Electric current transformers

  • KibirkštisFazė
    Not sure which current transformer ratio, class or type you need? The most common mistakes are too high a ratio, ignored lead losses and an output that does not match the instrument – the selection guide gives you a 30-second table, a calculation and diagrams.
  • Current transformer and Rogowski coil guide: ratio, accuracy class, burden and type

    This guide gives you quick ratio selection based on the incoming supply current, a decision by situation, a comparison of four measurement technologies and five selection rules, including a cable loss calculation. It also contains a matrix of all products in the group, a checklist, wrong-connection diagrams and practical questions and answers. The group includes solid-core X/5 A current transformers, split-core current transformers with 5 A and 333 mV outputs, flexible and rigid Rogowski coils with their integrators, panel multimeters supplied with current transformers, and a medium-voltage current transformer. Exact parameters are given in each product description.

    Colour key: ■ information · ■ benefit, solution · ■ ⚠ check · ■ ⚡ safety, mistakes

    ☝ ELSprendimai recommends: selection in 30 seconds →
    Know the rating of your incoming circuit breaker? The table shows the ratio and suitable products straight away.

    Selection in 30 seconds: ratio by incoming current

    Find the row that matches the rated current In of the line circuit breaker or the highest measured load current. The second column gives the recommended current transformer (CT) ratio, the third shows suitable products in this group.

    In / Imax Ratio What to choose in the group
    up to 63 A 75/5 A or 100/5 A solid-core X/5 A; without disconnecting the cable – split-core 100 A with 333 mV output or multimeter with 3 CTs
    100 A 100/5 A or 150/5 A solid-core X/5 A; in damp environments – sealed split-core IP67, 5 A output, 100–200 A
    125–160 A 200/5 A solid-core 200/5 A, class 0.5; for an existing cable – split-core 200/5 A, class 1, for Ø18 mm cable
    250 A 250/5 A or 300/5 A solid-core X/5 A; for an existing cable – split-core CTs
    400 A 400/5 A solid-core 400/5 A, class 1; for an existing cable – split-core 400/5 A
    630 A 600/5 A (750/5 A if the load stays close to 630 A for long periods) solid-core 600/5 A, class 1; for an existing cable – split-core 600/5 A, class 0.5, for Ø42 mm cable
    800 A 800/5 A split-core 800/5 A, class 0.5; for a monitoring module – split-core 800 A with 333 mV output
    1000 A 1000/5 A solid-core 1000/5 A, class 0.5, 15 VA
    1250–1600 A 1500/5 A or 1600/5 A solid-core 1500/5 A, class 0.5; busbar without dismantling – split-core 1600/5 A for 85×165 mm busbar
    2000–4000 A 4000/5 A or Rogowski coil solid-core 4000/5 A, class 0.5; for tight spaces – flexible Rogowski coil + integrator with 5 A output
    Rule: choose the ratio by the highest continuous current, not by the transformer or cable rating. The operating current should be 20–100 % of the CT rated current – below 5–20 % the error rises sharply. For a power factor controller, the CT is sized to the incoming circuit breaker and installed on the incomer upstream of all outgoing feeders – see the reactive power compensation guide.

    What do you need? Quick selection

    Situation Solution Where to look
    New panel: sub-metering, power analyser or meter with a 5 A input Solid-core CT X/5 A, class 0.5; rated burden (VA) based on cable length (see the calculation) Solid-core CTs
    Power factor (reactive power compensation) controller One X/5 A CT on an incomer phase, class 1 is sufficient; ratio based on the incoming circuit breaker Solid-core CTs, compensation guide
    The cable or busbar cannot be disconnected Split-core CT: clamps around the conductor without disconnection; 5 A output – for standard instruments Split-core CTs
    Energy monitoring module, IoT meter with a 333 mV input Split-core CT with 333 mV output or a 3-in-1 kit with RJ45 connector Split-core CTs, 3-in-1 kit
    High currents, wide busbars, several parallel conductors, tight space Flexible Rogowski coil + integrator with the required output (5 A, 4–20 mA or 333 mV) Flexible coils, integrators
    Temporary measurement, energy audit, fault finding Flexible Rogowski coils with an analyser; for a one-off measurement, renting pays off Flexible coils, analyser rental
    Damp or outdoor environment Sealed IP67 CTs or IP67/IP68 Rogowski coils Sealed CT, IP68 coil
    Simple current and voltage display on the panel door Panel multimeter supplied with 3 matched CTs Multimeters with CTs
    Medium-voltage (6–24 kV) installation MV current transformer or rigid Rogowski coil; for MV-qualified personnel only Rigid coils, MV CT

    How it works: four measurement technologies

    A current transformer reduces a high primary current to a safe, standardised value that an instrument can measure. It measures current only: voltage, power and cos φ are calculated by the connected instrument, which also receives a voltage signal. The group covers four technologies.

