Selector switch guide: knob or key, 2 or 3 positions, maintained or spring return
Here you will find quick selection by situation, 5 solution levels from a plastic selector switch to a key switch, position and contact logic, a MANUAL–0–AUTO mode diagram and the most common mistakes. Exact parameters are given in each product description.
Colour meanings: ■ information · ■ benefit, solution · ■ ⚠ check · ■ ⚡ safety, mistakes
What do you need? Quick selection
|
Situation |
Solution |
Where to look |
|
Simple ON–OFF on a panel door in a dry room |
Knob selector switch, 2 positions 0-1, maintained |
plastic 0-1, metal 0-1 |
|
MANUAL–0–AUTO modes for a pump, fan or compressor |
3-position 1-0-2 selector switch, maintained, with 2NO contacts |
plastic 1-0-2, metal 1-0-2 |
|
You need to see that the selected mode is active |
Illuminated 3-position selector switch. The LED voltage must match the control voltage |
green LED 230 V, green LED 24 V, red LED 230 V |
|
Short command only while held: JOG, OPEN–CLOSE, LEFT–RIGHT |
Spring-return selector switch, returns to 0 when released |
plastic 3-pos. spring return, metal 3-pos. spring return, metal 2-pos. spring return |
|
Only an authorised person may switch on: service, public area, lockout |
Key selector switch, 2 positions 0-1 |
key, plastic, key, metal |
|
Anyone can stop, but only a key holder can restart |
Mushroom STOP button released with a key |
mushroom with key |
|
You need to start and stop a motor |
This is a job for push buttons, not a selector: START–STOP with contactor self-holding |
Push button guide |
|
The switch is mounted at the machine, not in a panel |
Selector switch plus push button enclosure (1–3 positions) |
push button enclosures |
The right selector switch means four decisions: operation (knob or key), number of positions (2 or 3), action (maintained or spring return) and indication (with or without LED). The number of contacts follows from the positions: 1NO is enough for 2 positions, 3 positions need 2NO.
From basic to secure: 5 solution levels
Start at level 1 and move up only when the environment or function requires it. A key or LED is not “better” everywhere. They are needed only where they prevent a mistake or show the status.
LEVEL 3
With LED illumination
For: when the operator must see the selected mode or operation
What you get: switch and indicator in one, 24 V or 230 V, 3 positions
Price from 5.03 € incl. VAT
230 V: green · red · green, plastic
24 V: green · red
LEVEL 4
With key
For: service, public sites, equipment that outsiders must not switch on
What you get: position changed only with the key, 2 positions 0-1
Price from 4.17 € incl. VAT
plastic · metal
LEVEL 5
Mushroom STOP with key
For: anyone can stop, but only an authorised person can restart
What you get: latching NC mushroom released with a key
Price from 4.38 € incl. VAT
mushroom STOP with key
Positions and action: how they work
|
Type |
How it works |
Where to use |
|
2 positions 0-1, maintained |
The knob stays where you turned it: 0 – off, 1 – on |
ON–OFF, lighting group, heating, ventilation without contactor self-holding |
|
2 positions 0-1, spring return |
Position 1 works only while held, the released knob returns to 0 |
Pulse: e.g. ACKNOWLEDGE, JOG, short start |
|
3 positions 1-0-2, maintained |
Left (1), centre (0), right (2), each position stays |
MANUAL–0–AUTO, SUMMER–0–WINTER, pump 1 or 2 |
|
3 positions 1-0-2, spring return |
1 and 2 work only while held, return to 0 when released |
OPEN–CLOSE, UP–DOWN, LEFT–RIGHT |
|
With key |
The position can be changed only by inserting and turning the key |
Service, enable permission, public sites |
KibirkštisWhy can’t I just take a maintained 3-position switch and use it for OPEN–CLOSE?
FazėYou can, but then the gate or damper will keep moving until someone returns the knob to 0. Without limit switches the drive will reach the end and overheat. A spring-return switch stops the movement as soon as you let go.
