  • Modular time relay | timer | for forward/reverse motor direction control | 1s-100min | 5A | 230VAC | DIN

    Code: ES-ERS-07

    The electronic right–left cyclic time relay is designed for alternating control of two electrical loads, contactors, or drive directions. When power is applied, the right output is activated first. After the preset operating time has elapsed, it is switched off, the preset pause is observed, and then the left output is activated.

    The operating time of the right and left outputs is identical. According to the manufacturer's specifications, the time is adjustable from 1 second to 100 minutes. The R, OFF, and L LED indicators display the operating status of the right output, pause, and left output. 

  • Cyclic right–left timer relay for two loads – 1 s–100 min, 230 V AC, 5 A, DIN

    Electronic cyclic right–left timer relay is designed for alternating control of two electrical loads, contactors or drive directions. When power is applied, the right-direction output is activated first. After the preset operating time has elapsed, it is switched off, the preset pause is observed and the left-direction output is then activated.

    The operating duration of the right and left outputs is the same. According to the information supplied by the manufacturer, the time can be adjusted from 1 second to 100 minutes. The R, OFF and L LED indicators allow the right-direction, pause and left-direction operating stages to be monitored.

    Important information about the time settings:
    The supplied manufacturer description specifies an overall 1 s–100 min adjustment range, but it does not clearly explain whether the operating and pause times are set using separate controls or whether a common time value is used. Before connection, the front-panel markings and instructions for the specific product must be checked.
    Important information about reversing the motor direction:
    If the relay is used to reverse the direction of rotation of a three-phase motor, its outputs must control the coils of the forward and reverse contactors. The motor power circuit must not be connected directly through the timer relay. The direction contactors must be electrically interlocked and, where specified, mechanically interlocked.
    Main application:
    The relay is used in systems where two loads or two control directions must operate alternately: the first load is switched on for the preset time, a pause follows after it is switched off, and the second load is then switched on for the same operating time.
    Supply voltage
    230 V AC
    Time range
    1 s–100 min
    Controlled outputs
    RIGHT and LEFT
    Contact rating
    5 A / 250 V AC
    Indication
    R, OFF and L LEDs
    Mounting
    On a DIN rail

    Alternating control principle

    The relay is designed for two independent control directions or loads that must operate alternately rather than simultaneously. When the relay power supply is switched on, the operating sequence begins with the right-direction, or R, output.

    When the preset operating time has elapsed, the right-direction output is switched off. The relay then begins counting the waiting, or OFF, time, during which neither the right-direction nor the left-direction output is active.

    After the pause has elapsed, the left-direction, or L, outputis switched on. The left-direction operating time is the same as the right-direction operating time. According to the functional purpose of the relay, the sequence may repeat cyclically after the left-direction stage.

    Alternating control sequence:
    Power connected → RIGHT output switched on → preset operating time → RIGHT switched off → OFF pause → LEFT output switched on → preset operating time → next cycle stage.
    Cycle repetition:
    The supplied text describes the transition from the RIGHT output to the LEFT output in detail, but it does not clearly state whether the relay automatically returns to the OFF pause and starts a new RIGHT cycle after the LEFT operating time. Because the product is described as an alternating-function timer relay, cyclic operation is likely, but this must ultimately be verified against the diagram for the specific model.

    Operating sequence

    1. 230 V AC power is connected. The relay begins the alternating control sequence.
    2. The RIGHT output is activated. According to the supplied description, contact terminals 2 and 3 are connected.
    3. The RIGHT operating time is counted. The R LED indicator flashes and shows the active right-direction stage.
    4. The RIGHT output is switched off. When the operating time has elapsed, the circuit between contacts 2 and 3 opens.
    5. The OFF waiting time begins. At this time, neither the RIGHT nor the LEFT output is active, and the OFF LED flashes.
    6. The LEFT output is activated. After the pause has elapsed, the left-direction relay output is switched on.
    7. The LEFT operating time is counted. The L LED indicator flashes and shows the active left-direction stage.
    8. The left-direction stage is completed. Further repetition of the sequence depends on the functional diagram of the specific model.

    Equal operating duration for both outputs

    According to the manufacturer’s description, the right- and left-direction operating times are the same. This means that the selected operating duration applies to both outputs.

    This operating principle is suitable for processes in which both loads must operate for equal intervals, for example, to distribute the operating time of two pumps, fans or other mechanisms evenly.

    Time-setting accuracy:
    The supplied specification does not state the time-setting tolerance, repeatability or scale accuracy. When an exact interval is important to the process, the set time must be verified under actual operating conditions.

    OFF waiting time

    Between switching off one load and switching on the other, the relay creates a waiting period. During this time, both relay outputs are switched off.

