Power distribution terminal | 1P | 85 A (Cu/Al) | Cu 1.5–16 mm² / Al 1.5–16 mm² | 1000 V AC | DIN 35 | grey (L) | Promfactor Baltic | FT1016F
Code: FT1016FPrice 2.08 € VAT incl.( 1.72 € VAT excl. )Promfactor Baltic FT1016F – 1P terminal 85 A, 1000 V AC / 1500 V DC, Cu 1.5–16 / Al 1.5–16 mm², grey (L), DIN rail mounted.
-
Power distribution terminal | 1P | 85 A (Cu/Al) | Cu 1.5–16 mm² / Al 1.5–16 mm² | 1000 V AC | DIN 35 | grey (L) | Promfactor Baltic | FT1016F
FT1016F – a Promfactor Baltic FT series 1P power distribution (connection) terminal for copper and aluminium conductors: Cu 1.5–16 mm², Al 1.5–16 mm², rated current 85 A (Cu/Al), rated voltage 1000 V AC / 1500 V DC. The grey housing is intended for the phase (L) circuit; the terminal is mounted on a 35×7.5 mm DIN rail.
Key idea:
The terminal connects and distributes phase conductors in the panel at one clearly marked point. One pole has 2 contacts – the incoming conductor is connected on one side and the outgoing one on the other, and the aluminium alloy clamps accept both Cu and Al conductors.Rated current (Cu/Al)
85 A (Cu/Al)Rated voltage
1000 V AC / 1500 V DCCross-section
Cu 1.5–16 mm² / Al 1.5–16 mm²Poles / colour
1P (2 contacts), grey – LOperating principle
FT1016F is clipped onto a 35×7.5 mm DIN rail in the distribution board, and the row ends are secured with an EW-35 end stop. The conductor is stripped to the clamp depth; an aluminium conductor is cleaned of oxide and coated with contact paste, then inserted into the clamp and tightened to the torque specified on the product page: 1.5 Nm (1.5 mm²); 3.5 Nm (2.5–6 mm²); 7 Nm (10–16 mm²).
The terminal pole has 2 contacts (2 in total); the aluminium alloy clamps accept 1.5–16 mm² copper and 1.5–16 mm² aluminium conductors. Rated current – 85 A (Cu/Al), rated voltage – 1000 V AC / 1500 V DC, polyamide housing, degree of protection IP20.
Result – a tidy location for phase connections: the grey housing clearly indicates the circuit function, connections are easy to check and retighten during maintenance, and the control panel is assembled without improvised connections.
Benefits FT1016F?
One terminal for Cu and Al wires (1.5–16 mm² Cu / 1.5–16 mm² Al), 85 A (Cu/Al), 1000 V AC / 1500 V DC, L colour coding and 1P design – fewer parts in stock and a clearer control panel layout.Technical specifications
Product type Power distribution (connection) terminal Manufacturer / code Promfactor Baltic / FT1016F Series FT (1P, 2P, 3P; Cu/Al 1.5–16 … 35–240 mm²; blue, green-yellow, grey) Standards IEC/EN 60947-7-1, IEC/EN 61238-1 Number of poles 1 Number of contacts 2 Rated voltage (Un) 1000 V AC / 1500 V DC Rated current (In) 85 A (Cu/Al) Copper conductors (Cu) 1.5–16 mm² Aluminium conductors (Al) 1.5–16 mm² Screw tightening torque 1.5 Nm (1.5 mm²); 3.5 Nm (2.5–6 mm²); 7 Nm (10–16 mm²) Housing material Polyamide PA66 Clamp material Aluminium alloy Degree of protection IP20 Installation 35×7.5 mm DIN rail Operating temperature -25…+55 °C Storage temperature -25…+70 °C Weight 21 g Enclosure colour grey Circuit by colour Phase L Code structure FT10xx – max. cross-section mm²; N – blue, G – green-yellow, F – grey; no suffix – 1P, 2 – 2P, 3 – 3P Main functions
- Cu and Al conductors – one terminal accepts copper 1.5–16 mm² and aluminium 1.5–16 mm² conductors.
- Rated current and voltage – 85 A (Cu/Al), 1000 V AC / 1500 V DC – suitable for both AC and DC circuits.
