  • Power factor correction capacitor | three-phase | 30 kvar @ 440 V | ≈24.8 kvar @ 400 V | 493.2 μF | Ø116×300 mm | 50 Hz

    Code: ES-HYSMK0.44-30-3

    Three-phase cylindrical capacitor for reactive power compensation in low-voltage networks. It is used as a fixed compensation step or as part of an automatic PFC panel at sites running motors, pumps, compressors and fans. The rated voltage is 440 V, so in a standard 3×400 V network the capacitor operates with a voltage margin.

  • Power factor correction capacitor | three-phase | 30 kvar @ 440 V | ≈24.8 kvar @ 400 V | 493.2 μF | Ø116×300 mm | 50 Hz

    Three-phase cylindrical capacitor for reactive power compensation in low-voltage networks. It is used as a fixed compensation step or as part of an automatic PFC panel at sites running motors, pumps, compressors and fans. The rated voltage is 440 V, so in a standard 3×400 V network the capacitor operates with a voltage margin.

    Key point:
    30 kvar is the output at 440 V. In a 3×400 V network this capacitor delivers approximately 24.8 kvar, so compensation steps must be sized for the actual network voltage. The voltage margin reduces dielectric stress when the supply voltage fluctuates and extends the capacitor's service life.
    Rated output
    30 kvar @ 440 V
    Output at 400 V
    ≈24.8 kvar
    Rated current
    39.4 A (≈35.8 A @ 400 V)
    Dimensions
    Ø116×300 mm, M16 mounting stud

    Operating principle

    Induction motors, transformers and reactors draw reactive power to build up their magnetic fields. This current flows through cables and the transformer, heating them and taking up capacity without doing any useful work.

    A capacitor connected to the same three phases supplies the reactive current locally, so less of it has to be drawn from the grid. After the capacitor is disconnected, the discharge device reduces the terminal voltage to ≤ 75 V within 3 min.

    After compensation, line current drops, the power factor cosφ rises, and losses in cables and the transformer decrease. Business customers may also see lower reactive energy charges.

    Why choose this capacitor?
    In a 400 V network, the 440 V rating provides a margin of about 10 %. This pays off when the voltage rises due to low night-time load or harmonics. The Ø116×300 mm housing and M16 mounting make it a suitable replacement for older capacitors, provided the dimensions and mounting match.

    Technical specifications

    Product type Three-phase power factor correction capacitor
    Code ES-HYSMK0.44-30-3
    Rated reactive power 30 kvar at 440 V, 50 Hz
    Output in a 3×400 V network ≈24.8 kvar (Q = 30 × (400/440)²)
    Rated voltage 440 V AC
    Number of phases 3 phases
    Frequency 50 Hz
    Capacitance 493.2 μF (per supplier specification)
    Capacitance tolerance −5 … +10 %
    Rated current 39.4 A at 440 V (≈35.8 A at 400 V)
    Permissible overcurrent 1.3 In
    Permissible overvoltage 1.1 Un – up to 8 h per 24 h
    Dissipation factor ≤ 0.001 (20 °C)
    Test voltage terminal–terminal 2.15 Un AC, 10 s
    Test voltage terminals–case 3.5 kV AC, 10 s
    Discharge ≤ 75 V within 3 min after disconnection
    Ambient operating temperature −25 … +50 °C
    Housing Cylindrical, metal
    Dimensions Ø116 × 300 mm
    Mounting M16 × 25 stud
    Installation location PFC panels, distribution and control panels

    Main functions

    • Reactive power compensation – reactive current is supplied locally, so less is drawn from the grid.
    • Higher cosφ – for the same active load, apparent power and current are reduced.
    • Lower load on cables and transformer – less heating, lower transmission losses and spare capacity for new equipment.
    • 440 V voltage margin – longer capacitor service life in a 400 V network with voltage fluctuations.
    • Discharge after disconnection – voltage drops to ≤ 75 V within 3 min. This is required before reconnection and maintenance.
    • Suitable for stepped compensation – used as a step in automatic panels with a power factor controller.

    Where is it used?

    • Automatic PFC panels in manufacturing plants
    • Compressor rooms and refrigeration plant
    • Pumping stations, water supply and wastewater facilities
    • Grain dryers, conveyors and agricultural machinery
    • Air handling units and HVAC distribution panels
    • Woodworking and metalworking shops
    • Replacing old, bulging or degraded capacitors in existing panels

    Use by need

    For PFC panel builders.
    A compensation step that can be combined with a power factor controller and capacitor-duty contactors.
    For facility energy managers.
    When reactive energy charges appear on the bill, a failed step can be replaced quickly without rebuilding the whole panel.
    For farm owners.
    Lower current at the incoming supply and in the cables when the dryer, fans and conveyors run simultaneously during the season.