    The pause can be used to allow a mechanical drive to stop completely, reduce transient processes, prevent an abrupt change of direction or ensure that the two loads cannot operate together even briefly.

    A suitable pause is required for direction reversal:
    The motor direction should not be reversed while the motor is still rotating in the opposite direction unless the drive and control system are specifically designed for this. The pause duration must be selected according to the motor inertia, load and mechanism stopping time.

    LED status indication

    R LED

    • indicates the right-direction operating stage;
    • flashes while the RIGHT operating time is being counted;
    • is associated with the right-direction relay output;
    • goes out when the RIGHT operating time has elapsed.

    OFF LED

    • indicates the intermediate waiting stage;
    • flashes while the OFF pause is being counted;
    • both outputs are switched off during the pause;
    • goes out when the next operating stage begins.

    L LED

    • indicates the left-direction operating stage;
    • flashes while the LEFT operating time is being counted;
    • is associated with the left-direction relay output;
    • goes out when the LEFT operating time has elapsed.

    Relay outputs and contacts

    The contact rating specified by the manufacturer is 5 A / 250 V AC for a resistive load. According to the supplied operating description, contact terminals 2 and 3 are connected when the output is activated.

    If the relay is used to control contactors, solenoids, valves or motors, it must be taken into account that these are not resistive loads. Their making and breaking currents may be higher than the rated operating current.

    For inductive and capacitive loads:
    Contactor coils, solenoids, motors, transformers, LED power supplies and other non-resistive loads may require interposing relays, contactors and suitable surge-suppression measures.

    Use for reversing the motor direction

    The relay can be used as a timing control element for the forward and reverse contactors of a three-phase motor. In such a system, the relay itself switches only the contactor control circuits.

    • two correctly selected direction contactors are required;
    • the contactors must be electrically interlocked;
    • mechanical interlocking is recommended where required by the design;
    • two phases are interchanged in the motor power circuit;
    • motor overload protection must be installed;
    • short-circuit protection must be provided;
    • the OFF pause must be long enough for the mechanism to stop;
    • the drive must be suitable for periodic direction reversal.
    Simultaneous activation of both directions is prohibited:
    Simultaneous operation of the forward and reverse contactors can cause a short circuit in the power circuit. Therefore, the timer relay cannot be the only protective measure — contactor interlocking is essential.

    Technical specifications

    Product type Electronic alternating right–left control timer relay
    Function RIGHT → OFF → LEFT alternating control sequence
    Number of controlled loads 2 loads or 2 control directions
    Supply voltage 230 V AC
    Operating frequency 50 / 60 Hz
    Power consumption Less than 5 VA
    Time range 1 s–100 min
    RIGHT and LEFT operating time The same for both outputs
    OFF waiting time Adjustable according to the product settings; check the diagram
    Outputs RIGHT and LEFT relay outputs
    Contact rating 5 A / 250 V AC, resistive load
    Contact state when the output is activated Terminals 2 and 3 are connected, according to the supplied description
    Indication 3 LEDs — R, OFF and L
    Connection method Terminal connection
    Conductor cross-section Up to 2.5 mm²
    Operating temperature −20 °C to +55 °C
    Operating altitude Less than 2000 m above sea level
    Mounting On a DIN rail
    Weight Less than 125 g
    Operating environment Dry indoor environment, protected electrical enclosure
    Degree of protection Not specified in the supplied specification

    Main functions and features

    • Alternating control of two outputs — for two loads or two directions.
    • RIGHT → OFF → LEFT sequence — with an intermediate pause between the outputs.
    • Equal operating time for both outputs — for a symmetrical cycle.
    • 1 s–100 min time range — for short and longer operating intervals.
    • R, OFF and L LED indicators — for monitoring each cycle stage.
    • 5 A / 250 V AC contacts — for a resistive load.
    • 230 V AC supply — for typical control circuits.
    • Power consumption below 5 VA.
    • DIN-rail mounting.
    • Operating temperature from −20 to +55 °C.

    Where is it used?

    • For motor direction control — to activate the forward and reverse contactors alternately.
    • In mixing equipment — to change the mixer direction periodically.
    • In conveyors — to create forward and reverse movement cycles.
    • In gate and mechanical drive systems — when alternating two-direction control is required.
    • In two-pump systems — to switch the loads on alternately.
    • In ventilation systems — to control two fans alternately.
    • In production equipment — for repeating two-action sequences.
    • In industrial automation panels — to control two contactors or interposing relays.
    • In process lines — when the opposite operation must be performed after one operation and a pause.

    Practical application example

    For example, a three-phase mixer motor must periodically rotate in the right and left directions. The relay’s RIGHT and LEFT outputs are connected to two mutually interlocked direction contactors.