Contacts: what closes in each position
Our selector switches have NO contacts. A 3-position switch has two NO contacts (2NO): one closes in position 1, the other in position 2. In the centre (0) both are open, so both modes can never be on at the same time.
|
Position |
Contact A |
Contact B |
|
1 |
closed |
open |
|
0 |
open |
open |
|
2 |
open |
closed |
A 2-position switch (0-1) has one NO contact: open in position 0, closed in position 1.
⚠ Check the terminal marking (e.g. 13–14, 23–24) and which side is “1” on the specific product before wiring.
LED illumination: what voltage do you need?
The LED of an illuminated selector switch is powered from the control circuit, so its voltage must match the control voltage: for 24 V control choose LED 24 V, for 230 V control – LED 230 V. A 24 V LED on 230 V burns out instantly, and a 230 V LED on 24 V will not light.
Selection matrix: all selector switches in the group
All selector switches mount in a Ø 22 mm hole, front protection degree IP40, standard IEC/EN 60947-5.
|
Product |
Operation |
Positions |
Action |
Contacts |
LED |
Ring |
Price |
|
View |
knob |
0-1 |
maintained |
1NO |
— |
plastic |
2.11 € |
|
View |
knob |
1-0-2 |
maintained |
2NO |
— |
plastic |
3.17 € |
|
View |
knob |
1-0-2 |
spring return |
2NO |
— |
plastic |
3.17 € |
|
View |
knob |
0-1 |
maintained |
1NO |
— |
metal |
3.21 € |
|
View |
knob |
0-1 |
spring return |
1NO |
— |
metal |
3.21 € |
|
View |
knob |
1-0-2 |
maintained |
2NO |
— |
metal |
3.82 € |
|
View |
knob |
1-0-2 |
spring return |
2NO |
— |
metal |
3.82 € |
|
View |
knob, green |
1-0-2 |
maintained |
2NO |
LED 230 V |
plastic |
5.03 € |
|
View |
knob, green |
1-0-2 |
maintained |
2NO |
LED 230 V |
metal |
6.55 € |
|
View |
knob, red |
1-0-2 |
maintained |
2NO |
LED 230 V |
metal |
6.55 € |
|
View |
knob, green |
1-0-2 |
maintained |
2NO |
LED 24 V |
metal |
6.55 € |
|
View |
knob, red |
1-0-2 |
maintained |
2NO |
LED 24 V |
metal |
6.55 € |
|
View |
key |
0-1 |
maintained |
1NO |
— |
plastic |
4.17 € |
|
View |
key |
0-1 |
maintained |
1NO |
— |
metal |
4.66 € |
⚠ What to check before buying
KibirkštisBefore ordering a selector switch I always check these things, otherwise I have to make a second trip.
|
What to check |
Why it matters |
|
Number of positions: 0-1 or 1-0-2 |
Two modes plus OFF need 3 positions |
|
Maintained or spring return |
Modes – maintained, movement commands – spring return |
|
Number of contacts |
3 positions need 2NO. If you need a signal to a controller, plan an additional contact block |
|
Knob or key |
A key is needed when only an authorised person may switch on or change the mode |
|
LED voltage |
Must match the control circuit: 24 V or 230 V |
|
Hole diameter |
Standard Ø 22 mm. Older 30 mm panels need another solution |
|
Environment |
IP40 is suitable for dry rooms. Outdoors and in washdown areas a sealed enclosure is needed |
✗ Most common mistakes
|
Mistake |
Consequence |
|
Maintained ON switch instead of START–STOP buttons for a motor |
When voltage drops and returns, the motor starts by itself. If this endangers people, use push buttons with contactor self-holding |
|
Two separate MANUAL and AUTO switches |
Both modes can be switched on at the same time. A 3-position 1-0-2 switch prevents this |
|
MANUAL mode bypasses the thermal relay or dry-run protection |
In manual mode the pump can burn out or run dry |
|
Maintained switch for movement commands |
The gate or damper keeps moving until someone returns the knob. A spring-return switch is needed |
|
The switch switches motor current directly |
Contacts burn. The switch controls the contactor coil, not the motor |
|
LED voltage does not match the control voltage |
The LED burns out or does not light |
⚡ Safe installation – Fazė’s advice
-
Before installation, disconnect the panel and verify that there is no voltage.
