Copper busbar | 40 × 10 mm | 4 m | Elsp Group | ESV40X10
Code: ESV40X10Rigid copper busbar 40 × 10 mm (400 mm²), 4 m length for phase, N and PE main bars in switchboards. Indicative current rating per DIN 43671 – 715 A (bare, AC, +35 °C). Bar weight – about 14.3 kg.
-
Copper busbar | 40 × 10 mm | 4 m | Elsp Group | ESV40X10
Rigid flat electrolytic copper busbar 40 × 10 mm, 4 m length. For L1–L3, N and PE main bars in distribution boards, transformer substations, UPS, battery and solar DC systems.
Key point:
Cross-section – 400 mm². Indicative continuous current rating per DIN 43671 – 715 A (one bare bar per phase, AC, ambient +35 °C, busbar temperature +65 °C). In a closed enclosure the rating is lower, for a painted bar higher, so the final size is confirmed by the switchboard designer.Cross-section
400 mm²Current rating (DIN 43671)
715 ABar weight
~14.3 kgLength
4 mHow it works
The busbar is fixed in the switchboard on insulated supports and connected to device terminals, switch-disconnectors and other bars by bolted joints. Before jointing, contact surfaces are cleaned to bare metal and coated with contact compound.
The flat 40 × 10 mm profile has a large cooling surface, so the bar dissipates heat well and carries high current at low resistance – about 43.1 µΩ/m at 20 °C.
With the right size and quality joints, the main bar runs without overheating, and losses and voltage drop at the joints stay minimal.
Why choose a 40 × 10 mm busbar?
It distributes up to 715 A through a single rigid conductor: no cable bundles, neat bolted tap-offs and a clear phase layout in the switchboard.Technical specifications
Product type Rigid flat copper busbar Manufacturer / code Elsp Group – ESV40X10 Material Electrolytic copper (Cu-ETP / M1), ~99.9 % Cu Dimensions (width × thickness) 40 × 10 mm Length 4 m Cross-section 400 mm² Weight per 1 m ~3.58 kg Bar weight ~14.3 kg Resistance at 20 °C ~43.1 µΩ/m Current rating per DIN 43671 715 A Equivalent power ~495 kW (400 V, 3-phase, cos φ = 1) Weight and resistance are calculated with a copper density of 8.96 g/cm³ and resistivity of 0.01724 Ω·mm²/m. DIN 43671 conditions: bare busbar, AC, ambient +35 °C, busbar +65 °C.Key functions
- Main bar – L1–L3, N and PE bars in the switchboard with a single rigid conductor.
- Low resistance – about 43.1 µΩ/m, so lower losses and voltage drop.
- Neat tap-offs – devices are bolted directly to the bar.
- Earthing bar – main earthing or equipotential bonding bar.
- Workable on site – the bar can be cut, drilled and bent to suit the switchboard.
How does it differ from similar busbars?
- 30 × 10 mm – smaller cross-section – 573 A, for lower loads.
- 50 × 10 mm – larger cross-section – 852 A, for higher loads or closed enclosures.
- Aluminium busbar – lighter and cheaper, but needs ~1.6 times the cross-section for the same resistance, plus Cu–Al transition joints.
- Flexible busbar – for short connections between devices and vibration compensation; a rigid bar is for main bars.
Where is it used?
- Distribution boards and MCCs – phase, N and PE main bars.
- Transformer substations – 0.4 kV side connections and incomers to LV switchboards.
- UPS and battery systems – DC bars where current is high and voltage low.
- Solar plants – main bars in AC and DC boards.
- Earthing – main earthing bar, equipotential bonding.
- Industrial equipment – power connections in control and distribution cabinets.
Use by need
Switchboard builder.
Uniform main bars for phases, N and PE – clear design and fast assembly.Power engineer and contractor.
Substation 0.4 kV side and main board connections with a known current rating.UPS and battery integrator.
