Lightning protection guide: how to protect the building and electrical equipment
Lightning current reaches tens and, in rare cases, hundreds of kiloamperes. A direct strike can puncture the roof and start a fire, while an indirect strike – to a line or near the building – brings a surge through the power and data network that destroys boiler controls, the inverter, computers and LED luminaires. That is why protection has three layers: an external lightning protection system (air terminal and down conductors), earthing with equipotential bonding, and surge protective devices (SPDs) in the distribution boards. If any layer is missing, a gap remains.
Blue – information Green – benefit to you Orange – ⚠ check this Red – ⚡ safety and mistakes
What do you need? Quick selection
|
Situation |
Solution |
Where to find it |
|
Residential house without LPS, underground cable supply |
T2 SPD in the main distribution board (In ≥ 5 kA, we recommend 20 kA), plus T3 at sensitive equipment where needed |
T2 4P 20 kA · T3 |
|
House supplied by an overhead line, open location, tallest building in the area |
Our recommendation: combined T1+T2 at the service entrance (Iimp 5–12.5 kA per pole); consider an external LPS |
T1+T2 4P 7 kA |
|
Building with an air terminal (external LPS) |
T1 (usually combined T1+T2) at the service entrance is mandatory, Iimp ≥ 12.5 kA per pole unless the design specifies otherwise; T2 in sub-distribution boards |
T1+T2 4P 12.5 kA |
|
House, garage, sauna – external LPS required |
Conventional Franklin rods, down conductors, earthing; together with T1+T2 in the board |
Conventional air terminals |
|
Large roof, farm, warehouse, open area |
ESE air terminal to NF C 17-102 – the zone is determined by the protection level and height |
ESE air terminals |
|
PV system on the roof or ground |
DC SPD at the inverter (T2; T1+T2 if the separation distance to the air terminal is not maintained) and an AC SPD |
DC 1000 V T2 · DC T1+T2 |
|
Internet, CCTV cameras, LED street lights |
Data line (RJ45) and LED SPDs at the equipment |
RJ45 CAT6A · LED |
|
Earthing, down conductors, fixing, connections |
Rods, tapes, wires, masts, bars, exothermic welding – covered in detail in the components guide |
Components guide |
What you gain from the right selection
-
Lightning current is conducted to earth along a defined path, not through the roof, walls or electrical installation.
-
The boiler, heat pump, inverter, gate automation and computers fail far less often after thunderstorms.
-
SPDs in different boards work in coordinated stages rather than at each other's expense.
-
Easy to check after a storm: the indicator shows which cartridge to replace.
Three layers of protection and when you need them
1. External lightning protection
The air terminal (rod, mesh or ESE) intercepts the strike, the down conductors carry the current down
→
2. Earthing and equipotential bonding
The current dissipates into the soil; all incoming metal services and PE are connected at the main earthing terminal
→
3. Surge protective devices
T1 at the service entrance → T2 in the boards → T3 at the equipment: each stage reduces the surge
|
Layer |
Protects against |
When required |
|
External lightning protection |
Direct strikes: fire, damage to the roof and structures |
When required by the design, the building's use or the insurer, or when a risk assessment to EN 62305-2 shows the risk is too high (tall, isolated and public buildings, farm buildings storing hay, filling stations) |
|
Earthing and equipotential bonding |
Dangerous potential differences between metal parts, step voltage |
Always: without it neither the air terminal nor the SPDs work |
|
Surge protective devices (SPD) |
Surges arriving via power, data and antenna lines |
HD 60364-4-443 requires surge protection where the consequences affect human life, public services, commercial or industrial activity, or large groups of people; in other cases it depends on a risk assessment. If the building has an air terminal, T1 at the service entrance is essential |
⚠ An air terminal without SPDs does not protect the equipment – on the contrary, during a strike the building's earth potential rises by hundreds of kilovolts relative to the incoming conductors, and flashover can occur between PE and the phase conductors. That is why, once an external LPS is installed, a T1 SPD at the service entrance is not an option but a necessity.