    Practical application

    Suppose a power quality analyser shows a load of 120 kW at cosφ 0.80, and the target is 0.95. This requires about 50 kvar of compensation (120 × (0.75 − 0.33)). In a 400 V network, two of these capacitors will deliver about 50 kvar, not 60 kvar. Therefore, size the steps for the actual voltage and switch them via an automatic controller to avoid overcompensation at low load.

    Pros

    • 440 V rated voltage – margin in a 400 V network
    • Permissible overcurrent 1.3 In and overvoltage 1.1 Un
    • Low dielectric losses (tgδ ≤ 0.001)
    • Discharge to ≤ 75 V within 3 min
    • Ø116×300 mm housing and M16 mounting
    • Suitable for automatic cosφ steps

    Cons / limitations

    • In a 400 V network the output is ≈24.8 kvar, not 30 kvar
    • Networks with variable frequency drives and other harmonic sources require detuned reactors
    • Capacitor-duty contactors (AC-6b) are required for switched steps
    • Fixed output, so overcompensation is possible without a controller
    • Requires qualified installation and load assessment

    Safety and installation notes

    • After disconnecting the capacitor, wait at least 3 min, verify the absence of voltage, then short-circuit and earth the terminals. Only then may they be touched.
    • Reconnection is only permitted once the capacitor has discharged, so the controller's step switching delay must be no shorter than the discharge time.
    • Protect each step with gG fuses (typically 1.6–1.8 In, ~63 A in a 400 V network) and switch it with a capacitor-duty contactor (AC-6b).
    • When connected directly to a motor, the capacitor output must not exceed ~90 % of the motor's no-load reactive power, otherwise the motor may self-excite.
    • In networks with harmonics, measure THD before installation. Where distortion is significant, use detuned (reactor-protected) steps.
    • Leave ventilation clearances in the panel: the ambient temperature must not exceed +50 °C.
    • Do not use a capacitor that is bulging, leaking or mechanically damaged.

    Quick selection guide

    30 kvar @ 440 V
    ≈24.8 kvar @ 400 V
    3 phases | 50 Hz
    Ø116×300 mm | M16
    Suitable when you need:
    • a step for an automatic PFC panel in a 400 V network;
    • to replace an old capacitor with matching dimensions and mounting;
    • to reduce reactive energy charges and incoming supply current.
    Check before use:
    • the actual network voltage and the required kvar;
    • the harmonic level (THD): whether detuned reactors are needed;
    • the contactor type (AC-6b) and step protection;
    • the available space and ventilation in the panel.
    Important reminder: the capacitor does not replace the power factor controller, contactors or protection. It is only one step of a compensation system.

    FAQ

    How many kvar will this capacitor deliver in a 400 V network?
    About 24.8 kvar, because output is proportional to the square of the voltage: 30 × (400/440)².
    Why choose 440 V if the network is 400 V?
    The voltage margin reduces dielectric stress and extends service life when the voltage fluctuates or harmonics are present in the network.
    Can the terminals be touched immediately after disconnection?
    No. Wait at least 3 min, verify the absence of voltage, then short-circuit and earth the terminals.
    How can I check whether the capacitor has lost capacitance?
    Measure the phase currents during operation and compare them with the rated value (≈35.8 A @ 400 V): a significantly lower current indicates capacitance loss.
    Is it suitable for networks with variable frequency drives?
    Where harmonics are significant, the capacitor must be used with a detuned reactor, otherwise resonance and overheating may occur.
    Can it be switched with a standard contactor?
    Capacitor-duty contactors (AC-6b) are recommended for switched steps, as they limit the inrush current.

    Power factor correction capacitor 30 kvar | 440 V | three-phase

    Three-phase 440 V capacitor for power factor correction and reactive power compensation in low-voltage networks. In a 400 V network it delivers about 24.8 kvar, discharges to ≤ 75 V within 3 min after disconnection, and its Ø116×300 mm housing is suited to automatic PFC panels.

    Published: 2026-11-04 · Data verified against supplier specification: 2026-11-04

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • Alternative products

  • Subscribtion to new arrivals

    privacy policy

    Information