- Wide cross-section range – from 1.5 to 16 mm² (Cu) – the incoming cable and branches are connected with terminals of the same series.
- Colour coding – the grey housing immediately identifies the L circuit – fewer errors during installation and maintenance.
- 1P, 2 contacts – one pole with input and output clamps – a freely configurable row.
- Screw clamp – tightening torque 1.5 Nm (1.5 mm²); 3.5 Nm (2.5–6 mm²); 7 Nm (10–16 mm²) – the connection can be checked and retightened during maintenance.
- Mounting on a 35×7.5 mm DIN rail – the terminal is placed in a common row with other FT series terminals, and the ends are secured with EW-35.
- Unified series – the same cross-section is available in blue, green-yellow and grey and in 1P, 2P and 3P versions – N, PE and L connections have the same design.
- Standards – IEC/EN 60947-7-1, IEC/EN 61238-1 – standards applicable to terminals and Cu/Al connections.
Where is it used?
- Apartment distribution board – switching of the incomer and final circuits
- Detached house panel – N and PE distribution
- Sub-distribution boards in garages and outbuildings
- Lighting and socket circuit panels
- Supply sub-panels for heat pumps and boilers
- Control sub-panels with 1.5–16 mm² conductors
- Connection of 1.5–16 mm² aluminium conductors in renovated buildings
On-demand operation
For installers of apartment and house panels.
The Cu and Al range of 1.5–16 mm² covers final circuit conductors and 16 mm² apartment supply cables.For installers passing through phase wires.
The grey housing is intended for phase L conductors, while the blue N and green-yellow PE terminals placed next to it remain visually distinct.For designers who prefer a modular row.
1P terminals are fitted one at a time, so it is easy to build a row with exactly as many poles as needed.Practical application
If a 10 mm² copper supply conductor needs to be connected in an apartment panel and distributed to the final circuits, then FT1016F (1P, 85 A (Cu/Al), Cu 1.5–16 mm² / Al 1.5–16 mm², grey) is used as the L circuit connection point, and the clamps are tightened to 1.5–7 Nm according to the conductor cross-section.Application guide: how it is used in practice
FT1016F adapts to different panels – only the cross-section of the connected cable and which conductors are routed onwards change:
Site What is connected Result Installer's note Apartment panel Incoming L conductor up to 16 mm² and circuit wires Phase connections concentrated in one place Use ferrules when connecting conductors up to 6 mm² House sub-distribution board Supply cable 10–16 mm² (Cu or Al) Sub-distribution board supplied without separate connectors Strip the Al conductor clean and coat it with contact paste Control sub-panel L wires 1.5–4 mm² Clear wire distribution Check the tightening after the first switch-on Terminal row on a DIN rail FT1016F together with FT1016N, FT1016G N, PE and L connections are arranged in a clear order Fit EW-35 at the ends of the row How to select an FT series connection terminal
