  • Split-core current transformer | 1600/5 A | class 0,5 | 10 VA | busbar 85 × 165 mm | Schneider Electric PowerLogic GJ | METSECT5GJ160

    Code: METSECT5GJ160

    Split-core current transformer 1600/5 A, accuracy class 0,5, 10 VA, busbar, window 85 × 165 mm. IEC 61869-2.

  • Split-core current transformer | 1600/5 A | class 0,5 | 10 VA | busbar 85 × 165 mm | Schneider Electric PowerLogic GJ | METSECT5GJ160

    Schneider Electric PowerLogic GJ METSECT5GJ160 is a split-core current transformer 1600/5 A for meters and power analysers with a 5 A current input. The core opens, so it is fitted onto an already installed busbar without disconnection.

    Key point:
    The main value of a split-core CT is that metering can be added without stopping the site. METSECT5GJ160 offers accuracy class 0,5 and a 10 VA rated burden – make sure the meter input plus secondary lead losses stay within this value.
    Ratio
    1600/5 A
    Class / burden
    cl. 0,5 / 10 VA
    Window
    85 × 165 mm
    Mounting
    bolted; DIN rail / surface

    Operating principle

    The transformer is opened, placed around the busbar and closed – fixed with screws.

    Primary current up to 1600 A is transformed into a proportional secondary current up to 5 A fed to the meter or analyser current input.

    The ratio 1600/5 is set in the meter – the device shows the real current, power and energy.

    Why choose METSECT5GJ160?
    Metering is installed in an existing installation without disconnecting busbars, and class 0,5 suits energy metering and load analysis.

    Technical specifications

    Product type Split-core current transformer
    Manufacturer / code Schneider Electric / METSECT5GJ160
    Range / type PowerLogic, type GJ
    Ratio 1600/5 A
    Accuracy class 0,5
    Rated burden 10 VA
    Instrument security factor FS ≤ 10
    Short-time withstand 60 kA / 1 s
    Primary window busbar, window 85 × 165 mm
    Outer dimensions 195 × 243 × 79 mm
    Operating voltage Ue < 720 V, 50 Hz
    Insulation voltage Ui 3 kV (50 Hz, 1 min)
    Insulation class E
    Mounting bolted; DIN rail / surface
    Operating temperature −5…+40 °C
    Storage temperature −25…+70 °C
    Standards IEC/EN 61869-1, IEC/EN 61869-2

    Main functions

    • Split core – installation without disconnecting the busbars.
    • Ratio 1600/5 A – standard 5 A signal for meters and analysers.
    • Class 0,5 – suitable for energy metering and load monitoring.
    • 10 VA burden – reserve for the meter input and secondary leads.
    • FS ≤ 10 – limits secondary current during short circuits and protects the instrument.

    Where is it used?

    • Building or plant incomer metering
    • Retrofit of distribution boards without shutdown
    • PV plant and generator metering
    • Energy monitoring of production lines
    • Current inputs of analysers and PLCs
    • Energy management (EMS) systems

    Use by need

    For the installing electrician.
    Fitted without disconnecting the busbars – shorter work and fewer shutdowns.
    For the energy / facility manager.
    Quickly reveals real consumption and the largest loads.
    For the panel builder.
    The Schneider PowerLogic range pairs well with Acti9 iEM3000 and PM5000 meters.

    Practical use

    If metering must be added in a busbar system without stopping operations, fit a METSECT5GJ160 on each phase, connect the secondary circuit to the meter and set the ratio 1600/5. First check that the real maximum current matches the CT rated current.

    Pros

    • Installation without disconnection
    • Accuracy class 0,5
    • 10 VA rated burden
    • Complies with IEC 61869-2
    • Pairs with Schneider iEM3000 / PM5000

    Cons / limitations

    • Fixed ratio – select for the real load
    • Busbar only – for cables choose type HJ / HM
    • IP rating not stated by the manufacturer – install in a closed enclosure
    • Operating temperature up to +40 °C

    Safety and installation notes

    • Never open the secondary circuit while primary current flows – short the leads or keep them connected to the instrument.
    • Observe the current direction marking (P1→P2) – otherwise power and energy are calculated wrongly.
    • Orient CTs identically on all phases and keep the phase sequence.
    • Fit only on insulated conductors or with the voltage switched off.
    • Installation must be done by a qualified electrician.

    Quick selection guide

    1600/5 A
    cl. 0,5
    10 VA
    85 × 165 mm
    FS ≤ 10
    IEC 61869-2
    Suitable when you need:
    • Metering in an existing board without shutdown
    • Connecting a meter or analyser with a 5 A input
    • Measuring currents up to 1600 A
    Check before use:
    • Busbar dimensions
    • Meter input burden and lead losses (total ≤ 10 VA)
    • Whether the meter supports an x/5 A ratio setting
    Important reminder: A current transformer does not protect the line and does not measure energy by itself – it needs a meter or analyser.
    ☝ Elsprendimai.eu recommends:
    • Schneider Acti9 iEM3250 / iEM3255 3-phase CT meter
    • Schneider PowerLogic PM5110 power analyser
    • Other PowerLogic HJ / HM / GJ ratios

    FAQ

    Do I need to disconnect the busbars?
    No – the core opens and the CT fits onto the existing conductor.
    What is the accuracy class?
    Class 0,5, rated burden 10 VA.
    Which meter does it suit?
    Meters and analysers with a 5 A current input.
    Does it fit a cable?
    No – type GJ is for busbars.
    What is the operating temperature?
    −5…+40 °C.
    Which standard?
    IEC/EN 61869-1 and IEC/EN 61869-2.

    Documents

    Split-core current transformer | 1600/5 A | class 0,5 | 10 VA | busbar 85 × 165 mm | Schneider Electric PowerLogic GJ | METSECT5GJ160

    Schneider Electric PowerLogic GJ METSECT5GJ160 – split-core current transformer 1600/5 A, class 0,5, 10 VA, busbar, window 85 × 165 mm. Metering retrofit in existing installations without disconnection.

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • Alternative products

  • Subscribtion to new arrivals

    privacy policy

    Information