Products catalog

  • CYKY-L 5G2.5 | 5×2.5 mm² | Copper power cable | 450/750 V | black | 1 m | Lietkabelis

    Code: CYKY-L 5G2,5
    Barcode: 4779026553345

    CYKY-L 5G2.5 (5×2.5 mm²) – 450/750 V copper power cable for three-phase 400 V circuits with neutral. Solid cores, PVC insulation and sheath, suitable indoors, outdoors and in the ground. AB Lietkabelis, price per 1 m.

  • CYKY-L 5G2.5 | 5×2.5 mm² | Copper power cable | 450/750 V | black | 1 m | Lietkabelis

    CYKY-L 5×2.5 mm² is a copper power cable made by AB Lietkabelis with 5 solid cores, PVC insulation and a black PVC sheath. It is designed for supplying and distributing electrical power in dry and damp rooms, outdoors and in the ground. Cores: L1, L2, L3, N, PE.

    Key point:
    This is a versatile cable for three-phase 400 V circuits with neutral: the same cable suits both a board feed indoors and a trench between buildings. The 2.5 mm² cross-section is the most common choice for socket circuits and low-power loads. Price is per 1 m.
    Cores
    5 × 2.5 mm² Cu – L1, L2, L3, N, PE
    Rated voltage
    450/750 V (U0/U)
    Outer diameter
    10.31 mm – for choosing the cable gland
    Current rating (approx.)
    ~24 A (method C, +30 °C)
    Fire class (CPR)
    Eca (EN 50575)
    Installation
    indoors, outdoors, in ground

    Construction and operating principle

    Each core is a solid annealed copper wire (class 1 to LST EN 60228) with TI1 type PVC insulation. The insulated cores are twisted together and covered with EPDM filler and a TM1 type PVC sheath, so the cable is round, robust and seals well in cable glands.

    Core colours to LST HD 308: brown, black, grey, blue, green/yellow (PE). The green/yellow core is used only as the protective PE conductor.

    Under normal conditions the conductor may reach +70 °C, and +160 °C during a short circuit. The permissible current depends on the installation method: in air, in conduit or in the ground the cable cools differently, so the same 2.5 mm² cross-section has a different current rating on different routes.

    Why choose CYKY-L 5G2.5?
    One cable type for the whole route – from the board indoors to a load outdoors or in another building, without joints when passing from inside into the ground. The 5×2.5 mm² configuration directly matches its purpose: three-phase 400 V circuits with neutral.

    Technical specifications

    Product type Copper power cable with PVC insulation and PVC sheath
    Manufacturer AB Lietkabelis (Lithuania)
    Model / designation CYKY-L 5G2.5
    Number of cores and cross-section 5 × 2.5 mm²
    Core functions L1, L2, L3, N, PE
    Core colours (LST HD 308) brown, black, grey, blue, green/yellow (PE)
    Conductor Solid, annealed copper, class 1 (LST EN 60228)
    Conductor resistance at +20 °C, max. 7.41 Ω/km (LST EN 60228)
    Insulation TI1 type PVC (LST EN 50363-3)
    Filler EPDM
    Sheath TM1 type PVC (LST EN 50363-4-1), black
    Rated voltage U0/U 450/750 V
    Test voltage 2 kV
    Outer diameter (approx.) 10.31 mm
    Weight (approx.) 221 kg/km
    Minimum bending radius > 5 cable diameters (~52 mm)
    Max. conductor temperature +70 °C; short circuit +160 °C
    Thermal shock 1 h at +150 °C
    Installation temperature -5 °C to +40 °C
    Operating temperature -30 °C to +70 °C
    Approx. current rating 24 A (3 loaded cores); HD 60364-5-52, method C, +30 °C
    Flame propagation Test to LST EN 60332-1-2
    Reaction to fire class (CPR) Eca (LST EN 50575), DoP LK-DoP 02/002/LT
    Compliance 2011/65/EU (RoHS), 2014/35/EU (LVD), Regulation (EU) No 305/2011
    Installation Dry and damp rooms, outdoors, in the ground
    Sales unit 1 m

    Diameter and weight are the manufacturer’s approximate values. The current rating is indicative: the final value is recalculated for the installation method, cable grouping and ambient temperature.

    Main features

    • Solid class 1 copper cores – hold firmly in terminals and are easy to shape in boards.
    • TM1 PVC sheath and EPDM filler – protect the cores and allow the cable to be laid in damp rooms, outdoors and in the ground.
    • 450/750 V rated voltage – a higher margin than 300/500 V installation cables.
    • Colour coding to HD 308 – clear identification of L, N and PE, fewer wiring errors.
    • Eca class under CPR – the cable has a declaration of performance required for construction products.
    • Sold by the metre – you buy exactly the length the route needs.

    Where is it used?

    • Three-phase 400 V lines with N and PE
    • Distribution boards, three-phase sockets, workshops
    • Outdoor and outbuilding socket circuits
    • Pumps, compressors, small heaters
    • Cable routes in the ground between buildings, in concrete, conduits and cable trunking
    • Damp and wet rooms: basements, boiler rooms, garages, outbuildings

    Use by need

    For a designer.
    A five-core TN-S solution: separate N and PE cores along the entire run.
    For an installing electrician.
    One cable for three-phase sockets, boards and high-power loads – indoors, outdoors and in the ground.
    For a homeowner.
    Supplying three-phase sockets or small three-phase loads in a garage or outbuilding.