Cross-section (Cu / Al), poles, colour Recommended model Cu 1.5–16 / Al 1.5–16 mm², 1P, blue, 85 A FT1016N (1P, for the N circuit) Cu 1.5–16 / Al 1.5–16 mm², 1P, green-yellow, 85 A FT1016G (1P, for the PE circuit) Cu 1.5–16 / Al 1.5–16 mm², 1P, grey, 85 A FT1016F (1P, for the L circuit) ← this model Cu 2.5–35 / Al 2.5–35 mm², 1P, blue, 135/120 A FT1035N (1P, for the N circuit) Cu 2.5–35 / Al 2.5–35 mm², 1P, green-yellow, 135/120 A FT1035G (1P, for the PE circuit) Cu 2.5–35 / Al 2.5–35 mm², 1P, grey, 135/120 A FT1035F (1P, for the L circuit) Cu 2.5–50 / Al 6–50 mm², 1P, blue, 160/145 A FT1050N (1P, for the N circuit) Cu 2.5–50 / Al 6–50 mm², 1P, green-yellow, 160/145 A FT1050G (1P, for the PE circuit) Cu 2.5–50 / Al 6–50 mm², 1P, grey, 160/145 A FT1050F (1P, for the L circuit) Cu 16–95 / Al 16–95 mm², 1P, blue, 245/220 A FT1095N (1P, for the N circuit) Cu 16–95 / Al 16–95 mm², 1P, green-yellow, 245/220 A FT1095G (1P, for the PE circuit) Cu 16–95 / Al 16–95 mm², 1P, grey, 245/220 A FT1095F (1P, for the L circuit) Cu 35–150 / Al 35–150 mm², 1P, blue FT1150N (1P, for the N circuit) Cu 35–150 / Al 35–150 mm², 1P, green-yellow FT1150G (1P, for the PE circuit) Cu 35–150 / Al 35–150 mm², 1P, grey FT1150F (1P, for the L circuit) Cu 35–240 / Al 35–240 mm², 1P, blue FT1240N (1P, for the N circuit) Cu 35–240 / Al 35–240 mm², 1P, green-yellow FT1240G (1P, for the PE circuit) Cu 35–240 / Al 35–240 mm², 1P, grey FT1240F (1P, for the L circuit) Cu 1.5–16 / Al 1.5–16 mm², 2P, blue, 85 A FT1016N2 (2P, for the N circuit) Cu 1.5–16 / Al 1.5–16 mm², 2P, green-yellow, 85 A FT1016G2 (2P, for the PE circuit) Cu 1.5–16 / Al 1.5–16 mm², 2P, grey, 85 A FT1016F2 (2P, for the L circuit) Cu 2.5–35 / Al 2.5–35 mm², 2P, blue, 135/120 A FT1035N2 (2P, for the N circuit) Cu 2.5–35 / Al 2.5–35 mm², 2P, green-yellow, 135/120 A FT1035G2 (2P, for the PE circuit) Cu 2.5–35 / Al 2.5–35 mm², 2P, grey, 135/120 A FT1035F2 (2P, for the L circuit) Cu 2.5–50 / Al 6–50 mm², 2P, blue, 160/145 A FT1050N2 (2P, for the N circuit) Cu 2.5–50 / Al 6–50 mm², 2P, green-yellow, 160/145 A FT1050G2 (2P, for the PE circuit) Cu 2.5–50 / Al 6–50 mm², 2P, grey, 160/145 A FT1050F2 (2P, for the L circuit) Cu 16–95 / Al 16–95 mm², 2P, blue, 245/220 A FT1095N2 (2P, for the N circuit) Cu 16–95 / Al 16–95 mm², 2P, green-yellow, 245/220 A FT1095G2 (2P, for the PE circuit) Cu 16–95 / Al 16–95 mm², 2P, grey, 245/220 A FT1095F2 (2P, for the L circuit) Cu 35–150 / Al 35–150 mm², 2P, blue FT1150N2 (2P, for the N circuit) Cu 35–150 / Al 35–150 mm², 2P, green-yellow FT1150G2 (2P, for the PE circuit) Cu 35–150 / Al 35–150 mm², 2P, grey FT1150F2 (2P, for the L circuit) Cu 35–240 / Al 35–240 mm², 2P, blue FT1240N2 (2P, for the N circuit) Cu 35–240 / Al 35–240 mm², 2P, green-yellow FT1240G2 (2P, for the PE circuit) Cu 35–240 / Al 35–240 mm², 2P, grey FT1240F2 (2P, for the L circuit) Cu 1.5–16 / Al 1.5–16 mm², 3P, blue, 85 A FT1016N3 (3P, for the N circuit) Cu 1.5–16 / Al 1.5–16 mm², 3P, green-yellow, 85 A FT1016G3 (3P, for the PE circuit) Cu 1.5–16 / Al 1.5–16 mm², 3P, grey, 85 A FT1016F3 (3P, for the L circuit) Cu 2.5–35 / Al 2.5–35 mm², 3P, blue, 135/120 A FT1035N3 (3P, for the N circuit) Cu 2.5–35 / Al 2.5–35 mm², 3P, green-yellow, 135/120 A FT1035G3 (3P, for the PE circuit) Cu 2.5–35 / Al 2.5–35 mm², 3P, grey, 135/120 A FT1035F3 (3P, for the L circuit) Cu 2.5–50 / Al 6–50 mm², 3P, blue, 160/145 A FT1050N3 (3P, for the N circuit) Cu 2.5–50 / Al 6–50 mm², 3P, green-yellow, 160/145 A FT1050G3 (3P, for the PE circuit) Cu 2.5–50 / Al 6–50 mm², 3P, grey, 160/145 A FT1050F3 (3P, for the L circuit) Cu 16–95 / Al 16–95 mm², 3P, blue, 245/220 A FT1095N3 (3P, for the N circuit) Cu 16–95 / Al 16–95 mm², 3P, green-yellow, 245/220 A FT1095G3 (3P, for the PE circuit) Cu 16–95 / Al 