  • Modular contactor | 4P | 4NO | 63A | 230VAC | DIN | ES-TXCH8-63/40

    Code: ES-TXCH8-63/40

    ES-TXCH8-63/40 – 4NO (four normally open contacts) modular contactor for DIN rail with a 220–240 V AC coil. Rated current 63 A (AC-7a), for motors 25 A (AC-7b), width 3 mod. (54 mm). Designed for three-phase loads and larger household motors.

  • Modular contactor | 4P | 4NO | 63A | 230VAC | DIN | ES-TXCH8-63/40

    ES-TXCH8-63/40 – 4NO (four normally open contacts) modular contactor for DIN rail, for larger three-phase loads. Rated current 63 A (AC-7a), for motors – 25 A (AC-7b), coil 220–240 V AC.

    Key point:
    A three-phase load must be disconnected on all phases, otherwise the switched-off appliance remains live. The 4NO contactor switches L1, L2, L3 and N on and off with a single signal.
    Current AC-7a (heating, lighting)
    63 A
    Current AC-7b (motors)
    25 A
    Coil voltage
    220–240 V AC
    Width in the board
    3 mod. (54 mm)

    Operating principle

    The contactor is mounted on the DIN rail in the distribution board, next to the circuit breaker (MCB) protecting the load, and occupies 3 mod. (54 mm). The power circuit is connected to the contact terminals and the control device to coil terminals A1–A2.

    When voltage is applied to the coil, all four contacts close; when the control voltage is removed, they open. This way a three-phase load is switched on and off on all phases and neutral.

    Among modular contactors, this model stands out with a higher AC-7b current (25 A), so it also suits larger household motors.

    Why choose the ES-TXCH8-63/40?
    A three-phase heater or heating element group is switched on and off on all phases and neutral with one device.

    Technical specifications

    Product type Modular contactor (DIN rail mounting)
    Series / model –
    Code ES-TXCH8-63/40
    Contacts 4NO
    Number of poles 4
    Rated current AC-7a / AC-1 63 A
    Rated current AC-7b (household motors) 25 A
    Rated operational voltage (Ue) 400 V
    Coil (control) voltage (Uc) 220–240 V AC
    Insulation voltage (Ui) 500 V
    Frequency 50/60 Hz
    Utilisation categories AC-7a, AC-7b
    Width 3 mod. (54 mm)
    Dimensions 85 × 68 × 54 mm
    Mounting DIN rail TH35 (35 × 7.5 mm)
    Standards IEC 61095, EN 61095

    Key functions

    • Remote load control – the load is switched by a time relay, thermostat, photo relay or controller via coil A1–A2.
    • Protects the control device from load current – the timer or thermostat contact switches only the coil current.
    • Compact installation – on the DIN rail in the distribution board, 3 mod. (54 mm).
    • Quiet operation – suitable for residential premises and offices.
    • Higher AC-7b current – 25 A for motors, when the MCF3 series limit (15 A) is not enough.

    Where is it used?

    • Three-phase heaters and electric boilers (stage control)
    • Heating element groups
    • Three-phase lighting groups (floodlights, street lighting)
    • Dryers and sauna heaters with separate control
    • Disconnecting several single-phase groups with one signal
    • Disconnecting a supply or group on an emergency signal (according to the load category)

    Use by customer need

    For boiler room and heating installers.
    One stage – one contactor: the thermostat or controller switches only the coil.
    For electricians.
    All three phases and neutral are disconnected together – a switched-off heater is fully de-energised.
    For building managers.
    Several lighting or heating groups are disconnected with one signal from a timer or controller.

    Practical application

    If an electric boiler has two stages, a separate 4NO contactor is installed for each stage. The boiler controller switches on the first stage and, at high demand, the second. Each stage is switched on all phases.

    Pros

    • The control device does not switch the load current – longer service life
    • Mounted on the DIN rail alongside circuit breakers
    • Quiet operation
    • AC-7a and AC-7b currents clearly stated
    • AC-7b 25 A – more than typical for modular contactors

    Cons / limitations

    • Does not protect against overload or short circuit – a circuit breaker is mandatory
    • IP20 – dry distribution boards only
    • Occupies 3 mod. (54 mm) – plan space in the board

    Safety and installation notes

    • A circuit breaker upstream of the contactor is mandatory, selected for the cable and the load. The contactor does not protect the circuit.
    • For motors, check the AC-7b current, not the AC-7a current given in the name; additionally protect the motor with a motor protection circuit breaker or thermal overload relay.
    • The coil voltage (220–240 V AC) must match the control voltage – a different voltage will burn out the coil or the contactor will not switch on.
    • When several contactors next to each other operate continuously (e.g. heating all night), leave a gap or fit a spacer – this reduces heating.
    • Installation and connection to the 230/400 V network must be carried out only by a qualified electrician with the power disconnected.

