Modular contactor | 2P | 2NO | 16A | 230VAC | DIN | MCF3 | Promfactor Baltic | MCF31620230 | 4779040154658
Code: MCF31620230Price 8.54 € VAT incl.( 7.06 € VAT excl. )MCF3 16-20 – 2NO (two normally open contacts) modular contactor for DIN rail with a ~230 V AC coil. Rated current 16 A (AC-7a), for motors 6 A (AC-7b), width 1 mod. (18 mm). Designed to remotely switch single-phase loads – a water heater, electric heating, a lighting group or ventilation.
-
Modular contactor | 2P | 2NO | 16A | 230VAC | DIN | MCF3 | Promfactor Baltic | MCF31620230 | 4779040154658
MCF3 16-20 (MCF31620230) – 2NO (two normally open contacts) modular contactor for DIN rail. Designed for remote on/off switching of single-phase loads – a water heater, electric heating, a lighting group or ventilation. Coil ~230 V AC, rated current 16 A (AC-7a), for motors – 6 A (AC-7b).
Key point:
When a load has to be switched by time, temperature or a signal, a thermostat or time relay cannot carry it directly. The 2NO contactor takes over the power circuit: it disconnects both phase and neutral, leaving the control device to switch only the coil current.Current AC-7a (heating, lighting)
16 ACurrent AC-7b (motors)
6 ACoil voltage
~230 V ACWidth in the board
1 mod. (18 mm)Operating principle
The contactor is mounted on the DIN rail in the distribution board, next to the circuit breaker (MCB) protecting the load. The power circuit is connected to the contact terminals and the control device to coil terminals A1–A2.
When ~230 V AC is applied to the coil, the electromagnet pulls in the armature: NO contacts close and NC contacts open. When the control voltage is removed, a spring returns the contacts to their initial position. The mechanism operates quietly, so it is also suitable for residential premises.
This way the control device (time relay, thermostat, photo relay, controller) switches only the small coil current, while the contactor carries the load current.
Why choose the MCF3 16-20?
One module handles all switching of a single-phase load: the control device runs without load current, and the water heater or heating is disconnected on both poles.Technical specifications
Product type Modular contactor (DIN rail mounting) Manufacturer Promfactor Baltic Series / model MCF3 16-20 Code MCF31620230 EAN 4779040154658 Contacts 2NO Number of poles 2 Rated current AC-7a / AC-1 16 A Rated current AC-7b (household motors) 6 A Power AC-7a, 230 V 3 kW Rated operational voltage (Ue) ~230/400 V Coil (control) voltage (Uc) ~230 V AC Insulation voltage (Ui) 500 V Impulse withstand voltage (Uimp) 4 kV Frequency 50/60 Hz Utilisation categories AC-1, AC-3, AC-7a, AC-7b Width 1 mod. (18 mm) Terminal wire cross-section 1–4 mm² Terminal tightening torque 0.8 Nm Endurance electrical 100,000 cycles / mechanical 1,000,000 cycles Operating time 0.05 s Degree of protection IP20 Operating temperature -25…+55 °C Storage temperature -25…+70 °C Altitude up to 2000 m Mounting DIN rail TH35 (35 × 7.5 mm) Comb busbar connection not provided Auxiliary contacts can be added (MF/AX11 1NO+1NC) Standards IEC/EN 61095, IEC/EN 60947-4-1 Key functions
- Remote load control – the load is switched by a time relay, thermostat, photo relay or controller via coil A1–A2.
- Protects the control device from load current – the timer or thermostat contact switches only the coil current.
- Compact installation – on the DIN rail in the distribution board, 1 mod. (18 mm).
- Quiet operation – suitable for residential premises and offices.
- Auxiliary contact – an MF/AX11 (1NO+1NC) can be fitted to the MCF3 for a status signal or interlock.
Where is it used?
- Water heater operation on the night tariff (via a time relay)
- Electric underfloor heating and convectors (via a thermostat)
- Outdoor and yard lighting groups (via a photo relay / twilight switch or timer)
- Switching ventilation and heat recovery units
- Lighting zones in commercial premises
- Smart home controllers whose relay output is too weak for the load
Use by customer need
For homeowners.
The water heater heats during cheaper tariff hours, and the timer and thermostat last longer because they do not switch the load directly.For electricians.
One module in the board, clearly marked terminals A1–A2 and 1–2 / 3–4 – fast, neat installation.For smart system integrators.
Turns the weak output of a controller or Wi-Fi module into reliable 16 A load switching.Practical application
If the water heater should heat only on the night tariff, a time relay energises the contactor coil A1–A2 during the set hours, and the contactor switches the heater's phase and neutral via contacts 1–2 and 3–4. During the day both poles are open, so the water heater is completely de-energised.Pros
- The control device does not switch the load current – longer service life
- Mounted on the DIN rail alongside circuit breakers
- Quiet operation
- AC-7a and AC-7b currents clearly stated
- MF/AX11 auxiliary contact can be added
Cons / limitations
- Does not protect against overload or short circuit – a circuit breaker is mandatory
- IP20 – dry distribution boards only
- Not connectable with a comb busbar
- AC-7b current (6 A) is considerably lower than AC-7a – for larger motors choose a standard AC-3 contactor with a thermal overload relay
Safety and installation notes
- A circuit breaker upstream of the contactor is mandatory, selected for the cable and the load. The contactor does not protect the circuit.
- For motors, check the AC-7b current, not the AC-7a current given in the name; additionally protect the motor with a motor protection circuit breaker or thermal overload relay.
- The coil voltage (~230 V AC) must match the control voltage – a different voltage will burn out the coil or the contactor will not switch on.
- Terminal wire cross-section – 1–4 mm², tightening torque – 0.8 Nm.
