Products catalog

  • Modular residual current circuit breaker with overcurrent protection (RCBO) | 1P+N | 20A | C | 6kA | 0.03A | type A | DIN | IEK | MAD22-5-020-C-30

    Code: MAD22-5-020-C-30
    Barcode: 4606056055252

    IEK AVDT32 residual current circuit breaker with overcurrent protection (RCBO) 1P+N, C20, 30 mA, breaking capacity 6 kA, type A. One device protects a circuit against overload, short circuit and residual current.

  • Modular residual current circuit breaker with overcurrent protection (RCBO) | 1P+N | 20A | C | 6kA | 0.03A | type A | DIN | IEK | MAD22-5-020-C-30

    IEK AVDT32 residual current circuit breaker with overcurrent protection (RCBO) 1P+N, C20, 30 mA, breaking capacity 6 kA, type A. One device protects a circuit against overload, short circuit and residual current.

    Key idea:
    One device protects a circuit against overload, short circuit and leakage at once, so a fault in one circuit does not switch off the whole board. The 30 mA residual current is intended for protection of people against electric shock.
    Poles
    1P+N
    Rated current
    C20
    Residual current
    30 mA
    Breaking capacity
    6 kA

    Operating principle

    The device is mounted on a 35 mm DIN rail and connected into a single circuit.

    The circuit breaker part disconnects the circuit on overload or short circuit according to the C characteristic. The residual current part compares outgoing and returning current and trips when the difference reaches 30 mA.

    Result – the circuit cable is protected against overheating and short circuit, and in case of leakage the other circuits stay on.

    Why choose MAD22-5-020-C-30?
    Instead of a separate circuit breaker and RCCB – one device per circuit: less space in the board, and a leak does not switch off the other circuits.

    Technical specifications

    Product type Residual current circuit breaker with overcurrent protection (RCBO)
    Manufacturer / code IEK / MAD22-5-020-C-30
    Series AVDT32
    Number of poles 1P+N
    Rated current (In) 20 A
    Tripping characteristic C
    Rated residual current (IΔn) 30 mA
    Rated breaking capacity (Icn) 6 kA
    Residual current type type A
    Standard IEC/EN 61009-1
    Impulse withstand voltage (Uimp) 4 kV
    Degree of protection IP20
    Width 2 modules (36 mm)
    Mounting 35 mm DIN rail

    Key functions

    • Overload protection – the circuit cable does not overheat when 20 A is exceeded for a long time
    • Short-circuit protection – the C characteristic quickly disconnects short-circuit current
    • Residual current monitoring – disconnects the circuit when leakage reaches 30 mA
    • Circuit-by-circuit selectivity – leakage in one circuit does not switch off the others
    • Test button – lets you check that the residual current part works

    Where is it used?

    • Bathroom socket circuit
    • Kitchen socket circuit
    • Outdoor sockets and garden equipment
    • Washing machine or water heater circuit
    • Office and shop circuits
    • House and country house boards

    Use by need

    Electrician.
    Fit each circuit with residual current and overcurrent protection in one device.
    House or apartment owner.
    Protect the family against the risk of electric shock.
    Panel builder.
    Equip the board with a device of verified parameters.

    Practical use

    If a circuit is protected by a C20 circuit breaker and the cable is rated for it, it can be replaced with this RCBO – the circuit gains 30 mA residual current protection, and in case of leakage the other circuits stay on.

    Pros

    • Overload, short-circuit and residual current protection in one device
    • Leakage in one circuit does not switch off the others
    • Breaking capacity 6 kA
    • Type A – also responds to pulsating DC residual current
    • Parameters verified against the manufacturer’s catalogue

    Cons / limitations

    • Type A is not suitable for smooth DC residual current (EV chargers without DC protection) – type B is needed
    • Protects only one circuit – several circuits need several devices
    • IP20 – for installation inside a board only; outdoors or in damp areas a sealed enclosure is required

    Safety and installation notes

    • Install only with the voltage disconnected and its absence verified.
    • Work must be carried out by a qualified electrician.
    • The circuit cable cross-section must match the 20 A protection.
    • Do not connect the neutral downstream of the device to the neutral of other circuits or to PE – otherwise it will trip unnecessarily.
    • After installation press the test button “T” and check that it trips.

    Quick selection guide

    1P+N
    C20
    30 mA
    type A
    6 kA
    Suitable when you need:
    • protection of one circuit against overload, short circuit and leakage
    • protection of people against electric shock
    • a new or upgraded board
    Check before use:
    • Whether the circuit has sources of smooth DC residual current
    • Whether 20 A matches the circuit cable cross-section
    • Whether there is enough space on the DIN rail
    Important reminder: An RCBO does not replace proper earthing – the installation must have a PE conductor.

    FAQ

    How does an RCBO differ from an RCCB?
    An RCBO also protects against overload and short circuit, an RCCB only against leakage.
    What is the 30 mA residual current for?
    The 30 mA threshold is used for protection of people against electric shock.
    Which residual current type is it?
    Type A – also responds to pulsating DC residual current.
    What does the C characteristic mean?
    The C characteristic tolerates higher inrush currents, so it suits general circuits with motors or transformers.
    Is it suitable for a three-phase installation?
    No – choose a 4P device for a three-phase circuit.
    How do I check that the device works?
    Press the test button “T” – a working device must trip.

    Modular residual current circuit breaker with overcurrent protection (RCBO) | 1P+N | 20A | C | 6kA | 0.03A | type A | DIN | IEK | MAD22-5-020-C-30

    IEK MAD22-5-020-C-30 – C20 30 mA type A RCBO 1P+N 6 kA for protecting a circuit against overload, short circuit and residual current.

    Published: 2026-11-15 · Data verified against the manufacturer’s catalogue: 2026-11-15

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • Alternative products

    Distribution box | 24-module enclosure | surface-mounted | metal | steel | 454x310x138mm | IP54 | PRO 4606056417463
    Code: MKM16-N-24-54-ZU

    This surface-mounted modular distribution box with 24 modules is a reliable solution for electrical installations in residential, commercial, or industrial environments. The robust steel enclosure ensures protection against mechanical impact, while the IP54 protection rating allows use both indoors and in limited outdoor areas. The box features two DIN rails for mounting modular devices (circuit breakers, RCCBs, RCBOs, contactors, etc.) and an integrated lock for added security.

    Price 77.17 € VAT incl.
    ( 63.78 € VAT excl. )