  • Contactor | 1NO | 3P | 4kW | 9A | 24-60VAC/20-60VDC | ABB | AF09Z-30-10-21 | 1SBL136001R2110

    Code: 1SBL136001R2110
  • Contactor | 1NO | 3P | 4kW | 9A | 24-60VAC/20-60VDC | ABB | AF09Z-30-10-21 | 1SBL136001R2110

    ABB AF09Z-30-10-21 is a 3-pole power contactor for switching three-phase motors and other loads. In AC-3 utilization category it switches 9 A / 4 kW at 400 V, is operated by a 24–60 V 50/60 Hz / 20–60 V DC coil; auxiliary contacts: 1NO.

    Key idea:
    A contactor is a remotely controlled switch: when the coil is energized, the three main contacts close the load circuit. AF09Z-30-10-21 is designed for direct-on-line motor starting and for controlling pumps, fans and heating circuits; the coil can be driven directly from PLC outputs. The contactor itself does not protect against overload or short circuit – an overload relay or motor protection circuit breaker is required for that.
    AC-3 / 400 V
    9 A · 4 kW
    AC-1 (40 °C)
    25 A
    Coil
    24–60 V AC / 20–60 V DC
    Auxiliary contacts
    1NO

    Operating principle

    The contactor is mounted in the panel on a 35 mm DIN rail or screwed to the mounting plate. Supply is connected to terminals 1/L1–5/L3, the load to 2/T1–6/T3, and coil A1–A2 to the control circuit (push buttons, relays, PLC).

    When 24–60 V AC / 20–60 V DC is applied to the coil, the electromagnet pulls in the armature and closes the three main contacts. The auxiliary contacts (1NO) change over at the same time – they are used for self-holding, interlocking and status feedback to the controller.

    When the coil supply is removed, springs open the contacts and the load is switched off. Combined with a ABB TF overload relay, the contactor forms a complete direct-on-line starter.

    Why choose AF09Z-30-10-21?
    Clear manufacturer data according to IEC/EN 60947-4-1: AC-3 9 A / 4 kW and AC-1 25 A, so it is easy to select by motor power or resistive load. The ABB AF series offers widely available accessories – auxiliary contact blocks, overload relays, mechanical interlocks.

    Technical specifications

    Product type Power contactor, 3-pole
    Manufacturer ABB
    Series AF
    Model AF09Z-30-10-21
    Main contacts 3 NO
    AC-3 current / power (400 V) 9 A / 4 kW
    AC-1 current (up to 690 V, 40 °C) 25 A
    Rated operational voltage Ue 690 V
    Coil voltage 24–60 V 50/60 Hz / 20–60 V DC
    Auxiliary contacts 1NO
    Connection Screw terminals
    Degree of protection IP20
    Mounting 35 mm DIN rail or screws
    Standard IEC/EN 60947-4-1

    Main functions

    • Three-phase load switching – a motor up to 4 kW (400 V, AC-3) is controlled by one device.
    • Remote control – the coil is switched by push buttons, timers, thermostats or a PLC.
    • Auxiliary contacts 1NO – for self-holding, interlocks and status signal.
    • Resistive load up to 25 A (AC-1) – for heaters and other non-inductive loads.
    • Compatible with TF overload relays – forms a complete starter.
    • Electronic coil with surge protection – direct control from PLC outputs, overvoltage suppression.

    Where is it used?

    • Direct-on-line motor starting circuits
    • Pumping stations and water supply systems
    • Ventilation and air conditioning units
    • Electric heating circuits
    • Automation and control panels
    • Production lines and machine tools
    • Compressor and conveyor control

    Use by need

    For panel builders.
    A standard, well-documented device that is easy to combine with TF relays and accessories.
    For electricians and maintenance engineers.
    A direct replacement for a failed AF contactor without rebuilding the panel.
    For automation integrators.
    The 20–60 V DC coil is driven directly from a PLC output.

    Practical use

    If a 4 kW pump has to be controlled in a 400 V network, AF09Z-30-10-21 is connected together with a TF overload relay selected for the motor current: the START button and an auxiliary NO contact form the self-holding circuit, while STOP and the NC contact of the overload relay interrupt the coil circuit.

    Pros

    • Manufacturer-confirmed AC-3 and AC-1 ratings
    • Extensive ABB AF accessory system
    • DIN rail mounting
    • Auxiliary contacts 1NO already fitted
    • Max. operating voltage 690 V
    • Widely used model – easy to find a replacement

    Cons / limitations

    • Does not itself protect against overload or short circuit – an overload relay or protective breaker is required
    • Coil voltage is fixed (24–60 V AC / 20–60 V DC) – another control voltage needs another code
    • In AC-4 duty (frequent reversing, plugging) the permissible current is lower than in AC-3

    Safety and installation notes

    • Before installation, disconnect all circuits and verify that they are de-energized.
    • Check that the coil voltage matches the control circuit.
    • Select the conductor cross-section according to the load current and the terminal range specified by the manufacturer.
    • Tighten the terminals to the torque specified by the manufacturer.
    • Install short-circuit protection (fuses or circuit breaker) upstream of the contactor.
    • Work must be carried out by a qualified electrician in accordance with applicable electrical safety requirements.

