Automatic aerosol fire extinguishing device | 10g | 170°C activation | 0.1m³
Code: ES-QRR0.01G/S-CFLCPrice 33.26 € VAT incl.( 27.49 € VAT excl. )Buy more, pay less10+ pcs. – 28.31 € for pcs. -14%Want another price? Suggest yours!Aerosol fire suppression device designed for the localized protection of small electrical, automation, and other technical cabinets. It is mounted on a flat surface, so it does not occupy space on the DIN rail. The device is automatically activated by a thermal activation line when the temperature reaches approximately 170 ±10 °C. It contains 10 g of fire-extinguishing agent, designed to protect a volume of up to 0.1 m³. Its compact dimensions of 142 × 24 × 16 mm allow installation in small electrical, PLC, automation, communication, and electronic cabinets.
-
Aerosol Fire Extinguishing Strip for Electrical Panels | 10g | 0.1m³ | 170°C Aerosol Fire Extinguishing Device for Electrical Panels | 10g | up to 0.1m³ | Thermal Activation
Aerosol fire extinguishing strip for electrical panels – a compact local protection device designed for installation inside electrical, automation and other small technical enclosures. The strip is mounted on a flat surface inside the panel and is activated by a thermal line when the temperature reaches approximately 170±10°C. The device contains 10g of aerosol-generating chemical agent, while the protected volume is up to 0.1m³ when the extinguishing density is 100g/m³.
Compact localised protection inside the electrical panelThanks to the slim 142x24x16mm housing, the device can be installed on a flat inner wall, door or other suitable surface inside an electrical panel or automation cabinet. In the event of a fire, when the thermal activation line reaches the specified temperature, the aerosol generation process is initiated and the extinguishing agent is dispersed throughout the protected space.
10gAmount of chemical agent0.1m³Protected volume170±10°CActivation temperature10 yearsService lifeOperating principle and main functions
Function Parameter Operating principle Thermal activation 170±10°C When the activation line reaches the specified temperature, the extinguishing process is initiated. Aerosol generation 10g When the device is activated, the chemical composition generates extinguishing aerosol, which is dispersed throughout the protected space. Extinguishing density 100g/m³ Indicates the design quantity of extinguishing agent per unit of protected volume. Protected volume Up to 0.1m³ Designed for localised protection of small enclosed electrical spaces. Installation On a flat surface Installed inside an electrical panel or technical cabinet on a suitably selected flat surface. How does the fire extinguishing strip work?
- The device is installed on a flat surface inside the protected electrical enclosure.
- The thermal activation line is positioned according to the installation requirements of the specific site and product.
- Under normal conditions, the extinguishing device remains passive.
- In the event of a fire, the temperature inside the protected space rises.
- When the thermal line reaches approximately 170±10°C, the device is activated.
- The generated extinguishing aerosol is dispersed throughout the protected enclosed space and acts on the combustion process.
Important: protected volume up to 0.1m³For one 10g device, the protected volume is up to 0.1m³ when the extinguishing density is 100g/m³. When selecting the device, the actual internal volume of the enclosure, ventilation openings, leakage, equipment arrangement and other specific installation conditions must be evaluated.
Flat-surface installationThe 142mm long and only 16mm thick construction is designed for installation where DIN rail space is unavailable or needs to be reserved for other modular equipment. The strip can be positioned on a suitable flat panel surface so that it does not interfere with electrical components and the manufacturer's specified installation conditions are maintained.
Fire classes and applications
Specified class Application A For fires involving solid combustible materials according to the declared application of the product. B For fires involving flammable liquids or fires of a similar nature according to the product specification. C For gas fires according to the declared scope of application. E For protection of electrical equipment. Specific conditions of use must be evaluated according to the product documentation and applicable local requirements. Technical specification
Product type Aerosol fire extinguishing device / strip for electrical panels Installation method Panel-mounted, on a flat surface Amount of extinguishing chemical agent 10g Protected volume Up to 0.1m³ Extinguishing density 100g/m³ Activation method Thermal line Activation temperature 170±10°C Operating temperature -50°C ~ +90°C Ambient relative humidity ≤95% RH Dimensions 142x24x16mm Product weight 48g Application classes A, B, C, E Oxidising agent Sr(NO3)2, KNO3 Oxidising agent content 70% Service life 10 years Applicable standard EN 15276-1:2019 Declared certificates / markings CE, TÜV, RoHS, ISO 9001, CMA, CNAS Panel installation inside an electrical enclosure
Does not occupy DIN rail spaceBecause the extinguishing strip is designed to be mounted on a flat surface, it can be installed separately from DIN modular equipment. This is useful in compact electrical panels where DIN rail space is needed for circuit breakers, contactors, relays, power supplies or other control equipment.