    Solid-core CT
    X/5 A
    Closed ferromagnetic core. The most accurate and the cheapest, but the conductor has to be passed through the window – for new panels.
    Split-core CT
    X/5 A · X/1 A
    The core opens and clamps around an existing cable or busbar. Installed without disconnection, accuracy class 0.5–1.
    CT with mV output
    333 mV
    Burden resistor built in. Safe to disconnect, but connects only to an instrument with an mV input.
    Rogowski coil
    mV/kA
    Air-cored coil: does not saturate, light and flexible. Needs an integrator and measures AC only.
    Feature Solid-core Split-core X/5 A mV output Rogowski
    Output 5 A (or 1 A) 5 A or 1 A 333 mV at In mV/kA (e.g. 50 or 85 mV/kA) → integrator
    Installation conductor passed through the window on an existing cable or busbar on an existing cable wrapped around a cable, busbar or bundle
    Measuring range up to ~120 % In up to ~120 % In up to In from tens of A to kA; no saturation
    Open secondary circuit ⚡ dangerous ⚡ dangerous safe safe
    Typical use metering, analysers, controllers refurbishment, upgrades monitoring modules, IoT high currents, audits, tight spaces
    ⚡ The most important safety rule. Never open the secondary circuit of a CT with a 5 A or 1 A output while current flows in the primary conductor: a dangerous voltage appears at the output, the core overheats and the insulation can fail. Short-circuit the secondary before disconnecting the instrument – most conveniently via a test terminal block. This risk does not apply to mV-output CTs and Rogowski coils.

    Selection rules: 5 steps

    1. Ratio by the highest current

    Primary rated current – the nearest standard value not lower than the highest continuous load current or the line circuit breaker In. Too high a ratio degrades accuracy at low currents; too low – the CT overheats and no longer measures peaks. Table – in 30 seconds.

    2. Accuracy class by application

    Per IEC 61869-2: 0.2S / 0.5S – billing (revenue) metering (accuracy maintained from 1 % In); 0.5 – sub-metering and power analysers (±0.5 % at 100–120 % In, ±1.5 % at 5 %); 1 – power factor controllers, panel meters (±1 % at 100–120 %); 3 – indication only. For billing metering, CTs must be metrologically verified and approved by the grid (distribution system) operator.

    3. Rated burden (VA) including cable losses

    The rated burden must cover the instrument input, the I²·R losses in the connecting leads and the terminal contacts. Class accuracy is guaranteed when the actual burden is between 25 and 100 % of the rated burden – so an excessive VA margin is not good either. In a 5 A circuit, cable losses are 25 times higher than in a 1 A circuit, so for leads longer than ~10 m an X/1 A CT is worth considering. Example – calculation.

    4. Window to fit the conductor

    Check that the cable with its insulation (outer Ø) or the busbar (width × thickness) will fit. Several parallel conductors through one window – same phase only. Window dimensions are given on the product page.

    5. Output to match the instrument

    The instrument input must match the CT output: 5 A, 1 A, 333 mV or Rogowski mV/kA. The Rogowski coil sensitivity (e.g. 50 or 85 mV/kA) must match the integrator setting. Three-phase measurement needs 3 identical CTs – one per phase.

    Burden calculation: is 2.5 VA enough?

    Example: 400 A incomer, 400/5 A CT, analyser installed 6 m from the CT, Cu 2.5 mm² connecting leads, instrument current input burden 0.2 VA. Copper resistivity ρ = 0.0175 Ω·mm²/m, loop length – out and back (2 × 6 m).

