Products catalog

  • Industrial mechanical thermostat | -35…+20 °C | 15(6) A 250 V AC | SPDT | IP65 | internal adjustment | Fantini Cosmi C10C2RIY

    Code: C10C2RIY

    Sealed IP65 mechanical thermostat for cold and chilled rooms that senses ambient air within -35…+20 °C. Temperature is set under the cover so others cannot change it, and the SPDT contact rated 15(6) A 250 V AC switches heating or cooling.

  • Industrial mechanical thermostat Fantini Cosmi C10C2RIY, -35…+20 °C, 15(6) A 250 V AC, IP65

    Fantini Cosmi C10C2RIY is a mechanical room (ambient air) thermostat in a sealed IP65 housing with internal adjustment: there is no knob, the temperature is set with the cover removed. Temperature is sensed by a liquid-filled spiral capillary that operates a microswitch via a stainless steel membrane. The scale is -35…+20 °C. Designed for cold rooms, refrigerated warehouses, outdoor cabinets and public technical rooms.

    ⚠ ⚠ 15(6) A contact per EN 60730-1: resistive load up to 15 A, inductive (cos φ 0.6) up to 6 A; for electromagnetic loads (AC-15, e.g. contactor coils) the manufacturer specifies 2.5 A at 220–250 V AC. Switch motors, compressors and larger fans via a contactor.
    Key idea:
    It is a simple and reliable way to hold temperature where electronic controllers struggle: dust, moisture, cold. The thermostat needs no power supply – it simply opens or closes the circuit. The SPDT contact lets the same device be used for heating as well as ventilation or cooling. The 2 K differential protects equipment from short cycling.
    Scale
    -35…+20 °C
    Contact
    SPDT 15(6) A 250 V AC
    Differential
    2 ± 0.5 K
    Protection
    IP65

    Operating principle

    The sensing element is a liquid-filled spiral capillary made of tinned copper. As air temperature changes, the liquid volume changes and transfers force through a stainless steel membrane to a snap-action microswitch.

    On rising temperature contact 1-2 opens, 1-4 closes. For heating use circuit 1-2 (the heater switches off at the setpoint); for ventilation or cooling use 1-4 (the fan switches on when temperature rises).

    The 2 ± 0.5 K differential is subtracted from the scale value: with a setting of +10 °C, heating switches back on at about +8 °C.

    Why choose the C10C2RIY?
    The -35…+20 °C range covers cold rooms and harsh climates where most domestic thermostats no longer work. Because the setting is under the cover, neither warehouse staff nor outsiders can turn it by accident.

    Technical specifications

    Product type Mechanical room (ambient) thermostat
    Manufacturer / model Fantini Cosmi C10C2RIY
    Scale range -35…+20 °C
    Differential 2 ± 0.5 K (subtracted from the scale value)
    Calibration accuracy ± 2 °C
    Adjustment Internal, under the cover (no knob)
    Contact SPDT, snap-action microswitch; on rising temperature 1-2 opens, 1-4 closes
    Contact rating (EN 60730-1) 15(6) A, 250 V~, 50 Hz
    AC-12 / AC-15 (220–250 V~) 15 A / 2.5 A
    DC-13 0.2 A
    Insulation voltage Ui / Ith 380 V~ / 15 A
    Operating principle Liquid expansion, spiral tinned copper capillary, stainless steel membrane
    Max. permissible body temperature 50 °C
    Degree of protection IP65
    Housing Impact-resistant, self-extinguishing V0 thermoplastic
    Cable entry Cable gland
    Mounting Wall
    Weight 0.16 kg
    Standards EN 60730-1, EN 60730-2-9, EN 60947-5-1

    Main functions

    • Ambient temperature sensing – the spiral capillary reacts quickly to room air temperature.
    • SPDT changeover contact – one device for heating (1-2) or ventilation (1-4).
    • Direct load switching – resistive loads up to 15 A without an interposing relay.
    • Fixed 2 K differential – stable operation without frequent contact switching.
    • IP65 housing – works in damp, dusty environments.
    • No power supply needed – no electronics to fail from frost or surges.

    How does it differ from similar products?

    Fantini Cosmi C10B2Y Scale -20…+40 °C and an external knob – when the setting must be easy to change and a higher upper limit is needed.
    DIN-rail panel thermostat Mounted inside the panel to control a panel heater; the C10C2RIY is wall-mounted and measures the whole room.
    Electronic thermostat with display More accurate and shows temperature but needs power; the C10C2RIY works mechanically and tolerates harsh conditions better.

    Where is it used?

