Products catalog

  • Modular residual current device | 2P | 63A | 0.3A | type AC | DIN | ECO FPR-AC | Promfactor Baltic | FPR2063300AC | 4779040159684

    Code: FPR2063300AC
    Barcode: 4779040159684
  • Modular residual current device | 2P | 63A | 0.3A | type AC | DIN | ECO FPR-AC | Promfactor Baltic | FPR2063300AC | 4779040159684

    FPR2063300AC – Promfactor Baltic FPR-AC series modular residual current device (RCCB): 2P, rated current 63 A, residual current 300 mA, type AC, electromechanical. Designed for single-phase ~230 V circuits (phase + neutral); used for fire protection and incoming / group-block protection where a selective stage above 30 mA devices is needed. The device does not protect against overload or short circuit – a circuit breaker is installed upstream or downstream for that.

    Key idea:
    FPR2063300AC continuously compares the current flowing into and out of the circuit: when the difference reaches 300 mA, the device disconnects all 2 poles. Type AC residual current protection responds to sinusoidal AC leakage currents – suitable for heating, lighting and ordinary socket circuits without high-power electronics. The rated current of 63 A is the operating current the device can carry through its contacts.
    Rated current
    63 A
    Residual current
    300 mA (0.3 A)
    Type
    AC, electromechanical
    Poles / voltage
    2P (1P+N) / ~230 V

    Operating principle

    The device is mounted in the panel on a 35 mm DIN rail. All live conductors of the circuit – phase and neutral – pass through its measuring transformer. The protective PE conductor is not routed through the device.

    While the current balance is intact, the magnetic fluxes in the transformer core cancel each other out. When current leaks to earth through a person or damaged insulation, a signal is induced in the secondary winding, and at 300 mA the electromechanical release trips the device within ≤0.1 s. Electromechanical operation does not depend on the supply voltage.

    Result – a single-phase circuit or group block up to 63 A is protected against residual currents, and the "T" button allows periodic function testing. The device works together with circuit breakers that protect the cables against overload and short circuit.

    Why choose FPR2063300AC?
    One 2P device can protect several circuits with separate circuit breakers, so the panel is more economical than with an RCBO for each circuit; the FPR-AC series includes 2P and 4P devices with 30, 100 and 300 mA sensitivity.

    Technical specifications

    Product typeModular residual current device (RCCB)
    Manufacturer / codePromfactor Baltic / FPR2063300AC
    SeriesFPR-AC (2P, 4P; 30 / 100 / 300 mA)
    Number of poles2P (1P+N)
    Rated current (In)63 A
    Rated residual current (IΔn)300 mA (0.3 A)
    Residual current typeAC
    Release typeElectromechanical
    Rated voltage (Un)~230/400 V
    Frequency50/60 Hz
    Insulation voltage (Ui)500 V
    Impulse withstand voltage (Uimp)4000 V
    Short-circuit current (stated by manufacturer as Icu)10 000 A
    Instantaneous tripping time≤0.1 s
    Electrical / mechanical endurance4000 / 20 000 cycles
    Terminalscable up to 25 mm²; tightening torque 3.5 Nm
    Mounting35 mm DIN rail
    Degree of protectionIP20
    Operating temperature-25…+55 °C
    Storage temperature-25…+70 °C

    Main functions

    • Residual current protection 300 mA – reduces fire risk from insulation faults and allows a selective stage above 30 mA devices.
    • Type AC – detects sinusoidal AC leakage currents – suitable for circuits without high-power electronics.
    • Electromechanical release – operation does not depend on supply voltage – the device trips even if the neutral is lost or the voltage drops.
    • All 2 poles disconnected – in case of leakage, phase and neutral conductors are disconnected.
    • "T" button – allows periodic testing of the tripping mechanism.
    • Modular housing – mounts on a 35 mm DIN rail next to circuit breakers.

    Where is it used?

    • Apartment and house distribution panels
    • Socket circuits
    • Bathroom and wet room circuits
    • Outdoor lighting and outdoor sockets
    • Country houses, garages, outbuildings
    • Office and shop circuits
    • Panel upgrades where residual current protection is missing

    Use by need

    For the installing electrician.
    One 63 A 300 mA device protects several single-phase circuits – fewer modules in the panel.
    For the apartment or house owner.
    Socket, bathroom and outdoor circuits get residual current protection in line with safety requirements.
    For the panel builder.
    FPR-AC 2P devices with 30, 100 and 300 mA allow flexible planning of protection stages.

    Practical application

    If in an apartment panel the socket and bathroom circuits are supplied through circuit breakers and the total load does not exceed 63 A, then FPR2063300AC is installed upstream of these breakers: in case of leakage it disconnects the whole block, while overload and short circuit are still handled by the circuit breakers.

    Advantages

    • 300 mA residual current protection, type AC
    • Electromechanical operation – independent of voltage
    • Disconnects all 2 poles
    • "T" button for periodic testing
    • IP20, operating temperature -25…+55 °C
    • One device can protect several circuits

    Disadvantages / limitations

    • Does not protect against overload and short circuit – a circuit breaker is required
    • Type AC is not suitable for circuits with frequency converters, inverters or EV charging – choose type A, F or B
    • In case of leakage, all circuits protected by the device are disconnected
    • 300 mA does not replace 30 mA additional protection of people where it is required

    Safety and installation notes

    • Installation by a qualified electrician after disconnecting the supply and verifying absence of voltage
    • Route all live conductors through the device; do not route the PE conductor through it
    • Do not interconnect the neutral conductors of different residual current devices
    • Protect the device with a circuit breaker not exceeding 63 A
    • After installation, check operation with the "T" button and an RCD tester

    Quick selection guide

    2P
    63 A
    300 mA
    type AC
    ≤0.1 s
    DIN 35 mm
    Suitable when you need:
    • residual current protection of single-phase circuits
    • loads up to 63 A
    • fire risk reduction and protection stages
    Check before use:
    • whether there is a circuit breaker ≤ 63 A upstream
    • whether type AC suits the connected equipment
    • that neutrals are not shared with other circuits
    • that the panel has 2 free modules
    Important reminder: A residual current device does not replace protective earthing, circuit breakers or periodic inspection of the electrical installation.

    FAQ

    Does FPR2063300AC protect against short circuit?
    No – a circuit breaker is installed upstream or downstream for that.
    What do 63 A and 300 mA mean?
    63 A is the rated operating current through the contacts, 300 mA is the residual current at which the device disconnects the circuit.
    Is it suitable for circuits with an inverter or frequency converter?
    No – for such circuits choose type A, F or B according to the equipment manufacturer.
    How often should the "T" button be pressed?
    Periodically, for example every few months, and after any work in the panel.
    How many modules does it take?
    The two-pole device takes 2 modules on the DIN rail.
    Can the PE conductor be routed through the device?
    No – only phase and neutral conductors pass through the device.

    Modular residual current device | 2P | 63A | 0.3A | type AC | DIN | ECO FPR-AC | Promfactor Baltic | FPR2063300AC | 4779040159684

    Promfactor Baltic FPR2063300AC – modular residual current device FPR-AC 2P 63 A 300 mA type AC, electromechanical, DIN rail – protection of single-phase circuits against residual currents, fire risk and insulation faults.

    Published: 2026-11-07 · Data verified against the manufacturer's datasheet: 2026-11-06

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • Alternative products

  • Subscribtion to new arrivals

    privacy policy

    Information