Modular residual current device | 4P | 63A | 0.1A | type AC | DIN | ECO FPR-AC | Promfactor Baltic | FPR4063100AC | 4779040151503
Code: FPR4063100ACPrice 23.98 € VAT incl.( 19.82 € VAT excl. )-
Modular residual current device | 4P | 63A | 0.1A | type AC | DIN | ECO FPR-AC | Promfactor Baltic | FPR4063100AC | 4779040151503
FPR4063100AC – Promfactor Baltic FPR-AC series modular residual current device (RCCB): 4P, rated current 63 A, residual current 100 mA, type AC, electromechanical. Designed for three-phase ~400 V circuits (3 phases + neutral); used for protection against insulation faults and fire caused by leakage currents where 30 mA sensitivity is not required or would cause nuisance tripping. The device does not protect against overload or short circuit – a circuit breaker is installed upstream or downstream for that.
Key idea:
FPR4063100AC continuously compares the current flowing into and out of the circuit: when the difference reaches 100 mA, the device disconnects all 4 poles. Type AC residual current protection responds to sinusoidal AC leakage currents – suitable for heating, lighting and ordinary socket circuits without high-power electronics. The rated current of 63 A is the operating current the device can carry through its contacts.Rated current
63 AResidual current
100 mA (0.1 A)Type
AC, electromechanicalPoles / voltage
4P (3P+N) / ~400 VOperating principle
The device is mounted in the panel on a 35 mm DIN rail. All live conductors of the circuit – three phases and neutral – pass through its measuring transformer. The protective PE conductor is not routed through the device.
While the current balance is intact, the magnetic fluxes in the transformer core cancel each other out. When current leaks to earth through a person or damaged insulation, a signal is induced in the secondary winding, and at 100 mA the electromechanical release trips the device within ≤0.1 s. Electromechanical operation does not depend on the supply voltage.
Result – a three-phase circuit or group block up to 63 A is protected against residual currents, and the "T" button allows periodic function testing. The device works together with circuit breakers that protect the cables against overload and short circuit.
Why choose FPR4063100AC?
One 4P device can protect several circuits with separate circuit breakers, so the panel is more economical than with an RCBO for each circuit; the FPR-AC series includes 2P and 4P devices with 30, 100 and 300 mA sensitivity.Technical specifications
Product type Modular residual current device (RCCB) Manufacturer / code Promfactor Baltic / FPR4063100AC Series FPR-AC (2P, 4P; 30 / 100 / 300 mA) Number of poles 4P (3P+N) Rated current (In) 63 A Rated residual current (IΔn) 100 mA (0.1 A) Residual current type AC Release type Electromechanical Rated voltage (Un) ~230/400 V Frequency 50/60 Hz Insulation voltage (Ui) 500 V Impulse withstand voltage (Uimp) 4000 V Short-circuit current (stated by manufacturer as Icu) 10 000 A Instantaneous tripping time ≤0.1 s Electrical / mechanical endurance 4000 / 20 000 cycles Terminals cable up to 25 mm²; tightening torque 3.5 Nm Mounting 35 mm DIN rail Degree of protection IP20 Operating temperature -25…+55 °C Storage temperature -25…+70 °C Main functions
- Residual current protection 100 mA – disconnects the circuit in case of insulation faults where 30 mA would cause nuisance tripping due to background leakage.
- Type AC – detects sinusoidal AC leakage currents – suitable for circuits without high-power electronics.
- Electromechanical release – operation does not depend on supply voltage – the device trips even if the neutral is lost or the voltage drops.
- All 4 poles disconnected – in case of leakage, all phase and neutral conductors are disconnected.
- "T" button – allows periodic testing of the tripping mechanism.
- Modular housing – mounts on a 35 mm DIN rail next to circuit breakers.
Where is it used?
- Three-phase incoming panels of houses and farmsteads
- Workshops and garages with three-phase equipment
- Distribution panels of commercial premises
- Farm buildings
- Construction site panels
- Heat pump and electric heating circuits
- Group blocks in industrial premises
Use by need
For the installing electrician.
One 63 A 100 mA device protects a block of three-phase circuits without a separate RCBO for each.For the house or farmstead owner.
