Product Catalog
- Security and Surveillance Systems | accessories
- Lighting solutions for industrial | commercial | residential | outdoor environments | accessories
- Automation and Control Systems
- Smart Automated Products | Control | Transmission | Detection
-
Electrical distribution and installation
- Reactive Power Compensation Devices
- Electrical power | power cables | wires with copper conductors
- Electrical Distribution Panels, Boxes & Accessories
- Modular equipment installed in electrical distribution boxes | panels
- Smart electrical network analyzers
- Reliable power management | stabilization | control | uninterrupted supply
- Fuse holder blocks
- Fuse disconnectors
- Fuses
- Electrical installation components
- Electric current transformers
- For domestic | professional use Extension cords | power supply extensions
- Industrial | domestic socket outlets | plugs | adapters for electricity supply
- High Voltage Equipment | Components 6kV | 10kV | 12kV | 20kV
- Underground Power Transmission | Overhead Power Lines
- Surge Protection and Lightning Protection
- Solar Energy Generation and Management Equipment
- HVAC control solutions for heating and ventilation
- Accessories for cars
- Workplace Safety | Electrical Safety Equipment | LOTO
- Technical maintenance | service equipment | fire protection solutions
- Emergency safety | hygiene | sanitary solutions
- Other products
- Quality used products
Fuses
-

Not sure which fuse size and current or which fuse switch disconnector you need? The selection guide gives you a 30-second table from 5×20 mm to NH4a, the cable protection rule In ≤ 0.9 Iz, selectivity and safe replacement diagrams. -
Read more
Fuse and fuse switch disconnector guide: size, gG / aM class, current and fuse holder
This guide gives you quick fuse size and fuse holder selection based on the circuit current, five solution levels from control circuits to incoming busbars, a comparison of fuse classes and the cable protection rule with a calculation. It also contains a matrix of all products in the group, the selectivity rule, a checklist, wrong-solution diagrams and practical questions and answers. The group includes cylindrical fuses 8×32, 10×38, 14×51 and 22×58 mm, NH000–NH4a NH (blade) fuses, E27 screw-in plug fuses, modular fuse disconnectors for DIN rail, horizontal and vertical NH fuse switch disconnectors for mounting plate or busbars, and their accessories. Exact parameters are given in each product description.
Colour key: ■ information · ■ benefit, solution · ■ ⚠ check · ■ ⚡ safety, mistakes
Contents: In 30 seconds · Solution levels · What do you need? · How it works · Selection rules · Calculation · Selection matrix · What to check · Mistakes · Wrong solutions · Faults and fixes · FAQ · Related guides · Sources☝ ELSprendimai recommends: selection in 30 seconds →
Know the circuit current? The table shows the fuse size and a suitable fuse holder or fuse switch disconnector straight away.Selection in 30 seconds: fuse size and fuse holder by current
Find the row that matches the required fuse rated current In (it is determined by the cable and the load – see the rules). The second column gives the fuse size, the third shows the fuse holder or fuse switch disconnector in this group.
Fuse In Fuse size Fuse holder, disconnector and fuses in the group up to 6.3–10 A, control circuits 5×20 or 6.3×32 mm terminal fuse holder 5×20 · terminal fuse holder 6.3×32 · fuse holder 6.3×32, AC/DC up to 25 A 8×32 mm (400 V) or 10×38 mm fuses 8×32, 16 A · 8×32, 25 A; fuse holder 10×38, 1P, 25 A · 10×38, 3P, 25 A up to 32 A 10×38 mm fuses 16 A · 20 A · 32 A; fuse holder 1P, 32 A, 690 V · 3P, 32 A up to 50 A 14×51 mm fuses 25 A · 40 A · 50 A; fuse holder 1P, 50 A · 3P, 50 A up to 125 A 22×58 mm fuses 63 A · 80 A · 100 A · 125 A; fuse holder 1P, 125 A · 3P, 125 A up to 160 A NH000 / NH00 fuses NH00C, 100 A · NH00, 160 A; fuse switch disconnector 160 A for mounting plate · 160 A for busbar · vertical 160 A up to 250 A NH1 (NH1C) fuses 160 A · 250 A; fuse switch disconnector 250 A for mounting plate · 250 A for busbar · vertical 250 A up to 400 A NH2 (NH2C) fuses 250 A · 400 A; fuse switch disconnector 400 A for mounting plate · 400 A for busbar · vertical 400 A up to 630 A NH3 (NH3C) fuses 400 A · 500 A · 630 A; fuse switch disconnector 630 A for mounting plate · 630 A for busbar · vertical 630 A up to 1250 A NH4a fuse 800 A; fuse switch disconnector vertical 1250 A for busbars Rule: the fuse current In must be no lower than the load current and no higher than 0.9 × the cable current-carrying capacity Iz (for gG fuses from 16 A). The fuse holder or fuse switch disconnector rated current must be no lower than that of the fuse. You will find the cable Iz in the cable selection guide.Solution levels: from a control circuit to incoming busbars
Each level is designed for higher currents and more powerful equipment. Choose the level by current and installation location.