16–95 mm², 3P, grey, 245/220 A FT1095F3 (3P, for the L circuit) Cu 35–150 / Al 35–150 mm², 3P, blue FT1150N3 (3P, for the N circuit) Cu 35–150 / Al 35–150 mm², 3P, green-yellow FT1150G3 (3P, for the PE circuit) Cu 35–150 / Al 35–150 mm², 3P, grey FT1150F3 (3P, for the L circuit) Cu 35–240 / Al 35–240 mm², 3P, blue FT1240N3 (3P, for the N circuit) Cu 35–240 / Al 35–240 mm², 3P, green-yellow FT1240G3 (3P, for the PE circuit) Cu 35–240 / Al 35–240 mm², 3P, grey FT1240F3 (3P, for the L circuit) Cu/Al 2.5–35 mm², 3P+N+PE FT503500 (five-pole block for a three-phase line) Cu 2.5–50 / Al 6–50 mm², 3P+N+PE FT505000 (five-pole block for a three-phase line) Rule: choose the terminal according to the smallest and largest conductor to be connected (Cu and Al ranges differ in FT1050 models), the colour according to the circuit (N – blue, G – green-yellow PE, F – grey for phase L), and the number of poles according to how many separate lines need to be connected; for a three-phase line with N and PE in one block, FT503500 and FT505000 are available.When to choose another solution: other colours – FT1016N, FT1016G; other number of poles – FT1016F2, FT1016F3; for thicker cables – FT1035 or FT1050; 3P+N+PE blocks – FT503500, FT505000; distribution terminals DTB080–DTB500; insulated terminals F807–F815; DIN rails FD010100–FD011000; end stop EW-35.Pros
- Rated current 85 A (Cu/Al), voltage 1000 V AC / 1500 V DC
- Copper 1.5–16 mm² and aluminium 1.5–16 mm² conductors
- Colour coding of the L circuit (grey)
- 1P, 2 contacts – freely configurable row
- Standards IEC/EN 60947-7-1, IEC/EN 61238-1
- Polyamide PA66 housing, operating temperature -25…+55 °C
- Mounting on a 35×7.5 mm DIN rail
Cons / limitations
- Degree of protection IP20 – install only in closed panels or cabinets
- Largest conductor – 16 mm², current 85 A; for thicker cables choose FT1035 or FT1050
- Fixed colour – for a different circuit you will need FT1016N, FT1016G
- Single pole – a three-phase line requires several terminals or the FT503500 / FT505000 block
- Correct tightening torque and Al conductor preparation (oxide removal, contact paste) are essential
Safety and installation notes
- Installation and connection must be carried out only by a qualified electrician after disconnecting the supply and verifying that the circuit is de-energised.
- Do not exceed the rated current of 85 A (Cu/Al) and the rated voltage of 1000 V AC / 1500 V DC.
- Tighten the clamps to the specified torque – 1.5 Nm (1.5 mm²); 3.5 Nm (2.5–6 mm²); 7 Nm (10–16 mm²) – and check the connections after the first load and during periodic maintenance.
- The terminal is IP20 – install only in a closed panel or cabinet, operating temperature -25…+55 °C.
- Use the grey terminal only for the phase (L) circuit; fit an EW-35 end stop at the ends of the row.
Quick selection guide
1P85 A1000 V AC / 1500 V DCCu 1.5–16 / Al 1.5–16 mm²grey (L)DIN 35IP20Suitable when you need:- connect or distribute phase (L) conductors in the control panel;
- connect copper 1.5–16 mm² and aluminium 1.5–16 mm² conductors up to 85 A (Cu/Al);
- one pole per conductor, with a freely configurable row.
Check before use:- the smallest and largest conductor to be connected – whether it fits Cu 1.5–16 mm² / Al 1.5–16 mm²;
- load current – no more than 85 A (Cu/Al);
- circuit – the grey housing corresponds to L; other circuits will require FT1016N, FT1016G.
