Products catalog

  • Modular contactor | 2P | 2NO | 25A | 230VAC | DIN | manual control | MCF3i | Promfactor Baltic | MCF3i2520230 | 4772151002375

    Code: MCF3i2520230
    Barcode: 4772151002375

    MCF3i 25-20 – 2NO (two normally open contacts) modular contactor with manual override and a ~230 V AC coil. Rated current 25 A (AC-7a). Remotely switches single-phase loads – a water heater, electric heating, a lighting group or ventilation, and the load can also be switched on or off by hand when needed.

  • Modular contactor | 2P | 2NO | 25A | 230VAC | DIN | manual control | MCF3i | Promfactor Baltic | MCF3i2520230 | 4772151002375

    MCF3i 25-20 (MCF3i2520230) – 2NO (two normally open contacts) modular contactor with manual override. Designed for remote on/off switching of single-phase loads – a water heater, electric heating, a lighting group or ventilation; if needed, the load can also be switched on or off by hand on the housing. Coil ~230 V AC, rated current 25 A (AC-7a).

    Key point:
    When a load has to be switched by time, temperature or a signal, a thermostat or time relay cannot carry it directly. The 2NO contactor takes over the power circuit: it disconnects both phase and neutral, leaving the control device to switch only the coil current.
    Current AC-7a (heating, lighting)
    25 A
    Control
    remote and manual
    Coil voltage
    ~230 V AC
    Contacts
    2NO

    Operating principle

    The contactor is mounted on the DIN rail in the distribution board, next to the circuit breaker (MCB) protecting the load. The power circuit is connected to the contact terminals and the control device to coil terminals A1–A2.

    Normally the contactor operates from the control signal: voltage on the coil closes the contacts, and its loss opens them. With the manual override switch on the housing, the contactor can also be switched on or off without control voltage.

    This is convenient during commissioning and adjustment, and when a timer, thermostat or controller fails – heating or ventilation can keep running until the control device is replaced.

    Why choose the MCF3i 25-20?
    One module handles all switching of a single-phase load: the control device runs without load current, and the water heater or heating is disconnected on both poles.

    Technical specifications

    Product type Modular contactor (DIN rail mounting)
    Manufacturer Promfactor Baltic
    Series / model MCF3i 25-20
    Code MCF3i2520230
    EAN 4772151002375
    Contacts 2NO
    Number of poles 2
    Rated current AC-7a / AC-1 25 A
    Rated operational voltage (Ue) ~230/400 V
    Coil (control) voltage (Uc) ~230 V AC
    Insulation voltage (Ui) 500 V
    Impulse withstand voltage (Uimp) 4 kV
    Frequency 50/60 Hz
    Utilisation categories AC-1, AC-3, AC-7a, AC-7b
    Terminal wire cross-section 1–4 mm²
    Terminal tightening torque 0.8 Nm
    Endurance electrical 100,000 cycles / mechanical 1,000,000 cycles
    Operating time 0.05 s
    Degree of protection IP20
    Operating temperature -25…+55 °C
    Storage temperature -25…+70 °C
    Altitude up to 2000 m
    Mounting DIN rail TH35 (35 × 7.5 mm)
    Comb busbar connection not provided
    Manual override yes – switch on the housing
    Standards IEC/EN 61095, IEC/EN 60947-4-1

    Key functions

    • Remote load control – the load is switched by a time relay, thermostat, photo relay or controller via coil A1–A2.
    • Protects the control device from load current – the timer or thermostat contact switches only the coil current.
    • Compact installation – on the DIN rail in the distribution board.
    • Quiet operation – suitable for residential premises and offices.
    • Manual override – the load can be switched on or off without a control signal, e.g. during commissioning or if the controller fails.

    Where is it used?

    • Water heater operation on the night tariff (via a time relay)
    • Electric underfloor heating and convectors (via a thermostat)
    • Outdoor and yard lighting groups (via a photo relay / twilight switch or timer)
    • Switching ventilation and heat recovery units
    • Lighting zones in commercial premises
    • Smart home controllers whose relay output is too weak for the load

    Use by customer need

    For homeowners.
    The water heater heats during cheaper tariff hours, and the timer and thermostat last longer because they do not switch the load directly.
    For electricians.
    One module in the board, clearly marked terminals A1–A2 and 1–2 / 3–4 – fast, neat installation.
    For smart system integrators.
    Turns the weak output of a controller or Wi-Fi module into reliable 25 A load switching.

    Practical application

    If the water heater should heat only on the night tariff, a time relay energises the contactor coil A1–A2 during the set hours, and the contactor switches the heater's phase and neutral via contacts 1–2 and 3–4. During the day both poles are open, so the water heater is completely de-energised.