The three-phase supply, workshop or heating equipment gets residual current protection in line with electrical safety requirements.For the designer.
The FPR-AC series has 4P devices with 30, 100 and 300 mA – convenient for building protection stages.Practical application
If in a three-phase panel a block of circuits is supplied through circuit breakers and the total load does not exceed 63 A, then FPR4063100AC is installed upstream of these breakers: in case of leakage it disconnects the whole block, while overload and short circuit are still handled by the circuit breakers.Advantages
- 100 mA residual current protection, type AC
- Electromechanical operation – independent of voltage
- Disconnects all 4 poles
- "T" button for periodic testing
- IP20, operating temperature -25…+55 °C
- One device can protect several circuits
Disadvantages / limitations
- Does not protect against overload and short circuit – a circuit breaker is required
- Type AC is not suitable for circuits with frequency converters, inverters or EV charging – choose type A, F or B
- In case of leakage, all circuits protected by the device are disconnected
- 100 mA does not replace 30 mA additional protection of people where it is required
Safety and installation notes
- Installation by a qualified electrician after disconnecting the supply and verifying absence of voltage
- Route all live conductors through the device; do not route the PE conductor through it
- Do not interconnect the neutral conductors of different residual current devices
- Protect the device with a circuit breaker not exceeding 63 A
- After installation, check operation with the "T" button and an RCD tester
Quick selection guide
4P63 A100 mAtype AC≤0.1 sDIN 35 mmSuitable when you need:- residual current protection of a three-phase group block
- loads up to 63 A
- fire risk reduction and protection stages
Check before use:- whether there is a circuit breaker ≤ 63 A upstream
- whether type AC suits the connected equipment
- that neutrals are not shared with other circuits
- that the panel has 4 free modules
Important reminder: A residual current device does not replace protective earthing, circuit breakers or periodic inspection of the electrical installation.FAQ
Does FPR4063100AC protect against short circuit?
No – a circuit breaker is installed upstream or downstream for that.What do 63 A and 100 mA mean?
63 A is the rated operating current through the contacts, 100 mA is the residual current at which the device disconnects the circuit.Is it suitable for circuits with an inverter or frequency converter?
No – for such circuits choose type A, F or B according to the equipment manufacturer.How often should the "T" button be pressed?
Periodically, for example every few months, and after any work in the panel.How many modules does it take?
The four-pole device takes 4 modules on the DIN rail.Can the PE conductor be routed through the device?
No – only phase and neutral conductors pass through the device.Modular residual current device | 4P | 63A | 0.1A | type AC | DIN | ECO FPR-AC | Promfactor Baltic | FPR4063100AC | 4779040151503
Promfactor Baltic FPR4063100AC – modular residual current device FPR-AC 4P 63 A 100 mA type AC, electromechanical, DIN rail – protection of three-phase circuits against residual currents, fire risk and insulation faults.
Published: 2026-11-07 · Data verified against the manufacturer's datasheet: 2026-11-06
Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.ManufacturerThis product is marked with the CE label, which confirms that it complies with all applicable European Union directives and regulations. CE marking is not just a formality – it is an important indicator of quality and safety, ensuring that the product has been properly assessed, tested, and can be safely used throughout the EU market.
CE certification means that the product has been evaluated according to the main criteria:
Safety requirements – ensures that the product does not pose a risk to the user or the environment
Electromagnetic compatibility (EMC) – the device does not interfere with other equipment and is resistant to external disturbances
Environmental standards – complies with current ecological and material usage requirements
Operational reliability – the product is suitable for long-term use according to its intended purposeCE marking allows this product to:
be legally supplied and used in all European Union countries
ensure a high level of quality and safety
be used in residential, commercial, and industrial environmentsThe CE mark is a declaration of the manufacturer’s responsibility, confirming that the product complies with all applicable standards and has been assessed according to EU legislation.
What does this mean for you as a buyer?
Safe use in everyday activities
Reliable performance and reduced risk of failure
Compliance with EU standards and requirements
Suitability for professional solutions
Love it? Share your thoughts in a review!Write Review Alternative products