Conventional or early streamer emission (ESE) air terminal
|
Feature |
Conventional (Franklin rod, mesh) |
Early streamer emission (ESE) |
|
Standard |
EN 62305-3 (rolling sphere, protective angle and mesh methods) |
NF C 17-102 (EN 62305 does not cover ESE) |
|
Protection zone |
Small per rod – the roof is covered with several rods or a mesh |
Larger per mast (Rp is calculated from ΔT, height and protection level) |
|
Number of down conductors |
Based on the perimeter: spacing between down conductors 10 m (LPL I–II), 15 m (III), 20 m (IV); at least 2 |
At least 2 per ESE (NF C 17-102) |
|
Best suited for |
Houses, garages, chimneys, rooftop equipment, small buildings |
Large flat roofs, farms, warehouses, open areas, historic buildings (fewer elements on the facade) |
|
What to watch for |
More components and installation work |
Check whether ESE is acceptable to your designer, client or insurer |
Lightning protection levels to EN 62305-3
|
Level (LPL) |
Rolling sphere radius |
Mesh size |
Typical buildings |
|
I |
20 m |
5 × 5 m |
Explosion hazard areas, hospitals, telecom centres |
|
II |
30 m |
10 × 10 m |
Public and industrial buildings with sensitive equipment |
|
III |
45 m |
15 × 15 m |
Residential, farm and office buildings |
|
IV |
60 m |
20 × 20 m |
Low-risk structures |
The level is determined by the designer based on a risk assessment (EN 62305-2). Building examples are indicative.
How many metres an ESE air terminal really protects
The protection radius Rp of an ESE air terminal is not a fixed value. According to NF C 17-102 it depends on three factors: the early streamer advance time ΔT (µs), the height h above the protected surface, and the protection level. The calculation uses a ΔT value of no more than 60 µs, even if the manufacturer declares more.
|
ΔT |
Rp, level I (h = 5 m) |
Rp, level IV (h = 5 m) |
|
30 µs |
≈ 48 m |
≈ 71 m |
|
45 µs |
≈ 63 m |
≈ 89 m |
|
60 µs (maximum used in calculation) |
≈ 79 m |
≈ 107 m |
How it is calculated (NF C 17-102, for h ≥ 5 m)
Rp = √(h × (2D − h) + ΔL × (2D + ΔL)), where ΔL = 10⁶ m/s × ΔT, and D = 20 / 30 / 45 / 60 m (level I / II / III / IV).
Example: ΔT = 60 µs → ΔL = 60 m; level I, h = 5 m → Rp = √(5 × 35 + 60 × 100) = √6175 ≈ 79 m.
Height h is measured from the ESE tip to the protected surface (e.g. the ridge), not to the ground. When h is between 2 and 5 m, Rp is smaller and is taken from the table in the standard; h may not be less than 2 m.
⚠ The figure in the product name (“30 m”, “60 m”, “R100m”) usually indicates ΔT or the radius declared by the manufacturer under the most favourable conditions (level IV, large height). When designing, calculate for your own protection level and actual h. If the declared ΔT exceeds 60 µs, still use 60 µs in the calculation. More on zones and the complete system – in the
components guide.
Surge protective devices T1, T2, T3
|
Type |
Test waveform and parameter |
Where installed |
Our products |
|
T1 (Class I, B) |
10/350 µs, Iimp – partial lightning current |
In the main distribution board when there is an air terminal or an overhead line |
T1+T2 SPDs |
|
T1+T2 (B+C) |
Both Iimp (10/350) and In (8/20) – one device covers both stages |
In the main distribution board when the protected equipment is close to the service entrance – the most common solution for houses and small sites |
FLP12.5 4P · A51-SPD02 4P |
|
T2 (Class II, C) |
8/20 µs, In and Imax |
At the service entrance (when there is no air terminal) and in sub-distribution boards |
MOP4-C 4P · SLP40 4P |
|
T3 (Class III, D) |
Combination wave Uoc (1.2/50 µs and 8/20 µs) |
At sensitive equipment located more than ~10 m of cable from the T2 |
T3 Up 1.2 kV · T2+T3 4P |
⚠ A “T1” SPD must have a stated Iimp (10/350 µs). If the product page or housing shows only In and Imax (8/20 µs), those are T2 parameters. Do not use such an SPD as T1 in a building with an air terminal until you have checked the manufacturer's datasheet – ask us and we will send it.
Selecting an SPD in 4 steps
1. Earthing system
TN-C – 3P; TN-S – 4P; TT – “3+1” (3 varistors L–N and a spark gap N–PE); single-phase – 1P+N
→
2. Uc
For a 230/400 V network Uc ≥ 1.1 × 230 V = 253 V → 275 V as standard. For an IT network Uc ≥ line-to-line voltage
→
3. Current
T1: Iimp ≥ 12.5 kA per pole (with an air terminal); T2: In ≥ 5 kA (minimum), 20 kA in practice
→
4. Up
The voltage protection level plus the voltage drop on the connecting leads must be lower than the equipment's withstand voltage
|
Overvoltage category (230/400 V) |
Equipment impulse withstand voltage |
Examples |
|
IV |
6 kV |
Service entrance, meters |
|
III |
4 kV |
Distribution boards, switches, stationary motors |
|
II |
2.5 kV |
Household appliances, tools |
|
I |
1.5 kV |
Sensitive electronics (computers, controllers) |
How to estimate the actual protection level
The equipment sees not only the SPD's Up but also the voltage drop on the connecting leads – allow about 1 kV per metre (HD 60364-5-534). Up(ef) ≈ Up + 1 kV/m × (a + b), where a is the lead from the phase to the SPD and b is the lead from the SPD to the PE bar.