Level 1. Old domestic panel
Flat or house with screw-in plug fuses.- E27 screw-in plug fuses for replacement
- same or lower current only
Level 2. Control circuits
Automation, controllers, alarms, measuring voltages. Each control circuit gets its own fuse.Level 3. Modular panel up to 125 A
Workshop, farm, compensation cabinet, motors.- modular fuse disconnectors for DIN rail
- cylindrical fuses 10×38–22×58 mm
Level 4. NH fuse switch disconnectors up to 630 A
Distribution panels, building incomers, industry. Replace fuses only with the disconnector cover open.Level 5. Incomer and busbar system
Transformer substations, large switchboards, up to 1250 A. Designed and installed by qualified professionals only.What do you need? Quick selection
Situation Solution Where to look A fuse has blown and I need the same one Same size, current, class (gG / aM) and no lower voltage. Do not fit a higher current. Cylindrical, NH, E27 Capacitor stage protection gG fuses at 1.6–1.8 × capacitor In, modular 22×58 fuse disconnector or NH00 fuse switch disconnector Modular fuse disconnectors, compensation guide Motor short-circuit protection aM fuses + thermal overload relay, or gG 1.6–2 times larger because of the starting current aM fuses, fuse disconnectors Distribution panel with several 100–400 A feeders NH fuse switch disconnectors: horizontal, for mounting plate or busbars For mounting plate, for busbars Compact busbar system, many feeders in one row Vertical NH fuse switch disconnectors – take up less width Vertical for mounting plate, for busbars Circuit breaker breaking capacity too low Upstream of it – a gG fuse as back-up protection (100–120 kA) Modular fuse disconnectors, circuit breaker guide Solar PV DC circuits gPV fuses and DC fuse holders only – AC fuses are not suitable Solar system fuses How it works: fuse classes and sizes
The fuse element melts when the current exceeds the permissible limit, and the quartz sand quenches the arc. A fuse interrupts the short-circuit current within a few milliseconds and limits its peak – which is why its breaking capacity (50–120 kA) is much higher than that of modular circuit breakers (6–10 kA). A blown fuse is replaced with a new one; it cannot be reset.
gG (gL)circuitsGeneral purpose: protects cables against overload and short circuit. gL is an older designation of the same type.aMmotorsShort-circuit protection only, withstands the starting current. Overload protection requires a thermal overload relay.gPVsolar DCFor direct-current photovoltaic circuits. An AC fuse must not be used in a DC circuit.Fuse switch disconnectorisolationA fuse holder with an isolating function: fuses can be replaced safely, with no voltage.Size Type Typical current Voltage Fuse holder 5×20 / 6.3×32 glass or ceramic up to ~10 A up to 250–600 V DIN terminal fuse holder 8×32 cylindrical up to 25 A 400 V modular fuse disconnector 10×38 cylindrical up to 32 A 400–690 V modular fuse disconnector 1P / 3P 14×51 cylindrical up to 50 A 400–690 V modular fuse disconnector 1P / 3P 22×58 cylindrical up to 125 A 400–690 V modular fuse disconnector 1P / 3P NH000 / NH00 NH (blade) up to 160 A 500–690 V NH fuse switch disconnector 160 A NH1 / NH2 / NH3 NH (blade) up to 250 / 400 / 630 A 500–690 V NH fuse switch disconnector 250 / 400 / 630 A NH4a NH (blade) up to 1250 A 500–690 V vertical unit for busbars ⚡ Safety. NH (blade) fuses must not be pulled out of a plain fuse base while load current is flowing – an electric arc is formed. Replace them only with the circuit disconnected or by using a fuse switch disconnector, with an insulated fuse puller, a face shield and dielectric gloves. Never replace a fuse with a higher-rated one or with wire.Selection rules: 6 steps
1. Fuse current by cable and load
The conditions IB ≤ In ≤ Iz and I2 ≤ 1.45 Iz must be met (IEC 60364-4-43). For a gG fuse from 16 A the conventional fusing current I2 = 1.6 In, so in practice In ≤ 0.9 Iz. Example – calculation.2. Class by load