    Component Calculation Result
    Lead resistance R = 0.0175 × 12 / 2.5 0.084 Ω
    Lead losses, 5 A P = 5² × 0.084 2.1 VA
    Instrument input per instrument data 0.2 VA
    Terminals and contacts indicative margin ~0.2 VA
    Total   ~2.5 VA
    Same with an X/1 A CT P = 1² × 0.084 + 0.2 + 0.2 ~0.5 VA
    Conclusion: a 2.5 VA CT would be working at its limit – choose 5 VA (the burden will be ~50 % of rated, accuracy guaranteed). For longer distances, increase the lead cross-section to 4 mm² or choose an X/1 A CT and an instrument with a 1 A input.

    Selection matrix: all products in the group

    Choose a situation – the matching rows will be highlighted:

    Product Type Key data When to choose Note
    Solid-core CTs X/5 A
    200/5 A solid-core CT class 0.5; 2.5 VA; housing 62/40 mm circuits up to 160 A, analysers leads up to ~4 m (2.5 mm²)
    400/5 A solid-core CT class 1; 5 VA; housing 62/40 mm power factor controllers, panel meters for metering choose class 0.5
    600/5 A solid-core CT class 1; 7.5 VA; housing 100/60 mm incomers 500–630 A higher VA – for longer leads
    1000 · 1500 · 4000/5 A solid-core CT class 0.5; 15 VA; housing 140/100 mm main incomers, busbars 15 VA allows long leads
    Test terminal block secondary circuit terminal block for current and voltage circuits; 25 A, 400 V AC for every metering or analyser circuit safe CT short-circuiting
    Split-core CTs X/5 A
    200/5 A, for Ø18 mm cable split-core CT class 1; 1 VA; IP20 upgrades, adding a controller CT low VA – short leads
    600/5 A, for Ø42 mm cable split-core CT (Schneider PowerLogic) class 0.5; 2.5 VA analyser in an existing panel  
    800/5 A, 2 × Ø42 mm split-core CT class 0.5; 0.5 VA; IP20 two parallel conductors of the same phase short leads to the instrument only
    1600/5 A, for 85×165 mm busbar split-core CT (Schneider PowerLogic) class 0.5; 10 VA main busbar without dismantling  
    100–200 A, Ø36 mm, IP67 sealed split-core CT 5 A output; 2 m cable damp or outdoor environment  
    Split-core CTs with mV and mA output
    100 A, Ø36 mm · 800 A, Ø50 mm split-core CT 333 mV at In; 1 m cable energy monitoring modules 333 mV input only
    3-in-1, 100 A set of 3 CTs 333 mV; RJ45 / RJ12 three-phase monitoring module with RJ connector check connector compatibility
    Ø16 mm, mA output high-accuracy split-core CT low currents up to 5 A; 2 m cable sub-metering of small loads matched input only
    Rogowski coils
    Ø50 mm, IP67 · Ø100 mm, IP68 flexible coil up to 1000 A; 2 m cable tight spaces, damp environments integrator required
    Ø100 mm, 85 mV/kA flexible coil 1000 A; ≤0.5 %; IP67 calibrated measurements, audits centre the conductor
    3-in-1, 600 A set of 3 flexible coils 50 mV/kA; RJ45 / RJ12 three-phase monitoring without disconnection  
    Ø100 mm, rigid rigid coil 2 m cable fixed installation, stable geometry lower position error
    MV rigid coils MV rigid coil up to 10–24 kV medium-voltage switchgear MV qualification only
    Rogowski coil integrators
    5 A output, 24 V DC single-phase DIN integrator 50 A–20 kA; class 0.5; ≤15 W Rogowski coil instead of an X/5 A CT for any instrument 24 V DC supply
    5 A output DIN integrator up to 15 W power factor controller or meter with a 5 A input  
    4–20 mA · 1 A / 4–20 mA three-phase DIN integrator for 50 mV/kA coils PLC, SCADA analogue inputs  
    333 mV three-phase DIN integrator for 50 mV/kA coils; 5 W monitoring modules with a 333 mV input  
    Multimeters with CTs and MV CTs
    100 A · 400 A · 10–100 A panel multimeter + 3 CTs current, voltage, frequency, power simple display on the panel door use only the CTs supplied in the kit
    600/5 A (ABB) MV current transformer for indoor installation MV switchgear MV qualification only

    All products in the group – solid-core, split-core, flexible coils, rigid coils, integrators and multimeters with CTs. Prices and availability – on the product pages.

