Products catalog

  • Industrial socket box | 2×16 A 5P 400 V + 4×230 V 16 A | with holder | IP44 | SEZ ROS 1605 D

    Code: SKU#ROS1605D-2x16A-4x230V
    Barcode: 8585007348154

    SEZ socket box with 2×CEE 16 A 5P + 4×230 V 16 A outlets, IP44 (outlets IP54), with a holder for portable use. No MCBs or RCD inside – protection is installed in the supply board.

  • Industrial socket box | 2×16 A 5P 400 V + 4×230 V 16 A | with holder | IP44 | SEZ ROS 1605 D

    SEZ ROS 1605 D – SEZ socket box with 2×CEE 16 A 5P 400 V and 4×230 V 16 A domestic outlets. The D version has a holder, so the box serves as a mobile power distribution point. Enclosure protection – IP44 (outlets IP54).

    Key point:
    One box gives you several three-phase outlets plus 230 V domestic outlets for hand tools, lighting or chargers. There are no MCBs or RCD in the box, so all protection must be in the supply board.
    Outlets
    2×CEE 16 A 5P + 4×230 V 16 A
    Protection
    IP44 (outlets IP54)
    Current
    16 A
    Mounting
    portable, with holder

    How it works

    Supply: a 5-core cable (L1, L2, L3, N, PE) is brought in and connected to a terminal strip rated for cable up to 5×4 mm². A cable with plug is not listed in the manufacturer data – the installer selects it.

    Outlets: the CEE 16 A 5P outlets receive all three phases, N and PE (400 V), while the 4×230 V outlets get one phase, N and PE (230 V).

    Protection: the box is unprotected (no MCBs or RCD). An MCB (not above 16 A) and a 30 mA RCD are installed in the supply board; IP44 (outlets IP54) applies only with the outlet lids closed.

    Why choose SEZ ROS 1605 D?
    One three-phase cable gives you both 400 V and 230 V outlets without a separate board. The holder lets you keep the box next to the work area. All outlets are 16 A, which makes line protection simple to select.

    Technical specifications

    Product type Socket box (portable, with holder)
    Manufacturer / model SEZ DK a.s. (Slovakia) / ROS 1605 D
    Manufacturer order No. 200224
    Series ROS 16yy, unprotected version
    400 V outlets 2× CEE 16 A 5P (3P+N+PE), 400 V, 6h
    230 V outlets 4× 230 V 16 A (confirm type)
    Rated voltage 400 V~ / 250 V~, 50 Hz
    Protective devices None (unprotected version, no MCBs or RCD)
    Switch None
    Degree of protection IP44 (enclosure), IP54 (outlets), with lids closed
    Impact resistance IK10 (empty enclosure)
    Enclosure Plastic, holder (D version)
    Supply connection Terminal strip, cable up to 5×4 mm²
    Ambient temperature −25…+40 °C (catalogue data)
    Standards EN 61439-3; CEE outlets to EN 60309-2
    Total load not above the line breaker (≤16 A)

    Main functions

    • 2× CEE 16 A 5P 400 V – for three-phase tools, compressors, mixers, heaters
    • 4× 230 V outlets – for hand tools, lighting, chargers
    • Holder (D version) – the box can be carried and used for mobile distribution
    • IP44 enclosure – protection against splashing water
    • IK10 – impact resistance of the empty enclosure
    • Terminals up to 5×4 mm² – supply cable sized to the line
    • No modules – simple design, protection stays in the supply board

    How does it differ from similar products?

    SEZ ROS 1605/S (575) Same outlet layout with Schuko outlets (2×16 A 5P + 4×Schuko), IP44, no holder – for fixed mounting.
    SEZ ROS 1603 D/S (591) 3×16 A 5P + 2×Schuko, IP44, with holder – more three-phase outlets.
    SEZ ROS 1601 D (590) 4×CEE 16 A 5P, IP44, with holder – three-phase loads only, portable.
    SEZ ROS 3203 D (2225) 2×16 A 5P + 2×32 A 5P, IP44 – when 32 A outlets are needed but 230 V is not.

    Where is it used?