-
Protect the control circuit with a separate circuit breaker or fuse according to the wire cross-section.
-
Wire the thermal relay contact and dry-run protection so that they work in both modes: MANUAL and AUTO.
-
Stick a position label on the switch (e.g. MAN – 0 – AUTO) so that the operator does not make a mistake.
-
Metal doors must be connected to PE.
Diagram: pump MANUAL–0–AUTO modes – wrong and right
The pump is controlled by contactor KM. In AUTO mode it is switched on by an automation contact (float switch, pressure switch or controller). The numbers match the explanations below the diagram.

✗ Wrong
L
no protection 3
→
MAN switch
separate 0-1 1
AUTO switch
separate 0-1 1
→
KM coil
no thermal relay 2
1 Both modes can be switched on at the same time 2 Manual mode bypasses overload protection 3 Control circuit without its own protection
✓ Right
L
breaker / fuse 3
→
Thermal relay
95–96 NC 2
→
Selector 1-0-2
1 = MAN · 0 · 2 = AUTO 1
→
2 = AUTO
via automation contact
→
KM coil
A1–A2 → N
1 One 3-position switch: both modes at once are impossible 2 The thermal relay protects in both modes 3 Separate protection for the control circuit
The diagram is a simplified schematic and may contain inaccuracies. Before wiring, check against the manufacturer’s instructions and the markings on the devices. The qualified electrician performing the installation is responsible for it. UAB „Elektrotechnikos sprendimai“ is not liable for the wiring or possible errors.
Why – explanation by diagram numbers
1 ✗ Two separate switches → ✓ One 1-0-2 selector switch
Why: a 3-position switch physically prevents both modes from being on, and position 0 clearly means “off”.
2 ✗ Manual bypasses protection → ✓ Thermal relay contact before the selector
Why: overload and dry running are dangerous in both modes, so protection must be in the common part of the circuit.
3 ✗ Control without its own protection → ✓ Separate breaker or fuse
Why: thin control wires must be protected according to their own cross-section.
Frequently asked questions
Questions from Kibirkštis – a young, curious electrician. Answers from Fazė – an experienced master.
KibirkštisWhat is the difference between a knob and a key selector switch?
FazėAnyone can turn a knob, but only the key holder can turn a key switch. A key is suitable where switching on or changing the mode must be controlled, e.g. a
metal key selector switch.
KibirkštisCan I switch a pump directly with a selector switch?
FazėNo. A selector switch is intended for the control circuit. Connect the pump via a
contactor with a thermal relay and let the switch control only the coil.
KibirkštisWhen should I choose a selector switch and when START–STOP buttons?
FazėA selector switch is suitable for modes and equipment that can safely restart by themselves after a power loss (ventilation, lighting, heating). For motors that must not restart by themselves, use
push buttons with contactor self-holding.
KibirkštisWhy does a 3-position switch have 2NO contacts?
FazėEach position (1 and 2) needs its own contact. In the centre (0) both are open, so both modes cannot be on together.
KibirkštisIs an illuminated selector switch always lit?
FazėThe LED lights when control voltage is applied to it. How you connect the LED (e.g. in parallel with the contactor coil) determines what status it shows. The LED voltage must match the control voltage.
KibirkštisDo you help select control devices for a whole panel?
FazėYes. Send the diagram or list of functions, the control voltage and ambient conditions. We will select selector switches, buttons, lamps, contactors and protection and send a quote.
Contact us.
Other related guides: Push button guide · Exit door button guide · All product selection guides
Sources
-
EN 60204-1 – Electrical equipment of machines (control devices, protection against unexpected start-up)
-
IEC/EN 60947-5-1 – Control circuit devices and switching elements
-
Promfactor Baltic FP series manufacturer data and product marking
This guide is for information purposes and does not replace a design, a risk assessment or the manufacturer’s instructions. UAB „Elektrotechnikos sprendimai“ accepts no liability for product selection based on this guide. The final decision is made by the designer or a qualified electrician. Published: 2026-11-06.
Selector switches, buttons, lamps and contactors – in one order
Send a diagram or a list and we will prepare a quote. Model not in the catalogue? Some products are supplied to order.
Get a quote +370 658 01033