    ⚠ What to check before buying

    • The highest continuous current and the line circuit breaker In – they determine the ratio.
    • The instrument current input: 5 A, 1 A, 333 mV or Rogowski – it must match the CT output.
    • The accuracy class for the application: 0.5 for metering and analysers, 1 for controllers.
    • The length and cross-section of the connecting leads – whether the CT rated burden (VA) is sufficient.
    • The cable outer diameter including insulation, or the busbar dimensions – whether it fits the window.
    • The installation point: can the conductor be passed through (solid-core), or is a split-core CT needed?
    • The environment: IP rating in damp or outdoor locations, operating temperature.
    • Quantity: three-phase measurement needs 3 identical CTs.
    • For billing metering – metrological verification and the grid operator’s requirements.

    ✗ The most common mistakes

    Mistake Consequence and how to avoid it
    Instrument disconnected without short-circuiting the CT secondary ⚡ Dangerous voltage at the terminals, core overheating. Always short-circuit via a test terminal block.
    Ratio chosen by transformer rating Operating current at 5–10 % In – the error is several times the class limit. Choose by the actual load.
    Lead losses not taken into account Rated VA exceeded – readings drop and are distorted. Calculate I²·R or choose X/1 A.
    Reversed P1 ↔ P2 orientation The analyser shows negative kW, the controller a capacitive cos φ. P1 – towards the supply side.
    CT phase does not match the voltage phase Wrong power and cos φ, even though the current reads correctly. CT on L1 – with voltage L1.
    Whole cable (L1, L2, L3, N) through one CT The phase currents sum to ≈ 0 – the CT shows nothing. Each phase – through its own CT.
    Rogowski coil and integrator sensitivity do not match E.g. an 85 mV/kA coil with a 50 mV/kA integrator – readings ~70 % too high.
    mV-output CT connected to a 5 A input The instrument shows nothing. mV CTs – to an mV input only.

    Wrong connections: wrong and correct

    ⚠ The diagrams are illustrative. They are not wiring diagrams. Connection must be carried out by a certified electrician according to the design and the instrument manufacturer’s instructions. UAB „Elektrotechnikos sprendimai“ accepts no liability for the connection or installation of equipment.

    1. CT orientation: P1 and P2

    ✗ WRONG✓ CORRECTsupplyloadP2P1CTP1 towards load – negative power shownsupplyloadP1P2CTP1 towards supply – correct direction

    Diagram. P1 marks the side of the primary terminal facing the supply source. If the CT is reversed, the instrument sees the current with a 180° phase shift: power becomes negative and the power factor controller switches stages incorrectly.

    2. Secondary circuit: disconnection and earthing

    ✗ WRONG✓ CORRECTCT X/5 Ainstrument⚡ open circuitleads removed under current – dangerousCT X/5 Atest terminal blockshorting linkinstrumentS2 – earthed at one pointshorted at terminal block, then removed

    Diagram. Left – the instrument leads are disconnected while primary current flows: a dangerous voltage appears in the secondary circuit. Right – the CT is first short-circuited at the test terminal block and only then is the instrument disconnected; S2 is earthed at a single point if the design or the instrument instructions require it.

    3. Three-phase measurement: one or three CTs

    ✗ WRONG✓ CORRECTL1L2L3NΣ I ≈ 0 Aall cores through one window – reads ~0L1CT 1L2CT 2L3CT 3each phase – its own CT

    Diagram. Left – the whole cable is passed through one CT: the phase currents cancel each other out and the CT reads close to zero. Right – each phase is passed through its own CT.

