellow). For most appliances, luminaires and extension leads.
    4G – two outputs
    L and L' (e.g. two luminaire modes, fan speed) + N + PE, 230 V.
    5G / 7G – control
    Several control or signal lines in one sheath. Not for three-phase 400 V supply.

    Core colours according to HD 308: brown / black / grey – phases and controlled outputs, blue – neutral N, green-yellow – protective PE only. Never use the green-yellow core for another function.

    Cross-section according to load current and power

    Indicative maximum continuous load for a flexible PVC cable at +30 °C ambient temperature, cable freely in air and two loaded conductors (single-phase appliance). Power calculated at 230 V, cos φ = 1.

    mm² Indicative current Protection (typical) Power at 230 V Typical use
    0,75 6 A 6 A ≈ 1,4 kW Luminaires, small electronics, control
    1 10 A 10 A ≈ 2,3 kW Luminaires, fans, control
    1,5 16 A 16 A ≈ 3,7 kW Extension leads, most household appliances
    2,5 20–25 A 16–20 A ≈ 3,7–4,6 kW Heaters, higher-power appliances, longer extension leads
    ⚠ Table values are indicative and may contain inaccuracies. The final cross-section and protection must be selected by a qualified electrician according to manufacturer data, installation conditions and applicable regulations. UAB “Elektrotechnikos sprendimai” is not responsible for calculation errors or inaccuracies.
    ⚠ Reduce the load when: the cable is wound on a reel (an unwound cable heats much less), installed in a bundle with other cables, in thermal insulation or at a higher temperature, or when more than 2 cores are loaded. Rule: IB ≤ In ≤ Iz – load current ≤ protective device current ≤ permissible cable current.

    Length and voltage drop

    In a long flexible cable, part of the voltage is “lost”: a heater produces less heat and a motor starts with more difficulty. The table shows the indicative maximum length for a 230 V circuit when voltage drop does not exceed 3% or 5% (copper, ρ ≈ 0.0225 Ω·mm²/m).

    mm² Load Up to 3% (6.9 V) Up to 5% (11.5 V)
    0,75 6 A ≈ 19 m ≈ 32 m
    1 10 A ≈ 15 m ≈ 25 m
    1,5 10 A ≈ 23 m ≈ 38 m
    1,5 16 A ≈ 14 m ≈ 24 m
    2,5 16 A ≈ 24 m ≈ 40 m
    2,5 20 A ≈ 19 m ≈ 32 m
    How to calculate: ΔU = 2 · L · I · ρ / S.
    Example: extension lead 3G1.5, 25 m, 2 kW heater (≈ 8.7 A) → ΔU ≈ 2 × 25 × 8.7 × 0.0225 / 1.5 ≈ 6.5 V (≈ 2.8%). The same heater over 40 m – ≈ 4.5%, so for a longer run 3G2.5 is advisable.
    ⚠ Table values are indicative and may contain inaccuracies. The final cross-section and protection must be selected by a qualified electrician according to manufacturer data, installation conditions and applicable regulations. UAB “Elektrotechnikos sprendimai” is not responsible for calculation errors or inaccuracies.

    Construction and technical data

    Product type Flexible round copper cable BVV-LL (also designated OMY on the market)
    Manufacturer AB “Lietkabelis” (data – on product pages)
    Conductors Stranded annealed copper conductors, flexibility Class 5
    Insulation / sheath PVC conductor insulation and PVC sheath; white or black
    Number of cores and cross-section 2×1–2,5; 3G1–2,5; 4G1–2,5; 5G0,75–2,5; 7G1–1,5 mm²
    Rated voltage U₀/U 300/300 V – for single-phase 230 V and control circuits
    Conductor temperature In operation −30…+70 °C (manufacturer data); short circuit – according to manufacturer conditions
    Installation temperature −5…+40 °C – PVC hardens in the cold and may crack
    Bending radius More than 5 × cable diameter (e.g. 3G2.5: Ø 7.94 mm → > 39.7 mm)
    Reaction to fire Eca according to manufacturer data – this is not fire resistance
    Sale By the metre – we cut the required length

    BVV-LL or another cable?