    Quick selection guide

    63 A AC-7a
    25 A AC-7b
    4NO
    220–240 V AC
    3 mod. (54 mm)
    Suitable when you need to:
    • switch a three-phase load on and off on all phases
    • control heating stages
    • disconnect several groups with one signal
    Check before use:
    • the load type: for heating – AC-7a current, for motors – AC-7b current
    • the coil voltage and the control device output
    • space in the board and gaps between continuously operating contactors
    • the circuit breaker upstream of the contactor
    Important reminder: A contactor only switches the load on and off – it does not replace a circuit breaker, motor protection or a residual current device.

    FAQ

    Does the contactor protect against overload and short circuit?
    No – the circuit is protected by the circuit breaker installed upstream of the contactor.
    Can it control a pump or fan?
    Yes, if the motor operating current does not exceed 25 A (AC-7b); for larger motors choose a standard AC-3 contactor.
    How much space does it take in the board?
    3 mod. (54 mm).
    What can control it?
    A time relay, thermostat, photo relay, smart module or controller whose output suits a 220–240 V AC coil.
    How does it differ from the MCF3 63 A?
    The AC-7a current is the same (63 A), but the AC-7b current is higher – 25 A instead of 15 A.

    Modular contactor | 4P | 4NO | 63A | 230VAC | DIN | ES-TXCH8-63/40

    ES-TXCH8-63/40 – 4NO (four normally open contacts) modular contactor for DIN rail: 63 A (AC-7a), 25 A for motors (AC-7b), coil 220–240 V AC. Intended for remote control of three-phase loads – heaters, boiler heating elements or lighting groups on all phases in a distribution board.

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • Alternative products

    LED signal lamp | 22 mm | 230 V AC/DC | red | IP54 | compact | Promfactor Baltic | FPL230RD
    Code: FPL230RD

    Compact one-piece LED signal lamp for a Ø 22 mm hole, 230 V AC/DC. Connected with two terminals and takes little space behind the door.

    Price 1.49 € VAT incl.
    ( 1.23 € VAT excl. )
    Modular photo relay | twilight switch with external sensor | 16 A | 12–240 V AC/DC | 1–50 000 lx | 1CO | DIN | GanzKK | SOU-1/UNI
    Code: SOU-1/UNI

    DIN rail twilight switch with universal 12–240 V AC/DC supply and external sensor: 1–50,000 lx, 1CO 16 A AC1, 0–2 min delay, 1 module.

    Price 42.47 € VAT incl.
    ( 35.10 € VAT excl. )
    Terminal | connector paste for contacts | reduces oxidation | 35.3g | WAGO | ALU PLUS | 249-130 | for connecting aluminium and copper wires
    Code: 4017332133890

    Contact paste designed to protect aluminum conductors from oxidation and ensure a reliable electrical connection. This special paste allows aluminum and copper conductors to be safely and efficiently connected within the same connector, making it particularly useful when renovating older electrical installations where aluminum wiring is commonly found.

    Aluminum naturally oxidizes, and the resulting oxide layer increases contact resistance, causes connection heating, and may become a source of electrical faults. By using WAGO ALU-PLUS, the oxidation layer is reduced, electrical conductivity is improved, and the service life of the connection is significantly extended. 

    Price 2.83 € VAT incl.
    ( 2.34 € VAT excl. )
    Industrial modular socket panel | 2×CEE 16 A 5P 400 V + 1×CEE 32 A 5P 400 V + 2×Schuko 230 V | space for 11 modules of protection | IP44 | SEZ ROS11/x-14
    Code: ROS11/x-14 2x230V+2x16A+1x32A

    SEZ ROS11/x-14 – a sealed industrial panel with sockets (2×CEE 16 A 5P 400 V + 1×CEE 32 A 5P 400 V + 2×Schuko 230 V) and space for 11 modules of protective devices. Degree of protection: IP44, mounting – wall-mounted (surface).

    Price 62.90 € VAT incl.
    ( 51.99 € VAT excl. )
    Cable ties with marker tag | 2,5x110mm | white | 100 pcs | 4772124000407
    Code: 4772124000407

    Marker cable ties (code 4772124000407) – white PA66 nylon cable ties, 2.5x110 mm, with an integrated marking plate, in a pack of 100 pcs. Designed to bundle wires, cables and tubing while labelling them at the same time: the circuit number, port name or other information is written on the plate, so one tie handles both fastening and identification.

    Price 2.42 € VAT incl.
    ( 2.00 € VAT excl. )
  • privacy policy

    Information