    Faults and fixes: symptom → cause → what to do

    Symptom Likely cause What to do
    The analyser shows negative active power on one phase CT reversed or S1/S2 leads swapped Check the P1 orientation and the S1/S2 connection in that phase circuit
    Power and cos φ make no sense, currents are correct CT and voltage phases mixed up Check phase matching: CT L1 – voltage L1, and so on
    Readings consistently too low, especially at high load CT rated burden (VA) exceeded due to long or thin leads Recalculate the burden, increase the cross-section or choose a higher-VA or X/1 A CT
    Low-current readings fluctuate or show zero Ratio too high; current below 5 % In Reduce the ratio or choose class 0.5S
    Split-core CT readings deteriorated after installation Dirty or not fully closed core joints Clean the core faces and close the core until it latches
    Rogowski readings vary by a few percent as the coil is moved Conductor off-centre or the coil closure near another phase Centre the conductor and keep the closure away from adjacent conductors

    Frequently asked questions

    Kibirkštis asks – a young, curious electrician who dares to ask what others won’t. Fazė answers – an experienced engineer.

    Kibirkštis
    Kibirkštis
    What CT ratio do I need?
    Fazė
    Fazė
    Based on the highest continuous current or the line circuit breaker: 200/5 A for a 160 A breaker, 400/5 A for 400 A, 600/5 A for 630 A. The operating current should be 20–100 % of the CT rated current. Full table – in 30 seconds.
    Kibirkštis
    Kibirkštis
    What is the difference between class 0.5 and class 1?
    Fazė
    Fazė
    The permissible ratio error at rated current: ±0.5 % and ±1 %. At low current the error increases: at 5 % In, class 0.5 allows ±1.5 % and class 1 allows ±3 %. Use 0.5 for analysers and sub-metering; class 1 is enough for a power factor controller.
    Kibirkštis
    Kibirkštis
    What does VA mean and how much do I need?
    Fazė
    Fazė
    It is the burden the CT can supply to the secondary circuit without losing its accuracy class. Add up the instrument input and the I²·R lead losses: 6 m to the instrument with 2.5 mm² leads in a 5 A circuit is ~2.1 VA for the leads alone. See the calculation.
    Kibirkštis
    Kibirkštis
    5 A or 1 A secondary current?
    Fazė
    Fazė
    If the instrument is close (up to ~10 m) – 5 A, as it is the standard for most instruments. With long leads, losses in a 1 A circuit are 25 times lower. The instrument must have a 1 A input.
    Kibirkštis
    Kibirkštis
    Can I disconnect the analyser without short-circuiting the CT?
    Fazė
    Fazė
    No, not if the CT has a 5 A or 1 A output and the line is under load – a dangerous voltage appears at the open terminal. Short-circuit the circuit at the test terminal block first. mV-output CTs and Rogowski coils are safe.
    Kibirkštis
    Kibirkštis
    When is a Rogowski coil better than a CT?
    Fazė
    Fazė
    When currents are high (kA), busbars are wide or there are several parallel conductors, space is tight or the measurement is temporary. The coil does not saturate and weighs little. However, it needs an integrator with the correct sensitivity, it cannot measure DC and it is more sensitive to conductor position.
    Kibirkštis
    Kibirkštis
    Is a split-core CT as accurate as a solid-core one?
    Fazė
    Fazė
    Quality split-core CTs reach class 0.5, but their rated burden (VA) is usually lower and their accuracy depends on clean, firmly closed core joints. In a new panel, a solid-core CT is cheaper and more accurate.

    Related guides

    The measuring circuit also needs an instrument, cables and a panel – these guides will help you choose them:

    Sources

    Standards and manufacturer data used in this guide.

    • IEC 61869-1 / -2 – Instrument transformers: general requirements and current transformers (accuracy classes, rated burden)
    • IEC 61869-10 – Low-power passive current transformers (mV-output CTs and Rogowski coils)
    • IEC 61557-12 – Power metering and monitoring devices (PMD)
    • Schneider Electric – PowerLogic split-core CT technical data (se.com)
    • Manufacturer technical data in the product descriptions – solid-core and split-core CTs, Rogowski coils and integrators
    • Lithuanian Rules for the Supply and Use of Electricity – billing metering requirements

    Published: 2026-11-04 · Data checked against manufacturer specifications: 2026-11-04

    Disclaimer. This guide, its diagrams and calculations are for information only – they are not a design, wiring diagram or installation instructions. Current transformers must be selected, connected and commissioned by a qualified, certified electrical professional in accordance with the design, the manufacturer’s instructions and applicable legislation. UAB „Elektrotechnikos sprendimai“ accepts no liability for the selection, connection, installation or operation of equipment based on this guide, or for any resulting damage.