Advantages / benefits
- Extremely compact construction – 142x24x16mm dimensions allow the device to be installed in narrow areas inside electrical cabinets.
- Flat-surface mounting – does not occupy DIN rail space.
- Thermal activation allows the extinguishing process to start autonomously once the specified temperature is reached.
- Specified protected volume up to 0.1m³ is suitable for small electrical and automation cabinets.
- Wide operating temperature range from -50°C to +90°C.
- Ambient humidity up to 95% RH according to the specified operating conditions.
- Specified 10-year service life for long-term stationary protection.
- 48g product weight allows easy integration into small technical cabinets.
Disadvantages / limitations
- Small protected volume: one device is specified for protection up to 0.1m³, therefore larger enclosures require a separate engineering assessment.
- Thermal activation: the extinguishing process is initiated only when the thermal line reaches the specified temperature.
- Single-use operating principle: after activation, the extinguishing device must be replaced with a new one.
- Enclosed-space conditions: large ventilation openings or an insufficiently sealed enclosure may affect the aerosol concentration.
- Not a whole-room fire suppression system: the product is intended for localised protection of a small enclosed space.
What is it suitable for? (Applications)
- Electrical distribution panels
- Automation and PLC control cabinets
- Small control boxes
- Communication and telecommunications cabinets
- Electronic equipment enclosures
- Localised protection of contactor, relay and power supply areas
- Other small enclosed technical spaces up to the specified protected volume
What is it not suitable for?
- Spaces with a volume exceeding 0.1m³ without a separate engineering calculation
- Open or heavily ventilated spaces where the required aerosol concentration cannot be maintained
- Use as a manual portable fire extinguisher
Practical example
A small automation cabinet contains power supplies, contactors, relays and PLC equipment, while almost all DIN rail space is already occupied. The 142x24x16mm aerosol fire extinguishing strip is attached to a suitable flat internal surface of the cabinet. The thermal activation element is positioned within the protected area according to the manufacturer's installation requirements. In the event of a fire, when the temperature reaches approximately 170±10°C, the extinguishing device is activated and disperses aerosol throughout a protected volume of up to 0.1m³.
Frequently asked questions (FAQ)
What volume is this extinguishing strip designed to protect?According to the provided specification, one 10g device is specified for a protected volume of up to 0.1m³ when the design extinguishing density is 100g/m³.
How is the device installed?This is a panel-type device designed to be mounted on a suitable flat surface inside an electrical or automation cabinet.
Is a DIN rail required?No. This version is mounted on a flat surface and is not a DIN rail module.
How is the device activated?Activation is performed using a thermal line. The specified activation temperature is 170±10°C.
How much extinguishing agent is inside?The specified quantity of chemical agent is 10g.
What are the product dimensions?The product dimensions are 142x24x16mm and the specified weight is 48g.
What is the operating temperature?The operating ambient temperature range is from -50°C to +90°C.
What is the specified service life?According to the provided product information, the service life is 10 years, provided that the manufacturer's storage, installation and operating requirements are followed.
Can the device be used again after activation?No. The aerosol fire extinguishing generator is a single-use device and must be replaced after activation.
Important fire safety and installation noteThe aerosol fire extinguishing device must be selected and installed according to the manufacturer's technical documentation, the actual volume of the protected space, ventilation, openings, fire risk and applicable fire safety requirements. The specified 0.1m³ volume must not be automatically applied to any electrical enclosure without evaluating its construction. The device must not be dismantled, mechanically damaged, heated or activated other than for its intended purpose. After activation, the product must be replaced with a new one.
10g aerosol fire extinguishing strip – a compact flat-surface-mounted device designed for localised protection of small electrical and automation cabinets up to 0.1m³, using a 170±10°C thermal activation line and aerosol fire suppression technology.
Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.Circuit breakers, also known as protective breakers or circuit interrupters, are essential components of electrical protection systems. They automatically disconnect the electrical circuit when it becomes overloaded or when a short circuit occurs. They are used in electrical installations to protect equipment and people from electrical faults. Circuit breakers come in various types and have different characteristics depending on the installation location, circuit load, and other specifications.
Circuit Breaker Characteristics:
B, C, and D Characteristics:
B characteristic: Used in residential areas or low-load systems. They operate when the current exceeds the nominal current by 3 to 5 times.
