  • Surge protective device with integrated switch | Type 2 | 4P | 400 V AC | 20 kA (8/20) | DIN | ES-LY3027

    Code: ES-LY3027

    ES-LY3027 is a four-pole surge protective device with an integrated switch, 400 V AC, discharge current 20 kA (8/20 µs). The switch isolates the SPD for maintenance or insulation testing without touching the wiring.

  • Surge protective device with integrated switch | Type 2 | 4P | 400 V AC | 20 kA (8/20) | DIN | ES-LY3027

    ES-LY3027 is a four-pole surge protective device with an integrated switch, 400 V AC, discharge current 20 kA (8/20 µs). The switch isolates the SPD for maintenance or insulation testing without touching the wiring.

    Key point:
    This is a Type 2 SPD: it protects against switching and indirect lightning overvoltages inside the board. At an incomer exposed to partial lightning currents it is not enough on its own – a Type 1+2 is needed there.
    Class
    Type 2 / Class II / C
    Discharge current (8/20 µs)
    20 kA
    Voltage
    400 V AC
    Configuration
    4P

    Operating principle

    The SPD is mounted on a DIN rail in a distribution or automation switchboard and connected in parallel between the protected conductors and PE.

    During a surge, the varistors divert the switching or induced impulse (8/20 µs) to earth; the integrated switch allows the SPD to be disconnected from the supply.

    The switch lets you service the SPD and test insulation without disconnecting wires, then switch protection back on after the work.

    What does ES-LY3027 do for you?
    ES-LY3027 with an integrated switch simplifies maintenance: you disconnect the SPD with a handle instead of unscrewing wires – convenient in switchboards where insulation is tested frequently.

    Technical specifications

    Product type Surge protective device with integrated switch Type 2
    Manufacturer / model ES-LY3027
    Class (IEC / EN 61643-11) Type 2 / Class II / C (based on declared ratings)
    Poles / configuration 4P – for 3-phase TN-S: L1, L2, L3, N → PE
    Integrated switch Yes – to isolate the SPD
    Operating voltage 400 V AC (data provided by the supplier)
    Impulse current Iimp (10/350 µs) not stated by the manufacturer
    Discharge current (8/20 µs) 20 kA (data provided by the supplier)
    Mounting DIN rail 35 mm

    Main functions

    • T2 protection – 20 kA (8/20 µs) for switching and induced surges.
    • Integrated switch – disconnects the SPD for maintenance.
    • 4P, 400 V AC version – selected according to the circuit.
    • DIN mounting in the switchboard.
    • 1P–4P and 400 / 600 V AC versions – one series for different circuits.

    Wiring diagram – 4P (4+0) – three-phase TN-S supply

    4P (4+0) – three-phase TN-S supply – ES-LY3027 | elsprendimai.eu
    ☝ Click the diagram to open an enlarged version.
    ⚠ The diagram is for guidance only and may contain inaccuracies. Before wiring, check it against the manufacturer's instructions and the markings on the device.
    The qualified electrician carrying out the installation is responsible for it. UAB "Elektrotechnikos sprendimai" is not liable for the connection or any errors.

    Most common wiring mistakes

    ✗ Switch left off It is forgotten after testing – the SPD no longer protects, while the indication may look normal.
    ✗ T2 at a supply entry with a lightning protection system T2 is not designed for partial lightning current – the supply entry needs T1+T2.
    ✗ Unnecessarily high Uc A higher Uc increases Up – the equipment is left with a higher surge voltage.
    ✗ Long leads A total lead length of more than 0.5 m adds voltage and reduces protection.

    How does it differ from similar models?

    • ES-LY3028 – 4P | 20 kA (8/20) – Another version of this series: 4P, 600 V AC.
    • ES-LY3025 – 3P | 20 kA (8/20) – Another version of this series: 3P, 400 V AC.
    • LSP FLP12.5-275/4S – 4P TN-S | Iimp 12.5 kA | Up ≤ 1.5 kV – Iimp 12.5 kA per pole – choose it when the building has a lightning protection system. Different manufacturer. With remote signalling contact.

    Where is it used?

    • Sub-distribution boards downstream of a T1+T2 supply entry
    • AC side of a solar PV plant – the switchboard with the inverter
    • Automation and control switchboards
    • Boiler house and heat pump switchboards
    • Sites where insulation is tested frequently
    • Switchboards without a direct lightning current hazard

    Selection and installation

    • The supplier states 400 V or 600 V AC but does not specify whether this is Uc or Un and gives no Up. Ask us for the Uc and Up values before ordering. A normal TN 230/400 V network needs Uc 275–320 V, an IT network needs Uc ≥ 440 V L–PE.
    • 1P – one line, 2P – single-phase circuit (L and N → PE), 3P – three-phase TN-C, 4P – three-phase TN-S.
    • The manufacturer does not state Iimp (10/350 µs), so this SPD is not intended for an incomer with an LPS or overhead line – install a Type 1+2 there.