    With the operating time set to 30 seconds, the RIGHT output is activated first when power is switched on. The forward contactor starts the motor and the R LED indicator flashes.

    After 30 seconds, the RIGHT output is switched off and the preset OFF pause begins. During this time, the motor is disconnected and has time to stop.

    After the pause has elapsed, the LEFT output is activated. The reverse contactor interchanges two motor phases, causing the motor to rotate in the opposite direction.

    If the specific model operates cyclically, the sequence starts again after the left-direction operating time.

    Mounting method

    DIN-rail mounting

    • suitable for standard electrical and automation panels;
    • the relay must be securely fixed to the DIN rail;
    • the mounting location must be dry and protected;
    • the terminals must remain accessible for inspection and maintenance;
    • adequate clearance must be maintained from components that become very hot;
    • the wires must be routed neatly and without tension.

    Installation and commissioning instructions

    1. Disconnect the supply voltage. The control and power circuits must be completely de-energised.
    2. Check the supply parameters. The relay is intended for a 230 V AC, 50 / 60 Hz control circuit.
    3. Mount the relay on the DIN rail. Check that it is properly secured.
    4. Check the product diagram. Follow the terminal numbering shown on the specific product.
    5. Connect the relay power supply. Use conductors with a suitable cross-section.
    6. Connect the RIGHT output. Connect it to the first load or the forward contactor control circuit.
    7. Connect the LEFT output. Connect it to the second load or the reverse contactor control circuit.
    8. Install contactor interlocking. The direction contactors must not be energised simultaneously.
    9. Set the operating time. Select the required value from 1 s to 100 min using the product controls.
    10. Set the OFF pause. Select a waiting time suitable for the process and the mechanism stopping time.
    11. Perform a test without the power load connected. Check the RIGHT, OFF and LEFT sequence.
    12. Check the LED indicators. The R, OFF and L indication must correspond to the active cycle stage.
    13. Check that the contactors release. Before the opposite direction is energised, the first contactor must be completely de-energised.
    14. Perform a trial operating cycle. Observe the motor stopping, direction reversal, current and mechanism operation.
    Protective and disconnecting devices:
    The circuit must include a circuit breaker and a disconnecting switch that is easily accessible to the operator. They must be clearly marked as the disconnecting devices for the relay and the controlled system.

    Cleaning and maintenance

    • Completely disconnect the power supply before cleaning.
    • Disconnect the relay from the connected circuits.
    • Clean the enclosure with a dry, soft swab or cloth.
    • Do not use electrically conductive cleaning materials.
    • Do not use aggressive chemicals or solvents.
    • Do not allow water to enter the terminals or enclosure.
    • Check the terminal tightness and the condition of the wires.
    • Check the contactor interlocking circuit.
    • After maintenance, perform a trial cycle of the complete sequence.

    Installation and usage notes

    • Use the relay only for its intended purpose and in accordance with the wiring diagram.
    • Do not use the relay in a damp environment.
    • Disconnect all circuits before installation or maintenance.
    • Do not exceed the rated 230 V AC supply voltage.
    • Do not connect the motor power circuit directly through the relay.
    • Use suitable contactors to control the motor directions.
    • The forward and reverse contactors must be interlocked.
    • Simultaneous energisation of both direction contactors is prohibited.
    • The OFF pause must be long enough for the mechanism to stop.
    • The 5 A / 250 V AC rating is specified for a resistive load.
    • Contactor coils and solenoids are inductive loads.
    • The relay must be installed in a protected electrical enclosure.
    • Do not use the device at an altitude above 2000 m above sea level.
    • Connection work must be carried out by a qualified electrical specialist.
    • Check the complete alternating control sequence before operation.

    Advantages

    • Automatic alternating control of two outputs.
    • RIGHT, OFF and LEFT operating sequence.
    • Equal operating duration for both loads.
    • Wide 1 s–100 min time range.
    • Intermediate pause between the two outputs.
    • R, OFF and L LED indication.
    • 5 A / 250 V AC relay contacts.
    • DIN-rail mounting.
    • Operating temperature from −20 to +55 °C.
    • Suitable for alternating control of loads or drive directions.

    Limitations

    • Not suitable for switching the motor power current directly.
    • Two contactors are required for direction control.
    • Contactor interlocking is required.
    • The pause must be selected according to the mechanism stopping time.
    • The 5 A rating applies to a resistive load.
    • Additional measures may be required for inductive loads.
    • Not intended for a damp environment.
    • Degree of protection not specified.
    • Time-setting tolerance not specified.
    • It is unclear whether both times are adjusted separately.
    • Cycle repetition must be checked against the diagram for the specific model.