Important reminder: FT1016F – 1P grey terminal for the L circuit; versions in other colours and pole counts, as well as EW-35, are ordered separately.FAQ
What does the letter F mean in the code FT1016F?
The letter F denotes a grey housing for the L circuit; in the FT series, N stands for the blue, G for the green-yellow and F for the grey version.What wire cross-sections can be connected?
Copper 1.5–16 mm² and aluminium 1.5–16 mm² conductors; Al conductors must be cleaned of oxide and coated with contact paste before connection.How many poles and contacts does FT1016F have?
FT1016F is a 1P terminal with 2 contacts (2 per pole); in the FT series, a code without a suffix means 1P, suffix 2 – 2P, suffix 3 – 3P.What are the rated current and voltage?
Rated current 85 A (Cu/Al), rated voltage 1000 V AC / 1500 V DC.What tightening torque should be used for the screws?
Depending on the conductor cross-section: 1.5 Nm (1.5 mm²); 3.5 Nm (2.5–6 mm²); 7 Nm (10–16 mm²).How is the terminal installed?
The terminal is clipped onto a 35×7.5 mm DIN rail, and an EW-35 end stop is fitted at the ends of the row.Power distribution terminal | 1P | 85 A (Cu/Al) | Cu 1.5–16 mm² / Al 1.5–16 mm² | 1000 V AC | DIN 35 | grey (L) | Promfactor Baltic | FT1016F
Promfactor Baltic FT1016F – 1P power distribution terminal 85 A (Cu/Al), 1000 V AC / 1500 V DC, for copper 1.5–16 mm² and aluminium 1.5–16 mm² wires, grey housing for the L circuit, IP20, DIN rail mounting, IEC/EN 60947-7-1, IEC/EN 61238-1.
Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.ManufacturerThis product is marked with the CE label, which confirms that it complies with all applicable European Union directives and regulations. CE marking is not just a formality – it is an important indicator of quality and safety, ensuring that the product has been properly assessed, tested, and can be safely used throughout the EU market.
CE certification means that the product has been evaluated according to the main criteria:
Safety requirements – ensures that the product does not pose a risk to the user or the environment
Electromagnetic compatibility (EMC) – the device does not interfere with other equipment and is resistant to external disturbances
Environmental standards – complies with current ecological and material usage requirements
Operational reliability – the product is suitable for long-term use according to its intended purposeCE marking allows this product to:
be legally supplied and used in all European Union countries
ensure a high level of quality and safety
be used in residential, commercial, and industrial environmentsThe CE mark is a declaration of the manufacturer’s responsibility, confirming that the product complies with all applicable standards and has been assessed according to EU legislation.
What does this mean for you as a buyer?
Safe use in everyday activities
Reliable performance and reduced risk of failure
Compliance with EU standards and requirements
Suitability for professional solutions
Love it? Share your thoughts in a review!Write Review Alternative products
Aluminium power cable | 4x50mm² | AXMK | Class 2 | 1500m | BlackCode: SKU#165996533759726861Aluminium power cable AXMK 4×50 mm², designed for fixed 0.6/1 kV power transmission and distribution installations. The cable features Class 2 aluminium conductors, XLPE insulation and a black UV-resistant PVC sheath. Suitable for installation outdoors, underground, in dry, damp and wet areas, cable ducts, conduits and concrete. Maximum operating temperature – 90 °C.
Sold by the drum, i.e. the minimum order quantity is 1500 metres.
Delivery time: up to 6 weeks.
Price 6.32 € VAT incl.( 5.22 € VAT excl. )Terminal | connector paste for contacts | reduces oxidation | 35.3g | WAGO | ALU PLUS | 249-130 | for connecting aluminium and copper wiresCode: 4017332133890Contact paste designed to protect aluminum conductors from oxidation and ensure a reliable electrical connection. This special paste allows aluminum and copper conductors to be safely and efficiently connected within the same connector, making it particularly useful when renovating older electrical installations where aluminum wiring is commonly found.
Aluminum naturally oxidizes, and the resulting oxide layer increases contact resistance, causes connection heating, and may become a source of electrical faults. By using WAGO ALU-PLUS, the oxidation layer is reduced, electrical conductivity is improved, and the service life of the connection is significantly extended.
Price 2.83 € VAT incl.( 2.34 € VAT excl. )