    • Garages and car service shops
    • Workshops and production areas
    • Farm buildings and barns
    • Temporary power for repairs and events
    • Construction work – fed from a site board
    • Indoor and covered areas

    Use by need

    Beginner.
    The box comes fully fitted – it needs a suitable cable and connection to a protected board. It is not an extension lead with breakers: leave the connection to an electrician.
    Experienced installer.
    Use a flexible rubber 5-core cable (e.g. H07RN-F) sized to the line, not larger than 5×4 mm²; check phase sequence at the CEE outlets and PE continuity.
    Power engineer / designer.
    The box is an end point without internal protection: overload and short-circuit protection (not above 16 A) and a 30 mA RCD are designed into the supply board. For sites – HD 60364-7-704.

    Practical use

    In a car service shop the box is kept at the repair bay: a three-phase compressor plugs into the CEE outlet, a lamp and grinder into the 230 V outlets. It is fed from the board through a 16 A MCB and a 30 mA RCD.

    Pros / advantages

    • Three-phase and domestic outlets in one enclosure
    • All outlets 16 A – protection is simple to select
    • Holder for portable use
    • IP44 enclosure and IK10
    • Terminals for cable up to 5×4 mm²

    Cons / limitations

    • No MCBs or RCD – protection must be in the supply board
    • No switch – for local switching choose SEZ ROS 4/V-12 (16 A) or ROS 4/V-10 (32 A)
    • Total load of all outlets is limited by the line breaker (up to 16 A), as the outlets have no separate protection
    • IP44 – not for continuous rain or water jets; outdoors it needs cover

    Safety and installation notes

    • ⚡ Connection and testing must be done by a qualified electrician, with the supply switched off.
    • ⚡ There are no MCBs or RCD in the box: protect the supply line with an MCB sized to the cable, not above 16 A, and a 30 mA RCD. The total load of all outlets must not exceed the line breaker.
    • If the supply line is single-phase, the CEE 400 V outlet must not be used – it will not have 400 V; feed the box from a three-phase 5-core line.
    • The PE contacts of the 230 V outlets must be connected – check PE continuity to every outlet and phase sequence at the CEE outlet.
    • On construction sites feed the box only from a site distribution board (HD 60364-7-704).
    • IP44 (outlets IP54) applies only with the outlet lids closed and the cable entry tightened.

    Quick selection guide

    2×CEE 16 A 5P 400 V
    4×230 V 16 A
    IP44 (outlets IP54) / IK10
    No MCBs or RCD
    Suitable when you need:
    • 400 V and 230 V outlets from one cable
    • Moving the box between work areas
    • Work indoors or under cover
    Check before choosing:
    • Is there a ≤16 A MCB and a 30 mA RCD in the supply board
    • Is the cable 5-core and does it fit the cable entry (up to 5×4 mm²)
    • Confirm the domestic outlet type (Schuko or French with earth pin) when ordering
    • Is a total load of 16 A enough
    Important reminder: The box does not replace a protective board: it has no MCBs or RCD. All protection must be in the supply board.
    ☝ Elsprendimai.eu recommends:

    FAQ

    Does the box contain MCBs or an RCD?
    No. The manufacturer lists it as an unprotected version, so an MCB (not above 16 A) and a 30 mA RCD must be in the supply board.
    Which supply cable should I use?
    A 5-core (L1, L2, L3, N, PE) flexible rubber cable, e.g. H07RN-F; the electrician selects the cross-section by protection and length. Terminals take cable up to 5×4 mm².
    Can it be fed from a single-phase line?
    No. The 230 V outlets would work, but there would be no 400 V at the CEE 5P outlet. The box is intended for three-phase supply.
    What does the letter D mean?
    The D version has a holder – the manufacturer intends it for mobile distribution.
    What type are the 230 V outlets?
    The manufacturer data only states 230 V 16 A. Confirm the type (Schuko or French with earth pin) when ordering.
    Can it be used outdoors or on a construction site?
    The IP44 enclosure is splash-proof, but it needs cover from rain. On sites – only when fed from a site board with an RCD (HD 60364-7-704).

    Sources: SEZ DK a.s. product page (https://www.sez.sk/produkty/ros-1605-d/); catalogue K1.1 "Zásuvkové rozvodnice a bubny" (2017). Checked 2026-10-20.

    SEZ ROS 1605 D – socket box 2×CEE 16 A 5P + 4×230 V 16 A, IP44

    SEZ ROS 1605 D – socket box (2×16 A 5P 400 V + 4×230 V 16 A), IP44, with holder, no MCBs or RCD. Suitable for garages, workshops and temporary power supply.

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • Subscribtion to new arrivals

    privacy policy

    Information