gG – cables, circuits, capacitors, general protection. aM – motors, together with a thermal overload relay. gPV – solar PV DC circuits. Do not substitute one class for another – the protection characteristic will change.3. Voltage and breaking capacity
The fuse rated voltage must be no lower than the network voltage (for a three-phase 400 V network – 400 V or higher). The breaking capacity (20–120 kA) must exceed the prospective short-circuit current at the installation point: at the incomer and next to the transformer choose 100–120 kA.4. Selectivity
For only the fuse nearest to the fault to blow, the upstream gG fuse current must be at least 1.6 times higher than the downstream one (e.g. 100 A above 63 A, 160 A above 100 A).5. Fuse holder or fuse switch disconnector
Plain fuse holder – replace the fuse only with no load. A fuse switch disconnector lets you disconnect the load and replace the fuses safely. The fuse holder current must be no lower than that of the fuse, and the size must be the same (an NH1C fuse goes into an NH1 fuse base).6. Mounting and connection
DIN rail (modular), mounting plate or busbar system (NH fuse switch disconnectors). Check the terminal cross-section, the connection bolt and, if required, the terminal adapters and covers. For a busbar system – the busbar spacing according to the product description.Calculation: fuse and cable for a three-phase circuit
Example: three-phase circuit, load current IB = 55 A, copper PVC-insulated cables, installation method C, 3 loaded conductors (IEC 60364-5-52). We are looking for a gG fuse and a cable.
Step Calculation Result Nearest fuse ≥ IB standard series: 50, 63, 80 A 63 A Cable 16 mm², Iz = 68 A 0.9 × 68 = 61.2 A < 63 A ✗ not suitable Cable 25 mm², Iz = 89 A 0.9 × 89 = 80.1 A ≥ 63 A ✓ suitable Fuse size 63 A 22×58 mm or NH00 Upstream fuse ≥ 1.6 × 63 A 100 A gG Conclusion: for a 55 A circuit – a gG 63 A 22×58 mm fuse in a modular 3P 125 A fuse disconnector or an NH00 160 A fuse switch disconnector, 25 mm² Cu cable, with a 100 A fuse upstream. With a 16 mm² cable you would have to choose a 50 A fuse, which is too small for a 55 A load.Selection matrix: all products in the group
Choose a situation – the matching rows will be highlighted:
AllOld domestic panelControl circuitsModular panel up to 125 ANH panel up to 630 AIncomer and busbarsMotors (aM)Fuse replacementProduct Type Key data When to choose Note Cylindrical fuses 4 · 6 · 10 · 16 · 20 · 25 A cylindrical 8×32 mm, gG 400 V; 20–50 kA small circuits, control 400 V networks only 1 · 4 · 10 · 16 · 20 · 25 · 32 A cylindrical 10×38 mm, gG 400–500 V; 100–120 kA circuits up to 32 A, capacitors, control the most popular size 1 · 2 · 4 · 6 A cylindrical 10×38 mm, aM 500 V; 120 kA motors, transformers with a thermal overload relay 16 · 25 · 32 · 40 · 50 A cylindrical 14×51 mm, gG 400–690 V; 80–120 kA circuits up to 50 A 32–50 A – 400–500 V 63 · 80 · 100 · 125 A · 32 · 50 A, 690 V cylindrical 22×58 mm, gG 500–690 V; 80–120 kA circuits up to 125 A, compensation stages 10 · 16 · 32 · 63 · 100 A cylindrical 22×58 mm, gG 100 kA economical replacement check the voltage in the description Screw-in plug fuses and NH (blade) fuses 10 · 16 · 25 A screw-in plug fuse E27 230 V old domestic panels worth upgrading 40 · 80 · 100 · 125 · 160 A · NH00 160 A NH00C / NH00 blade fuse, gG 500 V; 120 kA NH 160 A fuse switch disconnectors 63 · 100 · 160 · 200 · 250 A · NH1 250 A NH1 / NH1C blade fuse, gG 500 V; 120 kA NH1 250 A fuse switch disconnectors C – compact body 63 · 100 · 160 · 250 · NH2 400 A NH2 / NH2C blade fuse, gG 500 V; 120 kA NH2 400 A fuse switch disconnectors 400 · 500 · 630 A NH3 / NH3C blade fuse, gG 500 V; 120 kA NH3 630 A fuse switch disconnectors, incomers 800 A NH4a blade fuse, gG 500 V; 120 kA high-current incomers vertical 1250 A unit Modular fuse disconnectors (DIN) 5×20, 6.3 A · 6.3×32, 10 A · 6.3×32, AC/DC terminal fuse holder up to 400–600 V control and measuring circuits 1P, 25 A · 1P, 32 A, 690 V · 3P, 25 A · 3P, 32 A fuse disconnector 