Example: Up = 1.5 kV, a + b = 0.5 m → Up(ef) ≈ 2.0 kV – suitable for category II equipment (2.5 kV). The same SPD with 1.5 m leads → ≈ 3.0 kV – it no longer protects category II equipment.
PV system, data lines, LED
|
Application |
What to install |
Important |
|
PV system (DC side) |
DC T2 1000 V; if the separation distance to the air terminal is not maintained – DC T1+T2 |
SPD Ucpv ≥ maximum string voltage Voc on the coldest day; an AC SPD must not be used in a DC circuit |
|
PV system (AC side) |
T2 (or T1+T2) at the inverter and at the service entrance |
The inverter is the most expensive and most sensitive part of the system |
|
Internet, CCTV cameras |
RJ45 CAT6A SPD at the equipment |
The SPD's PE is connected with a short lead to the same earth as the equipment |
|
LED street, yard and warehouse luminaires |
LED SPD in the luminaire or pole |
Long outdoor lines are the most common cause of LED driver failure after thunderstorms |
⚠ What to check before buying
Kibirkštis: “We put an air terminal on the roof and the cheapest SPD in the board. After the storm the boiler still burned out…”
|
What to check |
Why |
|
Whether the building has (or will have) an air terminal |
This determines whether T1 is needed at the service entrance or T2 is enough |
|
Earthing system (TN-C, TN-S, TT) and number of poles |
In a TT system, 4 varistors instead of “3+1” can cause leakage to PE and RCD tripping, and if a varistor fails short – a dangerous voltage on the PE conductor |
|
Iimp (10/350) on the SPD product page |
Without it, “T1” is just a label |
|
Up and position in the board |
Leads to the SPD and from it to PE – as short as possible, no more than 0.5 m in total |
|
Backup fuse |
The manufacturer specifies the maximum fuse upstream of the SPD; if the incoming fuse is larger, the SPD needs its own |
|
Replaceable cartridges and indication |
After a strike only the cartridge is replaced, not the whole SPD; a remote signalling contact reports a failure |
|
ESE: protection level and height h |
Radius in the product name ≠ radius on your site |
✗ Most common mistakes
|
Mistake |
Consequence |
|
Building with an air terminal, but only T2 at the service entrance |
T2 cannot withstand the partial lightning current, burns out and fails to protect the equipment |
|
SPD connected with long leads (1–2 m) or PE routed to a distant terminal |
Each metre adds ~1 kV – the equipment gets a surge even though the SPD “works” |
|
SPD only in the sub-distribution board, nothing at the service entrance |
The surge passes through the meter, the service entrance and other circuits |
|
4P SPD without an N–PE spark gap installed in a TT system |
Leakage to PE, RCD tripping, varistor overheating; if a varistor fails short – a dangerous voltage on the PE conductor |
|
ESE selected by the “R100 m” in the product name without recalculating for the level and height |
Part of the roof is left unprotected |
|
Down conductor too close to cables, antennas, metal pipes (separation distance s not maintained) |
Flashover into the installation – fire and burned-out equipment |
|
Separate earth electrodes for lightning protection, the electrical installation and telecoms, not interconnected |
During a strike a potential difference of tens of kilovolts arises between them |
|
⚡ SPD replaced or connected without isolating the supply |
Risk of electric shock and arc flash |
⚡ Safe installation – Fazė's advice
Work on the main distribution board only after isolating the supply and verifying that no voltage is present; the part upstream of the meter can only be disconnected by the network operator. Do not work on the air terminal, down conductors, roof or service entrance during a thunderstorm. Install the SPD close to the service entrance and the main PE bar, and run the leads short and straight, without loops. Check the SPD indicators after every severe storm. The lightning protection system must be installed, and measurements (earth resistance, bonding continuity) carried out, by a qualified specialist.
☝ Elsprendimai.eu recommends
Diagram: SPD connection – wrong and right
Kibirkštis: “There is an SPD in the board, the indicator is green, but the heat pump controller is dead after the thunderstorm. How?”
Fazė: “Because what matters is not only which SPD you have, but also how it is connected. Take a look.”