    Use by need

    For the electrician.
    Disconnection by switch – no need to unscrew wires for insulation testing.
    For the switchboard manufacturer.
    One series, 1P–4P, for different circuits.
    For the site owner.
    The second stage downstream of the supply-entry SPD, at the inverter or boiler.

    Practical application

    If measurements are frequently taken in a sub-distribution board serving a heat pump and inverter, install this T2 SPD with a switch: switch it off before testing and back on afterwards – the wires stay in place. The supply entry must have T1+T2.

    Pros

    • Integrated switch for maintenance
    • 1P–4P and 400 / 600 V versions
    • DIN mounting
    • Simple second protection stage

    Cons / limitations

    • The supplier does not state Iimp – not suitable for a supply entry with a lightning protection system or overhead line
    • The supplier does not specify Uc and Up – confirm before ordering
    • The switch does not replace the backup fuse

    ⚡ Safety and installation notes

    • Install only with the supply disconnected.
    • After insulation testing, switch the SPD switch back on – a switched-off SPD does not protect.
    • PE straight to the earthing bar, in a T2 circuit at least 6 mm² Cu.
    • If the fuse upstream of the SPD is larger than the manufacturer allows, provide a separate fuse.
    • Work must be carried out by a qualified electrician.
    ☝ From experience
    • The switch isolates the SPD but does not replace a backup fuse – if the incoming fuse is larger than the manufacturer allows, the SPD needs its own fuse or MCB.
    • After an insulation test remember to switch it back on – a switched-off SPD protects nothing, and this is the most common mistake we find when upgrading boards.
    • Keep the leads to the SPD and from it to PE as short as possible (total up to 0.5 m), PE straight to the earthing bar, at least 6 mm² Cu in a Type 2 circuit.
    • When protecting an inverter or heat pump, install the SPD in the same board the device is connected to – 10 m or more of cable already reduces the effect.
    ☝ Elsprendimai.eu recommends: Install a T1+T2 SPD at the supply entry, and for backup protection – fuses and fuse holders. You will find other T2 and T3 SPDs in this subgroup.

    Quick selection guide

    Type 2 / Class II / C
    20 kA
    400 V AC
    4P

    Suitable when you need:

    • Second-stage protection in a sub-distribution board
    • Convenient disconnection for insulation testing
    • Protection at the inverter, boiler or automation

    Check before use:

    • The actual Uc and Up values with the supplier
    • Whether the supply entry already has T1+T2
    • The number of poles for the network (1P–4P)

    Important reminder: A T2 SPD does not replace T1+T2 at the supply entry when the building has a lightning protection system or is supplied by an overhead line.

    FAQ

    Why is this SPD classed as Type 2?
    Type 1 requires a declared impulse current Iimp (10/350 µs). The supplier gives only a 20 kA (8/20 µs) rating, so we assign it to Type 2 use. For an incomer with an LPS choose a Type 1+2.
    Is it suitable for a PV plant?
    Yes, on the AC side – after the inverter or in the board where the inverter is connected. The DC side needs a dedicated DC SPD.
    What is the integrated switch for?
    To disconnect the SPD during maintenance or insulation testing without unscrewing wires.
    Does the switch replace the fuse?
    No, it only disconnects the SPD; backup protection is selected according to the supplier's instructions.
    Which version to choose – 400 V or 600 V?
    According to the actual Uc and the network; ask for the Uc and Up values before ordering – we will provide them.
    Can it be connected downstream of an RCD?
    Upstream of the RCD or downstream of an S-type RCD is recommended, so that the discharge current does not flow through the RCD.
    If the building has an LPS or is fed by an overhead line, the incomer needs a Type 1+2 SPD – see the Type 1+2 selection guide. Other Type 2 and Type 3 SPDs are in this subgroup; for selection contact us.

    Documents and sources

    Technical data provided by the supplier (the manufacturer's datasheet is not publicly available).

    Checked 2026-10-17.

    Surge protective device with integrated switch | Type 2 | 4P | 400 V AC | 20 kA (8/20) | DIN | ES-LY3027

    ES-LY3027 – T2 surge protective device with integrated switch, 4P, 400 V AC: discharge current 20 kA (8/20 µs). Second protection stage for sub-distribution boards and equipment.

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • Alternative products

  • Subscribtion to new arrivals

    privacy policy

    Information