10×38 mm up to 690 V; up to 120 kA with fuse circuits up to 32 A, capacitors 1P, 50 A · 3P, 50 A fuse disconnector 14×51 mm 400–690 V circuits up to 50 A, motors 1P, 125 A · 3P, 125 A fuse disconnector 22×58 mm 400–690 V circuits up to 125 A, compensation stages NH fuse switch disconnectors 160 A · 160 A · 160 A, 3P horizontal NH00 unit for mounting plate 690 V; IP30 distribution panels 250 A · 250 A · 250 A, 800 V · 250 A horizontal NH1 unit for mounting plate 690–800 V circuits up to 250 A 400 A · 400 A · 400 A, M10 horizontal NH2 unit for mounting plate 690 V; up to 100 kA circuits up to 400 A 630 A · 630 A horizontal NH3 unit for mounting plate 690 V incomers up to 630 A 160 · 250 · 400 · 630 A · 400 A horizontal unit for busbars 690 V; IP30 busbar system panels busbar spacing – in the description 160 · 250 · 400 · 630 A vertical unit for mounting plate 400–690 V; IP30 many feeders in one row 250 A · 1250 A vertical unit for busbars 690 V; 100 kA switchboards, transformer substations 16–70 mm², 160 A · 16–185 mm², 250 A · 50–300 mm², 630 A · cover 250 · 400 · 630 A terminals and covers for fuse switch disconnectors 690 V cable connection, touch protection according to the unit current All products in the group – cylindrical, NH (blade) and screw-in plug fuses, modular fuse disconnectors, NH fuse switch disconnectors and accessories. For solar PV plants – gPV fuses and DC fuse holders.
⚠ What to check before buying
- The fuse size (8×32, 10×38, 14×51, 22×58, NH000–NH4a) – it must fit the existing fuse holder.
- The rated current: no higher than 0.9 × the cable Iz and no lower than the load current.
- The class: gG for circuits, aM for motors, gPV for solar DC circuits.
- The rated voltage: 400, 500 or 690 V – no lower than the network voltage.
- The breaking capacity at the incomer and next to the transformer: 100–120 kA.
- Selectivity with the upstream fuse: a ratio of at least 1.6.
- The fuse holder or fuse switch disconnector current, number of poles (1P / 3P) and mounting: DIN, mounting plate or busbars.
- The terminal cross-section and, if required, terminal adapters and covers.
✗ The most common mistakes
Mistake Consequence and how to avoid it A blown fuse replaced with a higher-rated one The cable is no longer protected against overload – it overheats and may catch fire. Replace only with an identical fuse. A fuse “repaired” with wire ⚡ No protection at all, risk of fire and arc flash. Prohibited. Fuse chosen without the 0.9 Iz rule A sustained overload is not disconnected in time. Check In ≤ 0.9 Iz. Upstream and downstream fuses almost the same Both blow – the whole panel loses power. Ratio of at least 1.6. NH fuse pulled out of a plain fuse base under load ⚡ Electric arc, burns. Disconnect the load or use a fuse switch disconnector. aM fuse for a circuit without a thermal overload relay Overload is not disconnected – the cable overheats. aM – only with overload protection. AC fuse in a solar PV DC circuit The direct-current arc is not extinguished. gPV fuses only. NH fuse of a different size from the fuse base Poor contact, overheating. NH1 – into an NH1 fuse base only. Wrong solutions: wrong and correct
⚠ The diagrams are illustrative. They are not wiring diagrams. Protection must be selected and installed by a certified electrician according to the design and the manufacturer’s instructions. UAB „Elektrotechnikos sprendimai“ accepts no liability for the connection or installation of equipment.1. Selectivity: upstream and downstream fuse
Diagram. When the upstream and downstream fuse currents are similar, a short circuit on the feeder can blow both – the whole panel loses power. For gG fuses, a ratio of at least 1.6 ensures that only the fuse nearest to the fault blows.
2. Cable protection: fuse current
Diagram. The current-carrying capacity of a 2.5 mm² copper cable (installation method C, 3 loaded conductors) is about 24 A. A 32 A fuse does not protect it against overload; a 20 A fuse meets the condition In ≤ 0.9 Iz.