    • Unheated and heated warehouses
    • Cold rooms and refrigerated warehouses (down to -35 °C)
    • Greenhouses and growing rooms
    • Meat and cheese curing rooms
    • Industrial electrical panels and outdoor cabinets
    • Pump stations, boiler rooms, technical rooms

    Use by need

    Beginner.
    For heating, connect the phase to terminal 1 and the heater to terminal 2. With the voltage disconnected, remove the cover, set the temperature and close it – the setting stays protected.
    Experienced installer.
    Use terminal 4 for ventilation or alarm, and switch inductive loads above 2.5 A via a contactor.
    Energy engineer / designer.
    Take into account the ± 2 °C calibration accuracy and 2 K differential – for critical processes add a second thermostat for alarm.

    Practical use

    In an outdoor telecom cabinet with batteries, the C10C2RIY is set to +5 °C: contact 1-2 switches on a panel heater when temperature drops to about +3 °C. With no knob, service staff cannot change the setting by accident.

    Pros / advantages

    • IP65 – suitable for damp and dusty rooms
    • -35…+20 °C range for cold rooms and cold climates
    • SPDT contact for heating or cooling
    • Resistive loads up to 15 A directly
    • No power supply needed, simple wiring
    • Complies with EN 60730-1, EN 60730-2-9, EN 60947-5-1

    Cons / limitations

    • No temperature indication
    • Calibration accuracy ± 2 °C – not for laboratory precision
    • Inductive load only up to 2.5 A (AC-15)
    • Changing the setting requires disconnecting the voltage and opening the cover

    Safety and installation notes

    • ⚡ Installation and connection by a qualified electrician; disconnect power before opening the cover.
    • ⚡ Protect the circuit with a circuit breaker not exceeding the contact and cable ratings.
    • Mount on a wall in the zone whose temperature must be held, away from heaters, doors and direct sunlight.
    • Route the cable through the gland and tighten it properly – otherwise IP65 is not maintained.
    • Body temperature must not exceed 50 °C.
    • Do not use in explosive atmospheres without Ex certification.

    Quick selection guide

    -35…+20 °C
    SPDT 15(6) A
    IP65
    Internal adjustment
    Suitable when you need:
    • to hold air temperature in a warehouse or greenhouse
    • to protect a room or panel from freezing or overheating
    • reliable mechanical control in a damp environment
    Check before choosing:
    • Whether the required temperature is within -35…+20 °C
    • Load type and current (resistive up to 15 A, inductive up to 2.5 A)
    • Whether internal adjustment suits you (if it must be changed often, choose the knob version)
    Important reminder: The C10C2RIY measures the air around itself – it is not intended for liquid or pipe temperature. For that use a thermostat with a remote sensor or an immersion sensor in a thermowell.
    ☝ Elsprendimai.eu recommends:

    FAQ

    Is the C10C2RIY suitable for heating and cooling?
    Yes. Contact 1-2 is used for heating and 1-4 for ventilation or cooling, because on rising temperature 1-2 opens and 1-4 closes.
    What load can be switched directly?
    Resistive up to 15 A and inductive (cos φ 0.6) up to 6 A per EN 60730-1; electromagnetic loads (AC-15) up to 2.5 A at 220–250 V AC. Switch motors and larger loads via a contactor.
    Does the thermostat need a power supply?
    No. It is a mechanical device that only switches a contact, so no neutral connection is required.
    Why does the thermostat have no knob?
    In the RI version the temperature is set under the cover – this protects against accidental or unauthorised changes in public and technical rooms.
    Can it be installed outdoors?
    The housing is IP65, but protect it from direct sun and precipitation so it measures the true air temperature.
    How accurate is the thermostat?
    The manufacturer states ± 2 °C calibration accuracy and a 2 ± 0.5 K differential.

    Sources: Fantini Cosmi C10..Y series datasheet, C10 series technical sheet. Checked 2026-10-18.

    Fantini Cosmi C10C2RIY – IP65 thermostat for cold with a protected setting

    Fantini Cosmi C10C2RIY is a mechanical IP65 ambient thermostat for the -35…+20 °C range with internal adjustment and an SPDT contact rated 15(6) A 250 V AC. It suits cold rooms, refrigerated warehouses and outdoor cabinets where the setting must be protected.

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • Alternative products

    Smart | remote water valve controller | 12V | 1.6 MPa | Wi-Fi | Tuya | NOUS-L3 | 5907772033951
    Code: NOUS-L3

    NOUS L3 smart remote water valve controller is a practical solution that allows you to open or close a water valve remotely via a smartphone. The device operates via a 2.4 GHz Wi-Fi connection, is controlled through the Nous Smart Home app, and is compatible with Amazon Alexa and Google Assistant voice assistants.

    This controller is especially useful where it is necessary to automate water supply, reduce the risk of water leakage, or conveniently control water supply according to a schedule. It can be used for controlling a building’s water inlet, irrigation systems, filling water tanks, swimming pools, or drinking troughs. 

    Price 37.89 € VAT incl.
    ( 31.31 € VAT excl. )
  • Subscribtion to new arrivals

    privacy policy

    Information