✗ WRONG
① Building with an air terminal, only T2 at the service entrance
↓
② Leads L → SPD and SPD → PE: 0.8 m + 0.7 m = 1.5 m
↓
③ SPD's PE routed to a sub-board terminal, not to the main bar
↓ ⚡ strike
④ Controller 25 m from the board, no T3 – receives ≥ 3 kV (up to ~2 times more due to oscillation in the line)
✓ RIGHT
① T1+T2 at the service entrance, Iimp 12.5 kA per pole
↓
② a + b ≤ 0.5 m or V-wiring (through the SPD terminal)
↓
③ PE – directly to the main equipotential bonding bar, connected to the earthing
↓ ⚡ strike
④ T3 at the controller; the equipment sees a voltage below its withstand level
Why – explanation by diagram number
-
①: in a building with an air terminal, part of the lightning current flows through the service entrance (10/350 µs waveform). A T2 SPD is tested only with the 8/20 µs waveform, so it cannot handle this energy. A T1+T2 SPD with Iimp ≥ 12.5 kA per pole diverts it to PE.
-
②: during a strike, a voltage drop of about 1 kV per metre appears on the leads. Wrong: Up 1.5 kV + 1.5 m × 1 kV ≈ 3.0 kV. Right: 1.5 kV + 0.5 m × 1 kV ≈ 2.0 kV. V-wiring (where the conductor goes into the SPD terminal and continues out of it) reduces this drop even further.
-
③: the SPD must divert the current to the same point to which all metal parts and the earthing are connected. Otherwise a potential difference arises between PE and other metal parts.
-
④: when the equipment is more than ~10 m of cable from the T2, oscillations occur in the line and the voltage at the equipment end can increase. A T3 at the equipment (Up 1.2 kV), connected with short leads, reduces the voltage to a level that sensitive electronics can withstand (category I – 1.5 kV).
⚠ The diagram is for guidance only. Check the SPD type, current rating and connection against the manufacturer's instructions and the design. Installation is carried out by, and is the responsibility of, a qualified electrician. UAB “Elektrotechnikos sprendimai” is not responsible for the connection or any errors.
FAQ
Kibirkštis: I have an air terminal. Is a T2 SPD at the service entrance enough?
Fazė: No. In a building with external lightning protection, the service entrance needs a T1 (usually a combined T1+T2) with Iimp of at least 12.5 kA per pole, unless the design specifies otherwise. A T2 cannot withstand such a current.
Kibirkštis: I don't have an air terminal, but the house is supplied by an overhead line. What should I choose?
Fazė: At a minimum, T2 at the service entrance (In ≥ 5 kA, preferably 20 kA). Since lightning can strike an overhead line directly, we recommend a combined T1+T2 with Iimp 5–12.5 kA per pole: the price difference is small, and the SPD also withstands partial lightning current (10/350 µs).
Kibirkštis: Is an ESE air terminal better than a conventional one?
Fazė: Not universally. An ESE lets you protect a larger area with one mast, which makes it convenient for large roofs and sites. But it is designed to NF C 17-102, and EN 62305 does not cover it, so agree it with your designer or insurer before buying. For a house or garage, a few Franklin rods are often simpler and cheaper.
Kibirkštis: Does a surge protective device protect against a direct lightning strike to the house?
Fazė: No. An SPD protects equipment against surges on the conductors. Only an external lightning protection system with earthing protects against a direct strike to the building (fire, roof damage).
Kibirkštis: How do I know the SPD needs replacing?
Fazė: Most SPDs have an indicator window: green – OK, red – the cartridge needs replacing. Only the cartridge is replaced, e.g. V20 cartridges. Models with a remote signalling contact can report a failure to an alarm system or controller.
Kibirkštis: Do I need a T3 for every socket outlet?
Fazė: No. A T3 is fitted at sensitive and expensive equipment (server, boiler or heat pump controller, video recorder), especially if it is more than ~10 m of cable from the board with the T2. Without T1/T2 in the board, a T3 alone will not be effective and may fail quickly – it is only meant to suppress the residual surge.
Kibirkštis: What should the earth resistance be?
Fazė: For lightning protection, EN 62305-3 recommends that the earth electrode resistance be below 10 Ω where possible (measured at low frequency), but most importantly the earth electrode must have a suitable configuration and be connected to the building's entire equipotential bonding system. You will find rods, tapes and connection methods in the components guide.
Sources: EN 62305-1…4 (protection against lightning); NF C 17-102:2011 (ESE air terminals, Rp calculation, ΔT ≤ 60 µs); HD 60364-4-443 (protection against atmospheric and switching overvoltages); HD 60364-5-534 (selection and erection of surge protective devices); EN 61643-11 (low-voltage SPDs, T1/T2/T3 tests); EN 61643-31 (DC SPDs for photovoltaic installations); technical data from elsprendimai.eu product pages. Checked 2026-10-17.