3. Replacing NH fuses
Diagram. Left – an NH fuse is pulled out of a plain fuse base under load: an electric arc forms. Right – the fuse switch disconnector cover is open, the fuses are isolated from the circuit and replaced safely. The incoming terminals remain live.
Faults and fixes: symptom → cause → what to do
Symptom Likely cause What to do The fuse blows when the motor starts gG too small for the starting current aM fuse + thermal overload relay, or a larger gG sized to the cable Blows when a capacitor stage switches on Fuse too small for the inrush current gG at 1.6–1.8 × capacitor In, contactor with pre-charge resistors Fuse holder or fuse switch disconnector heats up Loose terminals, poor fuse contact, overload Tighten to the specified torque, replace the fuse, check the load The upstream fuse blows No selectivity A ratio of at least 1.6 between fuses The fuse blows often for no obvious reason Ageing after sustained overload, heating in the fuse holder Measure the load (with a power analyser), replace fuses as a full set Frequently asked questions
Kibirkštis asks – a young, curious electrician who dares to ask what others won’t. Fazė answers – an experienced engineer.
Kibirkštis
Why is a fuse better than a circuit breaker?
Fazė
A fuse has a very high breaking capacity (up to 120 kA), limits the short-circuit current and is inexpensive. A circuit breaker can be switched back on. That is why fuses are often used at incomers, and circuit breakers in final circuits.
Kibirkštis
What is the difference between gG and aM?
Fazė
gG protects against both overload and short circuit – suitable for cables and circuits. aM protects against short circuit only and withstands the motor starting current, so overload protection requires a thermal overload relay.
Kibirkštis
What fuse do I need for a 2.5 mm² cable?
Fazė
Usually 16–20 A gG, depending on the installation method. Check the condition In ≤ 0.9 Iz – see the cable guide.
Kibirkštis
Can I fit an NH1C fuse into an NH00 fuse base?
Fazė
No. The number indicates the size (blade dimensions), so an NH1C fuse fits an NH1 fuse base only. The letter C stands for a more compact body.
Kibirkštis
How does a fuse switch disconnector differ from a plain fuse holder?
Fazė
With a fuse switch disconnector you can disconnect the load and replace the fuses safely by opening the cover. A fuse can be removed from a plain fuse holder only after the circuit has been disconnected.
Kibirkštis
How do I ensure selectivity?
Fazė
Keep a ratio of at least 1.6 between gG fuses: e.g. 100 A above 63 A, 160 A above 100 A. Between a fuse and a circuit breaker – check the manufacturers’ selectivity tables.
Kibirkštis
Is a 400 V fuse suitable for a 690 V network?
Fazė
No. The fuse voltage must be no lower than the network voltage. For a 400 V network, 500 or 690 V fuses are also suitable.Related guides
Protection also needs cables, circuit breakers, a panel and busbars – these guides will help you choose them:- Cable selection guide – cable current-carrying capacity Iz
- Circuit breaker guide – when resettable protection is needed
- Moulded case circuit breaker (MCCB) guide – incomers up to 1600 A
- Switch disconnector and 1-0-2 changeover switch guide – isolation without fuses
- Busbar guide – busbars for NH fuse switch disconnectors
- Reactive power compensation guide – fuses for capacitor stages
- Panel and enclosure selection guide – enclosure for fuse switch disconnectors
- All product selection guides
Sources
Standards and manufacturer data used in this guide.
- IEC 60269-1 / -2 – Low-voltage fuses: general requirements, NH and cylindrical fuses, gG / aM characteristics, selectivity
- IEC 60269-6 – gPV fuses for solar photovoltaic systems
- IEC 60947-3 – Switch disconnectors and fuse switch disconnectors
- IEC 60364-4-43 and -5-52 – Protection against overcurrent, current-carrying capacities of cables
- Manufacturer technical data in the product descriptions – fuses, modular fuse disconnectors, NH fuse switch disconnectors
Published: 2026-11-04 · Data checked against manufacturer specifications: 2026-11-04
Disclaimer. This guide, its diagrams and calculations are for information only – they are not a design, wiring diagram or installation instructions. Fuses and fuse switch disconnectors must be selected, installed and replaced by a qualified, certified electrical professional in accordance with the design, the manufacturer’s instructions and applicable legislation. UAB „Elektrotechnikos sprendimai“ accepts no liability for the selection, connection, installation or operation of equipment based on this guide, or for any resulting damage.