    Quick selection guide

    3P
    AC-3 9 A
    4 kW / 400 V
    AC-1 25 A
    24–60 V AC / 20–60 V DC
    1NO
    AF09Z-30-10-21
    Suitable when you need to:
    • control a three-phase motor up to 4 kW at 400 V
    • switch a resistive load up to 25 A
    • replace an existing ABB AF contactor
    Check before use:
    • coil voltage and type of current
    • motor rated current and utilization category
    • required number of auxiliary contacts
    Important reminder: the contactor switches the load on and off, but does not replace an overload relay, motor protection circuit breaker or short-circuit protection.

    FAQ

    What motor power can be switched with AF09Z-30-10-21?
    Up to 4 kW at 400 V in AC-3 category (rated current 9 A).
    Does the contactor protect the motor against overload?
    No, an overload relay (e.g. ABB TF) or a motor protection circuit breaker is required.
    What is the coil voltage?
    24–60 V 50/60 Hz / 20–60 V DC.
    How many auxiliary contacts does it have?
    1NO.
    What resistive load can be switched?
    In AC-1 category up to 25 A at 40 °C ambient temperature.
    How is it mounted?
    On a 35 mm DIN rail or screwed to the panel mounting plate.

    Concise technical description (LT / EN)

    LT: ABB AF09Z-30-10-21 3 polių kontaktorius, AC-3 9 A / 4 kW 400 V, AC-1 25 A, ritė 24–60 V AC / 20–60 V DC, 1NO.

    EN: ABB AF09Z-30-10-21 3-pole contactor, AC-3 9 A / 4 kW 400 V, AC-1 25 A, 24–60 V AC / 20–60 V DC coil, 1NO.

    Contactor | 1NO | 3P | 4kW | 9A | 24-60VAC/20-60VDC | ABB | AF09Z-30-10-21 | 1SBL136001R2110

    ABB AF09Z-30-10-21 – 3-pole contactor: AC-3 9 A / 4 kW (400 V), AC-1 25 A, 24–60 V AC / 20–60 V DC coil, 1NO. Designed for controlling motors and three-phase loads in automation panels.

    Published: 2026-11-24 · Data verified against the manufacturer datasheet: 2026-11-24

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • Alternative products

    Industrial modular socket panel | 2×CEE 16 A 5P 400 V + 1×CEE 32 A 5P 400 V + 2×Schuko 230 V | space for 11 modules of protection | IP44 | SEZ ROS11/x-14
    Code: ROS11/x-14 2x230V+2x16A+1x32A

    SEZ ROS11/x-14 – a sealed industrial panel with sockets (2×CEE 16 A 5P 400 V + 1×CEE 32 A 5P 400 V + 2×Schuko 230 V) and space for 11 modules of protective devices. Degree of protection: IP44, mounting – wall-mounted (surface).

    Price 62.90 € VAT incl.
    ( 51.99 € VAT excl. )
    Flexible copper cable H03VV-F | 3G0.75 mm² | 300/300 V | round | black | 1 m | Lietkabelis
    Code: 91530702

    H03VV-F 3G0.75 mm² – AB Lietkabelis flexible round copper cable with class 5 conductors, PVC insulation and a black PVC sheath, 300/300 V. Sold by the metre.

    Cores: L, N, PE. Indicative current ≈ 6 A – for light appliances indoors.

    Price 0.54 € VAT incl.
    ( 0.44 € VAT excl. )
    LED signal lamp | 22 mm | 230 V AC/DC | red | IP54 | compact | Promfactor Baltic | FPL230RD
    Code: FPL230RD

    Compact one-piece LED signal lamp for a Ø 22 mm hole, 230 V AC/DC. Connected with two terminals and takes little space behind the door.

    Price 1.49 € VAT incl.
    ( 1.23 € VAT excl. )
    Cable ties with marker tag | 2,5x110mm | white | 100 pcs | 4772124000407
    Code: 4772124000407

    Marker cable ties (code 4772124000407) – white PA66 nylon cable ties, 2.5x110 mm, with an integrated marking plate, in a pack of 100 pcs. Designed to bundle wires, cables and tubing while labelling them at the same time: the circuit number, port name or other information is written on the plate, so one tie handles both fastening and identification.

    Price 2.42 € VAT incl.
    ( 2.00 € VAT excl. )
    Terminal | connector paste for contacts | reduces oxidation | 35.3g | WAGO | ALU PLUS | 249-130 | for connecting aluminium and copper wires
    Code: 4017332133890

    Contact paste designed to protect aluminum conductors from oxidation and ensure a reliable electrical connection. This special paste allows aluminum and copper conductors to be safely and efficiently connected within the same connector, making it particularly useful when renovating older electrical installations where aluminum wiring is commonly found.

    Aluminum naturally oxidizes, and the resulting oxide layer increases contact resistance, causes connection heating, and may become a source of electrical faults. By using WAGO ALU-PLUS, the oxidation layer is reduced, electrical conductivity is improved, and the service life of the connection is significantly extended. 

    Price 2.83 € VAT incl.
    ( 2.34 € VAT excl. )