    Pros

    • The control device does not switch the load current – longer service life
    • Mounted on the DIN rail alongside circuit breakers
    • Quiet operation
    • Manual override – the system can keep running even if the control device fails

    Cons / limitations

    • Does not protect against overload or short circuit – a circuit breaker is mandatory
    • IP20 – dry distribution boards only
    • Not connectable with a comb busbar
    • The manufacturer does not specify a separate AC-7b current – for motors choose a contactor with a stated AC-7b current or a standard AC-3 contactor

    Safety and installation notes

    • A circuit breaker upstream of the contactor is mandatory, selected for the cable and the load. The contactor does not protect the circuit.
    • For motors, check the AC-7b current, not the AC-7a current given in the name; additionally protect the motor with a motor protection circuit breaker or thermal overload relay.
    • The coil voltage (~230 V AC) must match the control voltage – a different voltage will burn out the coil or the contactor will not switch on.
    • Terminal wire cross-section – 1–4 mm², tightening torque – 0.8 Nm.
    • When several contactors next to each other operate continuously (e.g. heating all night), leave a gap or fit a spacer – this reduces heating.
    • Installation and connection to the 230/400 V network must be carried out only by a qualified electrician with the power disconnected.

    Quick selection guide

    25 A AC-7a
    2NO
    ~230 V AC
    Suitable when you need to:
    • switch a single-phase load by time, temperature or signal
    • disconnect both phase and neutral
    • protect a thermostat or controller contact from load current
    Check before use:
    • the load type: for heating – AC-7a current, for motors – AC-7b current
    • the coil voltage and the control device output
    • space in the board and gaps between continuously operating contactors
    • the circuit breaker upstream of the contactor
    Important reminder: A contactor only switches the load on and off – it does not replace a circuit breaker, motor protection or a residual current device.

    FAQ

    Does the contactor protect against overload and short circuit?
    No – the circuit is protected by the circuit breaker installed upstream of the contactor.
    Can it control a pump or fan?
    The manufacturer does not specify a separate AC-7b current, so for motors choose a contactor with a stated AC-7b current.
    Why choose 2NO rather than 1NO?
    2NO disconnects both phase and neutral, so the switched-off load is left completely de-energised.
    What can control it?
    A time relay, thermostat, photo relay, smart module or controller whose output suits a ~230 V AC coil.
    When is a contactor with manual override worth choosing?
    When heating, ventilation or a pump must keep running even if the timer, thermostat or controller fails.

    Modular contactor | 2P | 2NO | 25A | 230VAC | DIN | manual control | MCF3i | Promfactor Baltic | MCF3i2520230 | 4772151002375

    MCF3i 25-20 (MCF3i2520230) – 2NO (two normally open contacts) modular contactor for DIN rail: 25 A (AC-7a), coil ~230 V AC. Intended for remote control of single-phase loads – a water heater, electric heating, a lighting group or ventilation in a distribution board.

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • Alternative products

    Marker cable ties | 2.5x110 mm | white | nylon PA66 | 100 pcs | 4772124000407
    Code: 4772124000407

    Marker cable ties (code 4772124000407) – white PA66 nylon cable ties, 2.5x110 mm, with an integrated marking plate, in a pack of 100 pcs. Designed to bundle wires, cables and tubing while labelling them at the same time: the circuit number, port name or other information is written on the plate, so one tie handles both fastening and identification.

    Price 2.42 € VAT incl.
    ( 2.00 € VAT excl. )
    Modular photo relay | twilight switch with external sensor | 16 A | 12–240 V AC/DC | 1–50,000 lx | 1CO | DIN | GanzKK | SOU-1/UNI
    Code: SOU-1/UNI

    DIN rail twilight switch with universal 12–240 V AC/DC supply and external sensor: 1–50,000 lx, 1CO 16 A AC1, 0–2 min delay, 1 module.

    Price 42.47 € VAT incl.
    ( 35.10 € VAT excl. )
    Industrial modular socket panel | 2×CEE 16 A 5P 400 V + 1×CEE 32 A 5P 400 V + 2×Schuko 230 V | space for 11 modules of protection | IP44 | SEZ ROS11/x-14
    Code: ROS11/x-14 2x230V+2x16A+1x32A

    SEZ ROS11/x-14 – a sealed industrial panel with sockets (2×CEE 16 A 5P 400 V + 1×CEE 32 A 5P 400 V + 2×Schuko 230 V) and space for 11 modules of protective devices. Degree of protection: IP44, mounting – wall-mounted (surface).

    Price 62.90 € VAT incl.
    ( 51.99 € VAT excl. )
    LED signal lamp | 22 mm | 230 V AC/DC | red | IP54 | compact | Promfactor Baltic | FPL230RD
    Code: FPL230RD

    Compact one-piece LED signal lamp for a Ø 22 mm hole, 230 V AC/DC. Connected with two terminals and takes little space behind the door.

    Price 1.49 € VAT incl.
    ( 1.23 € VAT excl. )
    Terminal | connector paste for contacts | reduces oxidation | 35.3g | WAGO | ALU PLUS | 249-130 | for connecting aluminium and copper wires
    Code: 4017332133890

    Contact paste designed to protect aluminum conductors from oxidation and ensure a reliable electrical connection. This special paste allows aluminum and copper conductors to be safely and efficiently connected within the same connector, making it particularly useful when renovating older electrical installations where aluminum wiring is commonly found.

    Aluminum naturally oxidizes, and the resulting oxide layer increases contact resistance, causes connection heating, and may become a source of electrical faults. By using WAGO ALU-PLUS, the oxidation layer is reduced, electrical conductivity is improved, and the service life of the connection is significantly extended. 

    Price 2.83 € VAT incl.