Products catalog

  • Modular | Residual current circuit breaker with over-current protection 2P | 32A | B | 10kA | 0.03A | Type A | DIN | FAP10-A Promfactor Baltic FAP10B32030A

    Code: FAP10B32030A

    This modular automatic circuit breaker with residual current relay is a modern solution for the protection of electrical circuits in residential, administrative, and commercial buildings. It ensures reliable protection against short circuits, overloads, and ground leakage currents, while also safeguarding people from electric shocks during direct or indirect contact. The product complies with the international IEC 61009 standard, guaranteeing high-quality protection and reliability even under challenging conditions.

  • Modular | Residual current circuit breaker with over-current protection 2P | 32A | B | 10kA | 0.03A | Type A | DIN | FAP10-A Promfactor Baltic FAP10B32030A

    FAP10B32030A – Promfactor Baltic ECO FAP10-A series circuit breaker with residual current protection (RCBO): 2P (1P+N), curve B 32 A, residual current 30 mA, type A, breaking capacity 10 kA. Overload, short-circuit and residual current protection in one device – for one single-phase ~230 V circuit where each circuit needs its own residual current protection.

    Key idea:
    The RCBO protects the 32 A circuit cable against overload and short circuit, and the 30 mA residual module protects people against electric shock. Type A also responds to pulsating DC leakage currents, so it suits circuits with electronic appliances. In case of leakage only this circuit trips, the others keep working.
    Rated current / curve
    B32 (32 A)
    Residual current
    30 mA (0.03 A), type A
    Breaking capacity
    10 kA
    Poles / voltage
    2P (1P+N) / ~230 V

    Operating principle

    The breaker is mounted in the panel on a DIN rail and connected to one single-phase circuit: phase and neutral pass through the device, the PE conductor does not.

    The thermal release responds to sustained overload above 32 A, the electromagnetic release to short-circuit current according to curve B (B – 3–5 In, for circuits with low inrush currents). The residual module compares phase and neutral currents and disconnects both poles at 30 mA.

    Result – each circuit has its own residual current protection: a fault in one circuit does not switch off the whole house or apartment, and the fault is easier to locate.

    Why choose FAP10B32030A?
    One modular device instead of a separate circuit breaker and RCD – a clearer panel layout and selective residual current protection for each circuit; breaking capacity 10 kA.

    Technical specifications

    Product typeCircuit breaker with residual current protection (RCBO)
    Manufacturer / codePromfactor Baltic / FAP10B32030A
    SeriesECO FAP10-A
    Number of poles2P (1P+N)
    Rated current (In)32 A
    Tripping curveB
    Rated residual current (IΔn)30 mA (0.03 A)
    Residual current typeA
    Ultimate breaking capacity (Icu)10 kA (10 000 A)
    Residual module typeElectromechanical
    Rated voltage (Ue)~230 V
    Frequency50/60 Hz
    Insulation voltage (Ui)500 V
    Impulse withstand voltage (Uimp)4000 V
    Selectivity class3
    Fast tripping time≤0.1 s
    Electrical / mechanical endurance6000 / 20 000 cycles
    Terminalscable up to 25 mm²; tightening torque 3.5 Nm
    Mounting35 × 7.5 mm DIN rail
    Degree of protectionIP20
    Operating temperature-25…+55 °C
    Storage temperature-25…+70 °C
    StandardIEC 61009

    Main functions

    • Overload protection – the 32 A circuit cable does not overheat.
    • Short-circuit protection B – more sensitive tripping for circuits with low inrush currents.
    • Residual current protection 30 mA – additional protection of people against electric shock.
    • Type A – also detects pulsating DC leakage currents.
    • Breaking capacity 10 kA – also suitable for sites with higher prospective short-circuit current.
    • Separate protection for each circuit – in case of leakage only one circuit trips.

    Where is it used?

    • Apartment and house panels with per-circuit residual current protection
    • Socket circuits
    • Bathroom and wet room circuits
    • Kitchen appliance circuits
    • Outdoor sockets and lighting
    • Office workstation circuits
    • Panel upgrades where there is no space for a separate RCD

    Use by need

    For the apartment or house owner.
    A fault in one circuit does not switch off the whole home – lighting and other appliances stay on.
    For the installing electrician.
    One device instead of two – faster installation and fewer connections in the panel.
    For the designer.
    The ECO FAP10-A series offers curves B and C – easy to match to the load.

    Practical application

    If in an apartment the kitchen sockets are supplied by a separate 32 A circuit and a leakage there should not switch off the whole apartment, protect this circuit with FAP10B32030A: overload, short circuit and 30 mA leakage will disconnect only the kitchen sockets.

    Advantages

    • Overload, short-circuit and residual current protection in one device
    • 30 mA additional protection of people
    • Breaking capacity 10 kA
    • Curve B 32 A
    • Selective protection – only one circuit trips
    • "T" button for periodic testing

    Disadvantages / limitations

    • Type A does not replace type F or B where the equipment manufacturer requires it
    • Intended for single-phase circuits only
    • More expensive than one shared RCD for several breakers
    • Curve and current must match the cable cross-section

    Safety and installation notes

    • Installation by a qualified electrician after disconnecting the supply and verifying absence of voltage
    • The circuit cable cross-section must match 32 A protection
    • Connect phase and neutral according to the device marking; do not route PE through it
    • Do not interconnect the neutrals of different RCBOs
    • Check that the prospective short-circuit current does not exceed 10 kA
    • After installation, test with the "T" button and an RCD tester

    Quick selection guide

    2P (1P+N)
    B32
    30 mA
    type A
    10 kA
    ~230 V
    Suitable when you need:
    • separate residual current protection for one circuit
    • protection of a 32 A circuit
    • overload, short-circuit and residual current protection in one device
    Check before use:
    • whether the cable suits 32 A protection
    • whether curve B suits the load
    • whether type A suits the connected equipment
    • whether the prospective short-circuit current is ≤ 10 kA
    Important reminder: An RCBO does not replace protective earthing or periodic inspection of the electrical installation.

    FAQ

    Does FAP10B32030A protect against short circuit?
    Yes – it contains a curve B circuit breaker and 30 mA residual current protection.
    What is the difference between curves B and C?
    B trips at 3–5 In, C at 5–10 In; C suits higher inrush currents.
    Is it suitable for frequency converters and EV charging?
    Only if the equipment manufacturer allows type A; type F or B is often required.
    How many modules does it take?
    It takes 2 modules on the DIN rail.
    Can it protect several circuits?
    One circuit per RCBO is recommended – that keeps selectivity.
    How often should the "T" button be pressed?
    Periodically, for example every few months, and after work in the panel.

    Modular | Residual current circuit breaker with over-current protection 2P | 32A | B | 10kA | 0.03A | Type A | DIN | FAP10-A Promfactor Baltic FAP10B32030A

    Promfactor Baltic FAP10B32030A – circuit breaker with residual current protection ECO FAP10-A 2P B32 30 mA type A, 10 kA, DIN – protection of a single-phase circuit against overload, short circuit and residual currents.

    Published: 2026-11-07 · Data verified against the manufacturer's datasheet: 2026-11-06

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • Alternative products

  • Subscribtion to new arrivals

    privacy policy

    Information