Products catalog

  • Ring cable lug | 35mm² | M8 | crimp | TCD-35/8 | DIN 46235 | 005420

    Code: 005420
    Barcode: 8435157376876
  • Ring cable lug | 35mm² | M8 | crimp | TCD-35/8 | DIN 46235 | 005420

    TCD-35/8 – crimp ring cable lug 35 mm² for a copper conductor with a stud hole for an M8 bolt. Made to DIN 46235 – a standardised type of compression lug for copper conductors. Used to terminate a cable or wire end and connect it reliably to a terminal, busbar or device bolt.

    Key idea:
    The lug is selected by two values: conductor cross-section (35 mm²) and the size of the bolt it is connected to (M8). Lugs of this cross-section are typically used in distribution boards, incomers, inverters and battery circuits. A correctly crimped lug forms a mechanically strong, low-resistance connection.
    Conductor cross-section
    35 mm²
    Stud hole
    M8
    Connection
    crimp
    Series / marking
    TCD-35/8 (DIN 46235)

    Operating principle

    Insulation is stripped from the conductor to the depth of the lug barrel and the strands are pushed fully into the barrel.

    The barrel is crimped with a crimping tool using a die for 35 mm² (hexagonal dies are used for DIN 46235 lugs). During crimping the barrel deforms together with the conductor – a solid joint is formed without a screw contact on the strands.

    The ring part with the M8 hole is bolted to the terminal or busbar, and the crimp area is insulated with heat-shrink tubing.

    Why choose TCD-35/8?
    An exact cross-section and bolt combination (35 mm² / M8) – no need to enlarge the hole or crimp a wrong-size lug, so the joint stays reliable throughout its service life.

    Technical specifications

    Product typeCrimp ring cable lug
    Marking / codeTCD-35/8 / 005420
    SeriesTCD
    Conductor cross-section35 mm²
    Stud hole (bolt)M8
    Conductorcopper
    Connection methodcrimping
    StandardDIN 46235

    Main functions

    • Conductor termination – the 35 mm² conductor is secured and does not splay under the bolt.
    • Crimped joint – strong mechanical and electrical connection without an extra screw on the strands.
    • M8 stud hole – fits an M8 bolt or stud directly.
    • DIN 46235 – standardised dimensions make it easy to choose the crimping die.
    • Easy identification – cross-section and bolt size are given in the marking TCD-35/8.

    Where is it used?

    • Distribution and incoming panels
    • Earthing busbars
    • Inverters and solar plants
    • Battery and UPS circuits
    • Motor and compressor supply
    • Generator connection

    Use by need

    For the installing electrician.
    One clear 35 mm² / M8 combination – fewer errors when building a panel.
    For the equipment repair technician.
    A damaged or overheated lug is replaced with a product of the same size.
    For the designer and buyer.
    The DIN 46235 marking makes it easy to specify the lug precisely.

    Practical application

    If a 35 mm² copper cable has to be connected in a panel to a busbar or device with an M8 bolt, use TCD-35/8: strip the insulation, push the conductor into the barrel, crimp with a 35 mm² die and insulate the joint with heat-shrink tubing.

    Advantages

    • Exact cross-section and bolt combination
    • Reliable crimped joint
    • Suitable for copper conductors
    • Standardised to DIN 46235
    • Compact ring part

    Disadvantages / limitations

    • Uninsulated – the crimp area must be insulated with heat-shrink tubing
    • Requires a crimping tool and the correct die
    • Not suitable for aluminium conductors – use bimetallic lugs
    • A lug of the wrong cross-section will not form a reliable joint

    Safety and installation notes

    • Install only with the voltage disconnected and its absence verified
    • Use a die intended for 35 mm²
    • Push the conductor to the end of the barrel, leave no protruding strands
    • Do not crimp several conductors in one lug unless intended
    • Tighten the bolt to the torque specified by the equipment manufacturer
    • After installation, check that the joint does not heat up under load

    Quick selection guide

    35 mm²
    M8
    crimp
    TCD DIN 46235
    for copper
    Suitable when you need:
    • to terminate a 35 mm² copper conductor
    • to connect to an M8 bolt or stud
    • a durable crimped joint in a panel or device
    Check before use:
    • whether the conductor cross-section is exactly 35 mm²
    • whether the terminal bolt is M8
    • whether you have the right crimping tool and die
    • whether the conductor is copper (bimetallic lugs for aluminium)
    Important reminder: A lug does not replace insulation of the joint – cover the crimp area with heat-shrink tubing.

    FAQ

    How do I choose a ring lug?
    By the conductor cross-section (35 mm²) and the bolt size (M8) – both must match.
    Is it suitable for aluminium cable?
    No – bimetallic (Al/Cu) lugs are used for aluminium conductors.
    Which tool is used for crimping?
    Crimping pliers or a hydraulic press with a 35 mm² die.
    Can it be fitted to a larger bolt?
    No – the M8 hole is only for an M8 bolt; choose another lug for a different bolt.
    Does it need insulating?
    Yes – the lug is uninsulated; cover the crimp area with heat-shrink tubing.
    What is DIN 46235?
    It is a standard for compression lugs for copper conductors with defined dimensions.

    Ring cable lug | 35mm² | M8 | crimp | TCD-35/8 | DIN 46235 | 005420

    TCD-35/8 – crimp ring cable lug 35 mm² M8 to DIN 46235 for terminating copper conductors and connecting them to panels, busbars and equipment terminals.

    Published: 2026-11-12 · Parameters according to the supplier's specification: 2026-11-12

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • Alternative products

    Aluminium power cable | 4x35mm² | AXMK | Class 2 | 1m | black
    Code: AXMK 4x35

    AXMK 4x35mm² – a four-core aluminium power cable designed for fixed transmission and distribution of electrical energy in 0.6/1 kV networks. The cable features Class 2 aluminium conductors, XLPE core insulation, and a black UV-resistant PVC outer sheath. Suitable for installation indoors and outdoors, directly in the ground, in concrete, cable ducts, and protective conduits. Maximum operating temperature – 90 °C. 

    Price 6.05 € VAT incl.