    Practical application

    If outbuilding sockets located 40 m away needs a three-phase supply and the expected current is about 10 A, CYKY-L 5G2.5 can be laid in a trench directly in the ground. Approximate voltage drop: √3 × 10 A × 40 m × 7.41 Ω/km ≈ 5.1 V, i.e. about 1.3 % of 400 V (calculated with conductor resistance at +20 °C). The final cross-section and protective device are selected according to the design and installation conditions.

    Pros

    • Suitable indoors, outdoors and in the ground – one cable for the whole route
    • 450/750 V rated voltage
    • Solid copper cores – reliable contact in terminals
    • Made in Lithuania (AB Lietkabelis), declared Eca class
    • Compact: ~10.31 mm diameter for a 5×2.5 mm² cable
    • Sold by the metre

    Cons / limitations

    • Solid cores are not suitable for moving equipment or frequent bending – use a flexible cable (e.g. H07RN-F) for that.
    • PVC sheath: do not install below -5 °C.
    • Eca class is not suitable where the design requires a higher CPR class or a halogen-free cable.
    • The manufacturer does not declare UV resistance – use conduit or trunking for long-term direct sun exposure.

    Safety and installation notes

    • Before installation, isolate the circuit and verify that it is dead.
    • Bending radius – at least 5 cable diameters (about 52 mm).
    • Do not install below -5 °C – cold PVC may crack.
    • When laying in the ground, follow installation rules: proper depth, sand bedding, warning tape, mechanical protection under roads and driveways.
    • Select the protective device according to the cable’s permissible current under the actual installation conditions.
    • Use the green/yellow core only as PE – never as a phase or neutral.
    • Work must be carried out by a qualified electrician; measure insulation resistance after installation.

    Quick selection guide

    5×2.5 mm²
    450/750 V
    L1, L2, L3, N, PE
    Ø ~10.31 mm
    Eca (CPR)
    Suitable when you need:
    • Three-phase 400 V circuits with neutral
    • Outdoor and outbuilding socket circuits
    • To lay the cable in the ground or in a damp environment
    Check before use:
    • Permissible current and protective device for the installation method
    • Voltage drop on long runs
    • Whether the design requires a higher CPR class
    • Cable gland and seal size for the ~10.31 mm diameter
    Important reminder: The cable does not replace calculation – cross-section, protection and installation method are confirmed by the electrical design or a qualified electrician.

    FAQ

    What does the designation 5G2.5 mean?
    5 cores of 2.5 mm², one of which is the green/yellow protective PE core (letter “G”).
    Can CYKY-L 5G2.5 be laid in the ground?
    Yes, the manufacturer states that the cable may be laid in the ground; in a trench follow installation rules for depth, warning tape and mechanical protection.
    What current can a 5×2.5 mm² cable carry?
    Approximately 24 A (3 loaded cores) to HD 60364-5-52 (method C, +30 °C); in the ground, in groups or at higher ambient temperature the value is recalculated.
    How does CYKY-L differ from NYM-J?
    NYM-J (300/500 V) is intended for installation inside buildings, while CYKY-L is a 450/750 V cable that can be laid both outdoors and in the ground.
    What are the cable diameter and weight?
    According to the manufacturer – about 10.31 mm and 221 kg/km.
    At what temperature can it be installed?
    Install from -5 °C to +40 °C; operate from -30 °C to +70 °C.

    CYKY-L 5G2.5 | 5×2.5 mm² | Copper power cable | 450/750 V | black | 1 m | Lietkabelis

    CYKY-L 5G2.5 is an AB Lietkabelis copper power cable, 5×2.5 mm², 450/750 V, with solid cores and a black PVC sheath, intended for three-phase 400 V circuits with neutral. Suitable for laying indoors, outdoors and in the ground; Eca class, sold by the metre.

    Published: 2026-11-13 · Data verified against the manufacturer’s datasheet: 2026-11-13

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • Alternative products

    Cable sheath and wire stripper 0.2–4.0 mm² | ErgoStrip KNIPEX
    Code: 169501SB

    KNIPEX high-quality, ergonomically designed wire and cable stripping tool for fast, precise, and safe work. This stripping knife is highly favored by professional electricians for its versatility, durability, and practical design. Suitable for removing insulation from both signal and power wires, as well as for installation, data, and coaxial cables.

    Perfectly suited for use on construction sites and in domestic installations, especially where wires need to be quickly and accurately prepared for connection in confined spaces. 

    Price 48.40 € VAT incl.
    ( 40.00 € VAT excl. )
    Cable Cutting Scissors | 240mm² | TLK10-250 | 4606056165289
    Code: TLK10-250

    Professional cable cutting scissors designed for reliable cutting of copper and aluminum cables with a cross-section of up to 240 mm². These scissors are an essential tool for electrical installations, cable laying works, and for use in the industrial and energy sectors. The tool operates with a two-handed mechanism, ensuring greater safety and cutting precision. The high-quality construction allows operation under various environmental conditions.

    Price 48.67 € VAT incl.
    ( 40.23 € VAT excl. )
    Holder | fastening strap | 22 mm | black | UP-22 | 5901350805718
    Code: UP-22

    Holder – a fastening tie designed for securing and organizing cables, wires, and various components. This compact yet strong tie ensures reliable fixation, aesthetics, and safety in electrical installations as well as in household or industrial systems. Due to its simple installation and universal size, this holder is indispensable for both professionals and everyday users. 

    Price 0.09 € VAT incl.
    ( 0.07 € VAT excl. )
  • privacy policy

    Information