- When several contactors next to each other operate continuously (e.g. heating all night), leave a gap or fit a spacer – this reduces heating.
- Installation and connection to the 230/400 V network must be carried out only by a qualified electrician with the power disconnected.
Quick selection guide
16 A AC-7a6 A AC-7b2NO~230 V AC1 mod. (18 mm)Suitable when you need to:- switch a single-phase load by time, temperature or signal
- disconnect both phase and neutral
- protect a thermostat or controller contact from load current
Check before use:- the load type: for heating – AC-7a current, for motors – AC-7b current
- the coil voltage and the control device output
- space in the board and gaps between continuously operating contactors
- the circuit breaker upstream of the contactor
Important reminder: A contactor only switches the load on and off – it does not replace a circuit breaker, motor protection or a residual current device.FAQ
Does the contactor protect against overload and short circuit?
No – the circuit is protected by the circuit breaker installed upstream of the contactor.Can it control a pump or fan?
Yes, if the motor operating current does not exceed 6 A (AC-7b); for larger motors choose a standard AC-3 contactor.Why choose 2NO rather than 1NO?
2NO disconnects both phase and neutral, so the switched-off load is left completely de-energised.How much space does it take in the board?
1 mod. (18 mm).What can control it?
A time relay, thermostat, photo relay, smart module or controller whose output suits a ~230 V AC coil.Can an auxiliary contact be added?
Yes, the MF/AX11 (1NO+1NC) auxiliary contact fits the MCF3 series.Modular contactor | 2P | 2NO | 16A | 230VAC | DIN | MCF3 | Promfactor Baltic | MCF31620230 | 4779040154658
MCF3 16-20 (MCF31620230) – 2NO (two normally open contacts) modular contactor for DIN rail: 16 A (AC-7a), 6 A for motors (AC-7b), coil ~230 V AC. Intended for remote control of single-phase loads – a water heater, electric heating, a lighting group or ventilation in a distribution board.
Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.ManufacturerThis product is marked with the CE label, which confirms that it complies with all applicable European Union directives and regulations. CE marking is not just a formality – it is an important indicator of quality and safety, ensuring that the product has been properly assessed, tested, and can be safely used throughout the EU market.
CE certification means that the product has been evaluated according to the main criteria:
Safety requirements – ensures that the product does not pose a risk to the user or the environment
Electromagnetic compatibility (EMC) – the device does not interfere with other equipment and is resistant to external disturbances
Environmental standards – complies with current ecological and material usage requirements
Operational reliability – the product is suitable for long-term use according to its intended purposeCE marking allows this product to:
be legally supplied and used in all European Union countries
ensure a high level of quality and safety
be used in residential, commercial, and industrial environmentsThe CE mark is a declaration of the manufacturer’s responsibility, confirming that the product complies with all applicable standards and has been assessed according to EU legislation.
What does this mean for you as a buyer?
Safe use in everyday activities
Reliable performance and reduced risk of failure
Compliance with EU standards and requirements
Suitability for professional solutions
Love it? Share your thoughts in a review!Write Review Alternative products
Industrial modular socket panel | 2×CEE 16 A 5P 400 V + 1×CEE 32 A 5P 400 V + 2×Schuko 230 V | space for 11 modules of protection | IP44 | SEZ ROS11/x-14Code: ROS11/x-14 2x230V+2x16A+1x32ASEZ ROS11/x-14 – a sealed industrial panel with sockets (2×CEE 16 A 5P 400 V + 1×CEE 32 A 5P 400 V + 2×Schuko 230 V) and space for 11 modules of protective devices. Degree of protection: IP44, mounting – wall-mounted (surface).
Price 62.90 € VAT incl.( 51.99 € VAT excl. )Modular photo relay | twilight switch with external sensor | 16 A | 12–240 V AC/DC | 1–50,000 lx | 1CO | DIN | GanzKK | SOU-1/UNICode: SOU-1/UNIDIN rail twilight switch with universal 12–240 V AC/DC supply and external sensor: 1–50,000 lx, 1CO 16 A AC1, 0–2 min delay, 1 module.
Price 42.47 € VAT incl.( 35.10 € VAT excl. )Marker cable ties | 2.5x110 mm | white | nylon PA66 | 100 pcs | 4772124000407Code: 4772124000407Marker cable ties (code 4772124000407) – white PA66 nylon cable ties, 2.5x110 mm, with an integrated marking plate, in a pack of 100 pcs. Designed to bundle wires, cables and tubing while labelling them at the same time: the circuit number, port name or other information is written on the plate, so one tie handles both fastening and identification.
Price 2.42 € VAT incl.( 2.00 € VAT excl. )LED signal lamp | 22 mm | 230 V AC/DC | red | IP54 | compact | Promfactor Baltic | FPL230RDCode: FPL230RDCompact one-piece LED signal lamp for a Ø 22 mm hole, 230 V AC/DC. Connected with two terminals and takes little space behind the door.
Price 1.49 € VAT incl.( 1.23 € VAT excl. )Terminal | connector paste for contacts | reduces oxidation | 35.3g | WAGO | ALU PLUS | 249-130 | for connecting aluminium and copper wiresCode: 4017332133890Contact paste designed to protect aluminum conductors from oxidation and ensure a reliable electrical connection. This special paste allows aluminum and copper conductors to be safely and efficiently connected within the same connector, making it particularly useful when renovating older electrical installations where aluminum wiring is commonly found.
Aluminum naturally oxidizes, and the resulting oxide layer increases contact resistance, causes connection heating, and may become a source of electrical faults. By using WAGO ALU-PLUS, the oxidation layer is reduced, electrical conductivity is improved, and the service life of the connection is significantly extended.
Price 2.83 € VAT incl.( 2.34 € VAT excl. )