    Quick selection guide

    Choose a right–left alternating control timer relay when two loads or two motor direction contactors must be controlled alternately for equal time intervals, with a safe switch-off pause between them.

    Supply
    230 V AC
    Time range
    1 s–100 min.
    Contacts
    5 A / 250 V AC
    Function
    RIGHT–OFF–LEFT
    Suitable when you need to:
    • switch two loads on alternately;
    • the same operating duration for both loads;
    • a pause between the first and second load;
    • control of the forward and reverse contactors;
    • a time range of 1 second to 100 minutes;
    • R, OFF and L status indication;
    • DIN-rail mounting;
    • a 230 V AC control circuit.
    Check before ordering:
    • whether the RIGHT–OFF–LEFT function is specifically required;
    • whether the relay must repeat the cycle automatically;
    • whether the operating and OFF times are adjusted separately;
    • whether the 1 s–100 min range is sufficient;
    • what type of loads will be controlled;
    • the voltage and current of the contactor coils;
    • whether electrical and mechanical interlocking is installed;
    • whether the pause is long enough for the mechanism to stop;
    • whether the control circuit is supplied with 230 V AC;
    • whether the device will be installed in a dry environment.
    Important reminder:
    When the relay is used to reverse the motor direction, the contactors controlled by the RIGHT and LEFT outputs must not be active at the same time. Suitable electrical interlocking is essential, and the OFF pause must be long enough for the motor and mechanism to stop safely.

    FAQ – frequently asked questions

    What is this timer relay used for?
    It is designed to switch two loads or two control directions alternately according to a preset operating and waiting sequence.
    What is the operating sequence?
    When power is switched on, the RIGHT output is activated first. After it is switched off, an OFF pause is observed, and the LEFT output is activated when the pause has elapsed.
    Is the operating time the same for both outputs?
    Yes. According to the information supplied by the manufacturer, the operating duration of the RIGHT and LEFT outputs is the same.
    What is the time adjustment range?
    The supplied specification states an adjustment range from 1 second to 100 minutes.
    Are the operating and pause times set separately?
    This is not clearly explained in the supplied description. The front-panel controls and the manufacturer’s diagram for the specific model must be checked.
    What happens during the OFF pause?
    During the pause, neither the RIGHT nor the LEFT relay output is active, and the OFF LED indicator flashes.
    What does the R indicator show?
    It shows that the right-direction output is active and its operating time is being counted.
    What does the L indicator show?
    It shows that the left-direction output is active and its operating time is being counted.
    Does the relay repeat the cycle automatically?
    The product is described as an alternating-function relay, so cyclic operation is likely. However, the supplied text does not clearly describe the return of the cycle from LEFT to RIGHT, so this must be checked against the diagram for the specific model.
    Can a three-phase motor be connected directly?
    No. The relay must control the coils of the forward and reverse contactors. The motor power circuit must be switched by contactors.
    Is contactor interlocking required?
    Yes. The forward and reverse contactors must be electrically interlocked and, where required by the design, mechanically interlocked.
    Why is the OFF pause required?
    It separates the operation of the two outputs and can give the mechanism time to stop before the opposite direction or the other load is switched on.
    Is the contact rating 5 A?
    The 5 A / 250 V AC rating is specified for a resistive load. Contactor coils, motors and solenoids must be treated as inductive loads.
    What is the relay supply voltage?
    This relay is intended for a 230 V AC, 50 / 60 Hz control circuit.
    Can it be mounted on a DIN rail?
    Yes. The relay is designed for DIN-rail mounting in a standard electrical or automation panel.
    Can it be used in a damp environment?
    No. The manufacturer states that the device must not be used in a damp environment. The relay must be installed in a dry, protected electrical enclosure.
    What conductor cross-section can be connected?
    According to the supplied specification, conductors with a cross-section of up to 2.5 mm² can be used.

    Alternating control of two loads or motor directions with an adjustable pause

    The electronic right–left timer relay is designed to switch two loads or two control directions alternately. When power is connected, the RIGHT output is activated first and is switched off after the preset operating time has elapsed.

    After the OFF waiting interval, the LEFT output is switched on. The operating time of both outputs is the same, and the R, OFF and L LED indicators allow the active cycle stage to be monitored.

    The relay is supplied with 230 V AC, has 5 A / 250 V AC contacts for a resistive load and is mounted on a DIN rail. It can be used for contactors, interposing relays, two loads or motor direction control circuits.

    When the relay is used to reverse the motor direction, correctly selected and mutually interlocked direction contactors, motor protection and a sufficient OFF pause before energising the opposite direction are required.

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.