    Cable When to choose Limitation
    BVV-LL (this group) Connecting appliances, luminaires and extension leads indoors; control circuits 300/300 V, light sheath
    BVV-PLL Same application, flat – when the cable needs to lie flat Only 2 cores, 300/300 V
    H03VV-F, H05VV-F Harmonised EU designation; H05VV-F 300/500 V – also for three-phase appliances Light to medium loads, indoors
    NYM-J Fixed indoor installation in walls Solid conductor – unsuitable for moving connections
    CYKY-L Fixed circuits, three-phase supply, outdoors and in the ground Rigid, for non-moving connections
    NHXMH-J Where halogen-free cables are required Fixed installation

    ⚠ What to check before buying

    Kibirkštis
    KibirkštisBefore buying, I check these points – and I do not need to come back a second time.
    What to check Why How
    Voltage BVV-LL – 300/300 V 230 V and lower only; 400 V → H05VV-F or CYKY-L
    PE core A metal enclosure must be earthed For a Class I appliance – 3G, 4G, 5G or 7G
    Load The cable must not overheat Appliance power (kW) → current (A) → cross-section in the table
    Length Voltage drop Entire run + allowance for connection; for long runs use a larger cross-section
    Location PVC sheath limitations Indoors; outdoors and on construction sites – rubber cable
    Colour Visible cable White – for interiors, black – for equipment and workshops

    ✗ Common mistakes and their consequences

    ✗ Mistake Consequence ✓ Correct solution
    5G BVV-LL used for a three-phase 400 V appliance The insulation is stressed above its rated voltage, ages faster and the risk of breakdown increases H05VV-F 5G (300/500 V) or rubber cable
    BVV-LL embedded in a wall as a fixed circuit Not intended for this use; difficult to protect, and replacement requires opening the wall In a wall – NYM-J or CYKY-L; BVV-LL – from the box to the appliance
    2×1 mm² for a metal luminaire Enclosure not earthed – electric shock hazard in case of a fault 3G1 mm² with PE
    3G1 mm² extension lead protected by 16 A Cable overheats; the protection does not protect it adequately 3G1.5 mm² or 3G2.5 mm²
    Heater connected through a cable reel that is not fully unwound Cable heats up and insulation melts Fully unwind the reel or use a shorter cable
    ⚡ Green-yellow core used as a phase conductor Voltage on the enclosure – lethal hazard Green-yellow – PE only, always

    ⚡ Safe installation – Phase’s advice

    Fazė
    FazėFlexible cables most often fail where they bend the most – near the plug and the appliance. Protect these areas.
    • Disconnect the power before work and verify absence of voltage.
    • Secure the cable sheath in the strain relief of the plug or appliance – the conductors must not be subjected to tension.
    • Crimp ferrules onto stranded conductor ends – loose strands may cause a short circuit.
    • Leave the PE conductor slightly longer – if the cable is pulled out, it should disconnect last.
    • Use a 30 mA residual-current device (RCD) for extension leads and appliances.
    • Replace a damaged sheath instead of wrapping it with insulating tape.
    • Fixed connections must be carried out by a qualified electrician.

    ☝ Elsprendimai.eu recommends

    Diagram: flexible cable – wrong and correct

    Kibirkštis
    KibirkštisI have a leftover reel of 5G1.5 BVV-LL. Can I use it to connect a three-phase tool or embed it in a wall?
    Fazė
    FazėNo and no. Look at the diagram – four mistakes I see most often and how to correct them.
    BVV-LL: where mistakes are common and how it should be doneSchematic diagram – selecting flexible cable for appliances, extension leads and three-phase equipment.✗ WRONG – common incorrect practice✓ CORRECT – how it should be1Three-phase 400 V5G BVV-LL 300/300 VTool 3~2Wall (under plaster)BVV-LL embeddedSocket316 A socket3G1 reel, not unwoundHeater4Socket2×1 without PEMetal luminaire1Three-phase 400 VH05VV-F 5G 300/500 VTool 3~2Wall: NYM-JBVV-LL from the boxAppliance316 A socket3G1.5 unwound, RCDHeater4Socket3G1 with PEMetal luminaireheats up1400 V between phases exceeds U = 300 V1300/500 V cable for three-phase equipment2Flexible cable used as a fixed circuit2In the wall use NYM-J; BVV-LL only up to the appliance3Reel overheats; 1 mm² is too small for 16 A protection31.5 mm² corresponds to 16 A, reel unwound4No PE – enclosure not earthed43G: PE connected to the enclosureKibirkštisFazė⚠ The diagram is for guidance and may contain inaccuracies. Before installation, verify against the manufacturer’s instructions and applicable regulations.Installation is the responsibility of the qualified electrician carrying out the work. UAB “Elektrotechnikos sprendimai” is not responsible for installation or possible errors.

    Diagram. BVV-LL selection – four common mistakes and the correct solutions

    ☝ Click the diagram to open an enlarged version.
    ⚠ The diagram is for guidance and may contain inaccuracies. Before installation, verify against the manufacturer’s instructions and applicable regulations.
    Installation is the responsibility of the qualified electrician carrying out the work. UAB “Elektrotechnikos sprendimai” is not responsible for installation or possible errors.