Low resistance in the DC bar – less voltage drop and heating.Practical use
If the switchboard needs a main bar with a design current of up to 715 A, a 40 × 10 mm busbar is suitable per DIN 43671 in an open installation. If the enclosure is closed and warm, choose a larger cross-section or a painted bar – decide this with the designer.
Pros
- High current rating – 715 A per DIN 43671.
- Low resistance – about 43.1 µΩ/m.
- Rigid profile – holds its geometry and withstands fixing loads.
- Easy to work – can be cut, drilled and bent.
- Known weight – ~14.3 kg per bar, easy to plan transport and installation.
Cons / limitations
- Bare bar – requires insulated supports, clearances and protective covers.
- Copper is heavier and costlier than aluminium – consider aluminium for long runs.
- Rating depends on conditions – lower than the table value in a closed enclosure.
- Not for vibration or movement – use flexible busbars there.
Safety and installation notes
- Before work, isolate the supply, secure it against switching on and verify that no voltage is present.
- Clean contact surfaces and apply contact compound.
- For bolted joints use class 8.8 bolts with disc spring washers, tightened to the manufacturer's torque.
- Set support spacing according to the short-circuit current.
- Connect copper to aluminium only via Cu–Al transition joints.
- Cover bare live parts; installation must be carried out by a qualified electrician.
Quick selection guide
If the switchboard needs a main bar with a design current of up to 715 A, a 40 × 10 mm busbar is suitable per DIN 43671 in an open installation. If the enclosure is closed and warm, choose a larger cross-section or a painted bar – decide this with the designer.
40 × 10 mm400 mm²715 A4 mSuitable when you need:- a main bar up to 715 A per DIN 43671;
- a phase, N or PE bar in a switchboard or substation;
- a low-resistance DC bar.
Check before use:- the design current and enclosure temperature;
- the short-circuit current and support spacing;
- device terminal width and bolt hole positions.
Important reminder: the busbar does not replace a switchboard design – current rating, clearances and short-circuit withstand are confirmed by the designer to IEC 61439.FAQ
What current can a 40 × 10 mm busbar carry?
Per DIN 43671 – 715 A (bare, AC, +35 °C); less in a closed enclosure.How much does the bar weigh?
About 3.58 kg/m, the whole 4 m bar – about 14.3 kg.How many kW can it carry?
In a three-phase 400 V system at cos φ = 1 – about 495 kW.Can it be used for DC?
Yes; resistance is about 43.1 µΩ/m, used to calculate voltage drop in a DC bar.Do two bars per phase give double the current?
No, about 1.6–1.8 times more, because parallel bars heat each other.Can the bar be cut, bent and painted?
Yes; bend only with a tool and leave contact areas unpainted.Copper busbar | 40 × 10 mm | 4 m | Elsp Group | ESV40X10
Rigid copper 40 × 10 mm (400 mm²) busbar for switchboard, substation and DC main bars: 715 A per DIN 43671, ~14.3 kg per 4 m bar.
Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.ManufacturerThis product is marked with the CE label, which confirms that it complies with all applicable European Union directives and regulations. CE marking is not just a formality – it is an important indicator of quality and safety, ensuring that the product has been properly assessed, tested, and can be safely used throughout the EU market.
CE certification means that the product has been evaluated according to the main criteria:
Safety requirements – ensures that the product does not pose a risk to the user or the environment
Electromagnetic compatibility (EMC) – the device does not interfere with other equipment and is resistant to external disturbances
Environmental standards – complies with current ecological and material usage requirements
Operational reliability – the product is suitable for long-term use according to its intended purposeCE marking allows this product to:
be legally supplied and used in all European Union countries
ensure a high level of quality and safety
be used in residential, commercial, and industrial environmentsThe CE mark is a declaration of the manufacturer’s responsibility, confirming that the product complies with all applicable standards and has been assessed according to EU legislation.
What does this mean for you as a buyer?
Safe use in everyday activities
Reliable performance and reduced risk of failure
Compliance with EU standards and requirements
Suitability for professional solutions
Love it? Share your thoughts in a review!Write Review Alternative products