C characteristic: Commonly used in both residential and commercial or industrial spaces. Their operating threshold is 5 to 10 times the nominal current, making them suitable for loads with high inrush currents (e.g., motors, lighting systems).
D characteristic: Used in industrial installations where loads have very high inrush currents (e.g., compressors, transformers). They operate when the current exceeds the nominal by 10 to 20 times.
Advantages (Pros) of Circuit Breakers:Safety: Circuit breakers ensure that the circuit is automatically disconnected in case of overload or short circuit, preventing wire burning, equipment damage, or even fires.
Reliability: They are highly reliable and can operate for long periods without maintenance, reacting automatically when electrical faults occur.
Ease of use: There is no need to replace the breaker after it trips. After an overload or short circuit, the circuit breaker can simply be reset to its operational position, avoiding the need to replace fuses.
Precision: Circuit breakers operate accurately according to the nominal current and circuit characteristics, ensuring minimal unnecessary power interruption.
Protection against short circuits and overloads: Breakers not only protect against short circuits but also against prolonged overloads, which can be harmful to electrical systems.
Versatility: There are various types of circuit breakers suitable for different systems, from small household installations to large industrial systems.
Easy reset: After a trip, the breaker can simply be reset without the need to replace it (unlike fuses that need to be replaced after a trip).
Disadvantages (Cons) of Circuit Breakers:High cost: Circuit breakers, especially those with more complex functions (e.g., adjustable protection limits), are more expensive than simple fuses.
Limited operating range: While breakers provide protection against overloads and short circuits, they cannot protect against all types of electrical faults, such as overvoltage. Additional protection devices are required for that.
Larger size: Circuit breakers are generally larger than fuses, meaning their installation may require more space in the distribution panel.
Limited protection against frequent overloads: If the electrical system experiences frequent overloads, circuit breakers may not fully protect equipment from long-term damage caused by continuous overload exposure.
More complex repair: Some complex circuit breakers may require more maintenance or repairs if they malfunction or trip incorrectly.
Applications of Circuit Breakers:Household Installations:
B characteristic breakers are most commonly used in residential installations to protect circuits from short circuits and overloads. They are suitable for lighting circuits, plugs, and other low-load devices.
C characteristic breakers are also used in homes but are better suited for areas with higher inrush currents, such as electric motors or heaters.
Commercial and Industrial Installations:C characteristic breakers are often used in commercial and industrial buildings. They are suitable for electrical equipment with medium inrush currents.
D characteristic breakers are used in industrial equipment where large inrush currents occur, such as for heavy motors, transformers, or high-power equipment protection.
Large Mechanisms and Industrial Equipment:D characteristic breakers are used where the inrush currents are very high. This includes electrical network distribution sections, industrial machinery, and transformers.
Protection of Electronics Equipment:Certain types of circuit breakers are used to protect electronic equipment, such as in server rooms or other sensitive systems where fast and precise protection is required.
Conclusion:
Circuit breakers are essential in modern electrical systems to ensure safe power supply and protection from faults. They have many advantages, such as reliability, safety, and easy resetting, but they also have some drawbacks, such as higher cost and larger size. Their selection depends on the intended use and required protection parameters.K – Trips when the current is 8-12 times higher than the nominal current, designed to protect circuits powering motors, capacitors, and transformers.
S – Trips when the current is 13-17 times higher than the nominal current, designed for the protection of control transformers.
Z – Trips when the current is 2-3 times higher than the nominal current, designed for the protection of computer equipment and other electronic components and devices.
This product is marked with the CE label, which confirms that it complies with all applicable European Union directives and regulations. CE marking is not just a formality – it is an important indicator of quality and safety, ensuring that the product has been properly assessed, tested, and can be safely used throughout the EU market.
CE certification means that the product has been evaluated according to the main criteria:
Safety requirements – ensures that the product does not pose a risk to the user or the environment
Electromagnetic compatibility (EMC) – the device does not interfere with other equipment and is resistant to external disturbances
Environmental standards – complies with current ecological and material usage requirements
Operational reliability – the product is suitable for long-term use according to its intended purposeCE marking allows this product to:
be legally supplied and used in all European Union countries
ensure a high level of quality and safety
be used in residential, commercial, and industrial environmentsThe CE mark is a declaration of the manufacturer’s responsibility, confirming that the product complies with all applicable standards and has been assessed according to EU legislation.
What does this mean for you as a buyer?
Safe use in everyday activities
Reliable performance and reduced risk of failure
Compliance with EU standards and requirements
Suitability for professional solutions