    Why – explanation by diagram number

    1Three-phase equipment
    ✗ 5G BVV-LL (300/300 V) on 400 V
    ✓ H05VV-F 5G (300/500 V), rubber cable, or CYKY-L for fixed installation
    Why: Rated voltage U indicates the voltage between two conductors for which the insulation is designed and tested. In a three-phase TN system there is 400 V between phases (230 V × √3). 400 V > 300 V, so the number of cores does not change the issue – the insulation voltage rating is insufficient.
    2Fixed circuit
    ✗ Flexible BVV-LL embedded in a wall
    ✓ In the wall – NYM-J or CYKY-L; BVV-LL only from the box or socket to the appliance
    Why: BVV-LL is intended by manufacturers for appliance connection (portable and stationary appliances). The light PVC sheath is not intended for plaster, mechanical pressure or prolonged service inside a wall; installation cables with the appropriate construction are made for that purpose.
    3Extension lead and load
    ✗ 3G1 mm² reel with 16 A protection, not unwound
    ✓ 3G1.5 mm² (16 A) or 3G2.5 mm², reel unwound, RCD 30 mA
    Why: The protective device must disconnect before the cable overheats: IB ≤ In ≤ Iz. For a 1 mm² flexible cable, indicative Iz ≈ 10 A for a 1 mm² flexible cable, so a 16 A circuit breaker does not protect it. A coiled cable cannot dissipate heat – its permissible current is significantly lower than when unwound.
    4Metal luminaire
    ✗ 2×1 mm² without PE
    ✓ 3G1 mm², green-yellow conductor connected to the enclosure PE terminal
    Why: Protection against electric shock for a Class I appliance relies on earthing the enclosure: if insulation fails, fault current flows through PE and the protective device (circuit breaker or RCD) disconnects the circuit. Without a PE conductor, the enclosure can remain live.

    FAQ

    Question from Kibirkštis, answer from Fazė.

    Kibirkštis
    KibirkštisHow does BVV-LL differ from H05VV-F?
    Fazė
    FazėBoth are flexible and PVC-insulated. BVV-LL (OMY) is rated 300/300 V, H05VV-F is 300/500 V, so H05VV-F is also suitable for three-phase 400 V appliances.
    Kibirkštis
    KibirkštisCan BVV-LL be used outdoors?
    Fazė
    FazėFor short-term use – yes, but for prolonged outdoor use, cold conditions and construction sites the PVC sheath is too light. Use H07RN-F rubber cable there.
    Kibirkštis
    KibirkštisWhich cable is suitable for an extension lead?
    Fazė
    FazėUsually 3G1.5 mm² up to 16 A. For lengths over about 25 m or powerful heaters – 3G2.5 mm².
    Kibirkštis
    KibirkštisCan it be installed under plaster?
    Fazė
    FazėNo. Use NYM-J or CYKY-L in walls and under plaster. BVV-LL is for the connection from a box or socket to the appliance.
    Kibirkštis
    KibirkštisWhen are 2 cores sufficient?
    Fazė
    FazėWhen the appliance is Class II (double insulation, symbol ⧈) and does not require PE. For metal luminaires and socket outlets use 3G only.
    Kibirkštis
    KibirkštisDo you sell by the metre?
    Fazė
    FazėYes, all 29 sizes and colours are sold by the metre. We can prepare an offer for projects and larger quantities.

    Sources

    • AB “Lietkabelis” BVV-LL data on product pages (voltage, conductor class, diameter, temperatures, bending radius) – checked 2026-10-14.
    • OMY 300/300 V cable technical data sheet (application, Class 5 conductors, 300/300 V) – Technokabel, checked 2026-10-14.
    • H03VV-F / OMY technical data sheet (EN 50525-2-11, bending radius 5 × Ø, −30…+70 °C) – checked 2026-10-14.
    • Load values are indicative, based on current-carrying capacity practice for flexible cables (VDE 0298-4); conductor colours – HD 308.

    Get an offer for BVV-LL cables

    Flexible BVV-LL cables with 2–7 cores, 0.75–2.5 mm², white or black sheath. We cut by the metre, help select the cross-section according to load and length, and can supply matching plugs and socket outlets.

    ☎ +370 620 72733✉ info@elsprendimai.eu
    Read more
    Copper cable 3x2.5mm² | flexible | round | BVV-LL 3G2.5 | 1m | black
    Code: 91532502 (1m)

    • The cables are used in residential premises for connecting medium-power household appliances (e.g., washing machines, refrigerators). Suitable for household use, including damp rooms.
    • The conductor is made of stranded thin annealed copper wires, making it very flexible. The insulated cores are twisted together and covered with a PVC sheath, making it convenient to use. 